7.0   SPECIFICATIONS

The following specifications are typical at 25°C unless otherwise noted.

INPUT/OUTPUT

Panel Capacity

     @35°C .............................................................................. 450A per Bus

     @40°C .............................................................................. 400A per Bus

     @50°C .............................................................................. 320A per Bus

     @70°C .............................................................................. 200A per Bus

Configuration

 ..................................450A Single Bus with 1 to 20 Breakers

                                                  900A Dual Bus 1 to 10 Breakers Each Bus

Breaker Capacity 

1

  ................................................................. 2.5A to 200A

Voltage 

1

     24/48V Version ......................................................................21-60VDC

     12V Version ........................................................................10.5-15VDC

Polarity  ............................................ Neutral, Positive or Negative Ground

ALARMS

Alarm Indicator  ....................................................Dual Color LED Per Bus

LED Status Indication ........................................................ Green = Normal

                                                                                     Red = CB Trip Alarm

                                                                                            Off = No Power

Alarm Relays .............................................. Form C Contacts for each Bus

SAFETY

 .................... UL60950-1 2

nd

 Ed., CSA22.2 No. 60950-1 2

nd

 Ed.,

                                                                                       EN60950-1 2

nd

 Ed.

ENVIRONMENTAL

Operating Temp. Range ..................................................... -10°C to +70°C

Storage Temp. Range ........................................................ -40°C to + 85°C

Humidity........................................................ 0% to 95%, Non-Condensing

PHYSICAL SPECIFICATIONS

Case Material ......................................................................................Steel

Finish ............................................................................ Powder Coat Black

Case Dimensions, Inches (mm) ........................3.45 H x 17.16 W x 5.98 D

                                                                                  (87.6 x 435.9 x 151.9

Weight (approx.) ........................................................... 12.5 lbs. (5.67 kg.)

Rack Mounting......................................................................  19 or 23 Inch

CONNECTIONS

Input Connections...........................................................................Bus Bar

Output Connections ...............................................1/4-20 Stud, 2-hole lugs

Chassis Ground Connection..................................1/4-20 Stud, 2-hole lugs

Alarm Relay Connections ...................Spring Clamp Terminals,16-26AWG

Notes:

1. See ordering guide to specify.

8.0   FRONT PANEL DESCRIPTION

The front panel of the DPP2U, shown in Figure 3 below, consists of the A and B 

sides and a center section.  The A and B sides can each accommodate up to 10 field 

installed/replaceable hydraulic magnetic circuit breakers rated from 2.5A to 200A.  

The center section has two green/red LEDs, one for the A side (left) and the other 

for the B side (right).  At the bottom of this center section is a slot for a wallet and 

designator card.  This card permits the recording of each output circuit by number.

A - ALM

B - ALM

1

2

3

4

5

6

7

8

9

10

A BUS - 450A MAX/100A MAX PER CB

1

2

3

4

5

6

7

8

9

10

B BUS - 450A MAX/100A MAX PER CB

NO-C-NC  NO-C-NC

ALM-B

ALM-A

NO-C-NC  NO-C-NC

10

9

8

7

6

5

4

3

2

1

0.63

(16.0)

0.76

(19.3)

0.42

(10.7)

0.25
(6.4)

1/4-20 stud
length = 0.50 (12.7),
0.625 (15.88) spacing

1/4-20 stud

length = 0.38 (9.7),

0.625 (15.88) spacing

0.57

(14.5)

0.37
(9.4)

0.90

(22.9)

ø

 0.306 (7.8)

0.49 (12.5) x

0.31 (7.9) slot

3.50

(88.9)

1.25

(31.8)

5.98

(151.9)

0.60

(15.2)

17.16

(435.9)

0.76

(19.3)

1.725

(43.82)

0.56

(14.2)

0.21
(5.3)

1.13

(28.7)

0.22
(5.6)

3.45

(87.6)

A - BUS OUTPUT FEED

B - BUS OUTPUT FEED

A - BUS RETURN

B - BUS RETURN

B - BUS FEED BREAKERS

A - BUS FEED BREAKERS

Alarm connector

Chassis GND

(1/4-20 THREAD)

A - BUS INPUT

FEED

B - BUS INPUT

FEED

10

9

8

7

6

5

4

3

2

1

Shorting Bus (-S Models)

OUTLINE OF SAFETY COVER

(blue dotted line)

4.60

(116.8)

0.625

(15.88)

0.500

(12.70)

0.750

(19.05)

4.642

(117.91)

Figure 3.  Front Panel View

Содержание DPP2U Series

Страница 1: ...TRIBUTION PANELS Manual No DPP2U MAN Rev 5 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Rights Res...

Страница 2: ...TION 4 2 0 FEATURES 4 3 0 PRODUCT LINE 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0 FRONT PANEL DESCRIPTION 8 9 0 BACK PANEL DESCRIP...

Страница 3: ...2U DC Power Distribution Panel 4 Figure 2 Block Diagram 7 Figure 3 Front Panel View 8 Figure 4 Back Panel View 9 Figure 5 Input Bus Bar Detail 9 Figure 6 Output Barrier Strip Detail 10 Figure 7 Alarm...

Страница 4: ...e up to 20 breakers single bus 450Aor 10A 10B 450A 450Adistribution and alarm capabilities The A and B sections of the dual bus panel are fully isolated can be separately configured for 12 or 24 48 vo...

Страница 5: ...T NUMBER 2 5 348 1441 0020 50 348 1441 0500 5 348 1441 0050 60 348 1441 0600 10 348 1441 0100 80 348 1441 0800 15 348 1441 0150 100 348 1441 1000 20 348 1441 0200 125 2 775 1524 0000 25 348 1441 0250...

Страница 6: ...this Distribution Panels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to the Distribution...

Страница 7: ...CUIT BREAKERS BATT BATT INPUT RET INPUT RET HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR LOADS LOADS 1 2 3 N A SIDE ALARM CIRCUITS B SIDE ALARM CIRCUITS A SIDE B SIDE S...

Страница 8: ...ugs Alarm Relay Connections Spring Clamp Terminals 16 26AWG Notes 1 See ordering guide to specify 8 0 FRONT PANEL DESCRIPTION The front panel of the DPP2U shown in Figure 3 below consists of the A and...

Страница 9: ...16 0 0 76 19 3 0 42 10 7 6 4 1 4 20 stud length 0 50 12 7 0 625 15 88 spacing 1 4 20 stud length 0 38 9 7 0 625 15 88 spacing 0 57 14 5 0 37 9 4 0 90 22 9 0 306 7 8 0 49 12 5 x 0 31 7 9 slot 3 50 88 9...

Страница 10: ...rear All connections use 1 4 20 threaded studs and are rated up to 100 amperes Maximum wire size is 2AWG UNIPOWER recommends using FLEX wire with either Panduit LCDXN2 14A E or LCDXN2 14AF E 90deg an...

Страница 11: ...onnection is made via two Phoenix Contact spring clamp terminal blocks J3 is for the Form C relay contact of side B and J4 is for the Form C relay contact of side B Terminals 1 2 and 3 viewed from lef...

Страница 12: ...0 57 14 5 0 37 9 4 0 90 22 9 0 306 7 8 0 49 12 5 x 0 31 7 9 slot 3 50 88 9 1 25 31 8 5 98 151 9 0 60 15 2 0 76 19 3 1 725 43 82 0 56 14 2 0 21 5 3 1 13 28 7 0 22 5 6 3 45 87 6 B B A Chassis GND 1 4 20...

Страница 13: ...here is evidence of damage do not attempt to test the unit The freight carrier should be notified immediately and a claim for the cost of the rectifier system should be filed with the carrier for dire...

Страница 14: ...eliably grounded 12VDC to 48VDC SELV source b The branch circuit over current protection shall be sized appropriate to the input current and shall not exceed 600A c Use minimum 350Kmcm copper conducto...

Страница 15: ...nput connections to the distribution panel and output connections to the load before operating the panel Reverse connections will not harm the distribution panel which is POLARITY NEUTRAL but may caus...

Страница 16: ...remove the cover plate undo the two knurled retaining screws at the left and right side of the unit and pull forward 12 2 Removing a breaker or blanking panel To remove a breaker pull the toggle swit...

Страница 17: ...l is rated for continuous operation at a maximum input of 450A per side 35C max 400A per side 40C max 320A per side 50C max and 200A per side 70C max 12 5 Connecting or disconnecting load circuits In...

Страница 18: ...n J4 measure the resistance between pins 1 and 2 This should read open Measure the resistance between pins 2 and 3 This should read short 13 5 On the A side trip circuit breaker no 1 The A side LED sh...

Страница 19: ...LLC 65 Industrial Park Rd Dunlap TN 37327 United States Manufacturing facility UNIPOWER Slovakia SRO ZLATOVSKA 1279 Business Center 22 91105 Trencin Slovakia Phone 1 954 346 2442 Toll Free 1 800 440...

Отзывы: