background image

Page 32

P O W E R I N G   T E C H N O L O G Y

Manual No. PM110-6500-00 rev-2a

PM110-6500-00-rev2a-0117.indd

5.8 Commissioning record

This is a step-by-step commissioning record for easy commissioning of Power Supply 

Systems.  Do not continue if any faults occur during this commissioning.  The checkpoints 

are to be considered as a minimum for commissioning of the system.

Checked 

(

)

Result

1

Check that the rack is level

2

Check that all breakers are turned to “off” position 

and that no rectifiers are mounted in the system.

3

Connect AC, and measure voltage on the outlet. 

AC Input 1:…....VAC
AC Input 2:........VAC

4

Mount the rest of the rectifiers

5

After connection of the battery, turn the battery 

breaker  “on”  and  the  controller  (if  fitted)  will 

read the battery current.

6

Check  float  charge,  U1,  and  boost  charge,  U2. 

It is to be adjusted according to the battery 

manufacturers requirements.

U1:…….VDC
U2:.........VDC

7

Check temperature compensation. It is to be 

adjusted according to the battery manufacture 

requirements.
Check temperature read from the controller 

compared to the ambient temperature.

Comp.:…….V/10°C

Read off:………°C

8

Check symmetry measurement and set number 

of battery strings according to actual number of 

supervised battery strings in the system.

Number: ….
Alarm limit:……

9

Check alarm transmission by running an alarm 

test.

  

Table 5-2 Commissioning Record

Содержание Aspiro 2U Enclosure

Страница 1: ...mber PM110 6500 00 rev2a 2017 UNIPOWER LLC All Rights Reserved PM110 6500 00 rev2a 0117 indd UNIPOWER LLC 3900 Coral Ridge Drive Coral Springs Florida 33065 USA sales unipowerco com North America 1 95...

Страница 2: ...this product manual are the property of their respective trademark holders These trademark holders are not affiliated with UNIPOWER LLC or our products They do not sponsor or endorse our products LIMI...

Страница 3: ...BD 11 2 4 4 Rectifier Module 12 Chapter 3 System Safety 13 3 1 Safety Warnings and Guidelines 13 3 1 1 System Markings 13 3 1 2 Safety Recommendations 13 3 1 3 Installation Warning 13 3 1 4 Electrical...

Страница 4: ...missioning Overview 28 5 2 Tools and Test Equipment 28 5 2 1 Tools List 28 5 2 2 Test Equipment 28 5 3 Preparation 28 5 4 Commissioning procedure 29 5 5 Test of output voltage 30 5 5 1 Float charge U1...

Страница 5: ...l Connection Detail 24 Figure 4 7 Load and Battery Connections Rear View 24 Figure 4 8 Battery Cable Detail 25 Figure 4 9 Symmetry Measurement for illustration only 26 Figure 4 10 Temperature Sensor C...

Страница 6: ...nstallation and installing the power system This manual assumes that the technician has an understanding of power systems in general and understands safety procedures for working around AC and DC volt...

Страница 7: ...r XPGe12 48 1200 W Rectifier DB22 Distribution Drawer 4 x load 1 x battery 1 4 Feedback Support For technical support or feedback please visit http www unipowerco com contact Alternatively email techn...

Страница 8: ...de wide input operating range wide operating temperature full self protection and three LEDs for immediate rectifier status indication The power system can be managed locally through messages and alar...

Страница 9: ...Modem using PowCom software Visual Indication Green LED System On Yellow LED Message s Red LED Alarm s Analog Inputs 12 x voltage inputs range 0 100VDC used for symmetry inputs Analog Outputs 4 x pot...

Страница 10: ...rear to front Protection Short circuit proof automatic current limiting selective shutdown of modules at excessive output voltage Alarms High output voltage shutdown Low voltage module failure LED In...

Страница 11: ...f 2 4 2 DC Distribution DC Distribution consists of 1 x 40A battery and 4 x 15A load breakers The distribution unit is designed for switching the battery and load on and off The battery and load break...

Страница 12: ...monitoring through an internal microprocessor giving up to the second updates to the system controller and companion rectifiers This guarantees tightly controlled load sharing among rectifiers and pr...

Страница 13: ...s and aisles Tools present a tripping hazard in confined areas Keep the system area clear and dust free during and after the installation Always know the location of emergency shut off switches in cas...

Страница 14: ...endations for working near the Power System WARNING Observe low voltage safety precautions before attempting to work on the system when power is connected Potentially lethal voltages are present withi...

Страница 15: ...dential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio comm...

Страница 16: ...burn these batteries may result in an explosion and the generation of toxic fumes Should a lead acid battery suffer damage it must be moved into a well ventilated area Contact with the corrosive flui...

Страница 17: ...that may be permanently damaged by the discharge of electrostatic charges encountered in routine handling testing and transportation 3 2 4 Traceability CAUTION Units are labeled with permanently atta...

Страница 18: ...duction This chapter provides detailed instructions for installing the Aspiro 1U Power System 4 2 Unpacking Check that the received equipment is in accordance with the packing list Ensure that the cab...

Страница 19: ...to be sufficient clearance at the front for rectifier installation and at the rear for connections When using side mains and DC connectors sufficient space should be allowed for access in this case 1...

Страница 20: ...em Mounting 19 mount NOTE Mounting hardware is not supplied with the system 4 5 Rear Connections All cable connections for the Aspiro system are available at the rear of the system see Figure 4 3 CAUT...

Страница 21: ...ed on the right rear side of the system shown in Figure 4 4 2 1 _ _ BATTERY _ AC INPUT 2 AC INPUT 1 BATTERY AC INPUTS UTS _ Figure 4 4 Mains Connection viewed from rear NOTE AC inputs are independent...

Страница 22: ...Voltage Inputs 1 12 can be reconfigured as external analog inputs The pin description detail for all signal connections is shown in Figure 4 5 Alarm connections are Form C relays and can be monitored...

Страница 23: ...18 0V Sense 5V 0V Sense 5V Battery Temp Ambient Temp Alarm 4 C Alarm 4 NC Alarm 4 NO Alarm 1 C Alarm 1 NC Alarm 1 NO Alarm 2 C Alarm 2 NC Alarm 2 NO Alarm 3 C Alarm 3 NC Alarm 3 NO Multipurpose 1 Mult...

Страница 24: ...nsert the connector back into the terminal block Maximum cable size is 1 5mm2 Maximum torque required for tightening the screw is 0 25Nm Figure 4 6 Signal Connection Detail 4 5 4 DC Load Connections L...

Страница 25: ...en to the system Battery cable ZLH 00254 01 is custom design for the Aspiro enclosure connections are available at the rear of the system adjacent to the load connections see Figure 4 8 To connect 1 C...

Страница 26: ...t is not delivered with the system NOTE See Figures 4 5 and 4 6 for connection to the system 4 5 7 Temperature Sensor Connection Temperature sensor connections for supervising battery temperature and...

Страница 27: ...P O W E R I N G T E C H N O L O G Y Manual No PM110 6500 00 rev 2a PM110 6500 00 rev2a 0117 indd Temp Sensor Figure 4 10 Temperature Sensor Connection NOTE See Figures 4 5 and 4 6 for connection to th...

Страница 28: ...SAFETY REGULATIONS If there are any difficulties in increasing the voltage to alarm level the alarm level can be adjusted to a lower level 5 2 Tools and Test Equipment 5 2 1 Tools List The essential...

Страница 29: ...If the voltage is negative change over the connection of the gray and black battery cables to the batteries 5 Plug in the AC power cord 6 Plug in the rectifier modules starting from the leftmost posi...

Страница 30: ...ise ordered the default output voltage is factory preset to 53 5V The total voltage has to be in accordance to the number of battery cells Please verify number of cells and the battery manufacturers r...

Страница 31: ...o make sure that it is in accordance with the battery manufacturer s recommendations For systems with battery temp probe cable Temperaturecompensation is factory preset Check that the temp probe is ac...

Страница 32: ...AC Input 1 VAC AC Input 2 VAC 4 Mount the rest of the rectifiers 5 After connection of the battery turn the battery breaker on and the controller if fitted will read the battery current 6 Check float...

Страница 33: ...g This troubleshooting chapter helps to determine the cause of the problem and suggests possible repair solutions If the first step of the recommendation does not solve the problem continue to the nex...

Страница 34: ...igh Voltage AC voltage rises above the set limit Verify the High AC voltage limit Verify the AC Input voltage Module Failure Faulty module AC OFF on a single rectifier if more than one rectifier is in...

Страница 35: ...fy there is no short circuit in load cabling Reset the breaker if it trips again there is a problem with the load or a breaker itself Return the system to the factory for repair Battery Fuse Failure T...

Страница 36: ...emperature is greater than 60 C Verify the temperature probe connection Verify the internal external temperature via controller front panel Replace the faulty probe with a new one Identify the root ca...

Страница 37: ...blanking panel using a flat or Pozidrive screwdriver as appropriate see Figure 7 1 Figure 7 1 Unlocking the Controller Removing the Blanking Panel 2 If removing a controller out it of the shelf as sh...

Страница 38: ...XR04 48 XR08 48 Replacement To replace an XR04 48 or XR08 48 rectifier follow the steps below 1 Loosen the screw on the rectifier front panel using a screwdriver Figure 7 3 1 2 Push the release sprin...

Страница 39: ...t Figure 7 4 1 2 Once unlocked pull both handles down and remove the rectifier from the slot Figure 7 4 2 3 Replace rectifier Make sure that the rectifier handle is in OPEN position forms 35 40 angle...

Страница 40: ...8 7 Alarm4 NC Alarm3 NO Alarm3 C Alarm4 NO Alarm4 C Alarm3 NC 15 14 13 Digital In2 Digital Out1 Digital In1 18 17 16 V sys V sys Digital Out2 X9 X10 F1 F1 F2 F3 F4 F2 F3 F4 8 7 6 5 4 3 2 1 X6 2 1 Bat...

Страница 41: ...EAR VIEW EXTERNAL CABLES ARE NOT INCLUDED IN 111 6500 00 SYSTEM CUSTOMER SPECIFIED CABLE UNIPOWER PN 262 8700 01 VENDOR TE 640713 2 UNIPOWER PN 262 8700 10 VENDOR TE 770246 3 FOR 12 10 GAUGE WIRE UNIP...

Отзывы: