2
PRE-INSTALLATION
Before proceeding with the battery installation, it
is necessary to check the compatibility between the
battery and the application it will be used.
What to check before installation:
•
Read the battery data sheet again.
•
Check the maximum absorption of your load and
compare with the electrical characteristics of the battery
(see technical data sheet).
•
Verify that the size, weight and length of the battery
cables are compatible with your application.
•
Check that the temperatures of the environment in
where the battery will be installed is within the limits
indicated in the technical data sheet.
Dimostrative example of ZLI012051 battery data sheet
Dimostrative example of ZLI012051 battery data sheet
Corrente costante di scarica /
Constant discharge current
100A
Corrente impulsiva di scarica /
Impulse discharge current
Max 200A per 15”
Max 400A per 3”
Corrente max di carica consigliata
Max recommended charging current
50A
Corrente impulsiva di carica /
Impulse charge current
> 80A per 10''
Tensione di carica consigliata /
Recommended charging voltage
13.9V
Tensione di carica massima /
Maximum charging voltage
14.6V
Temperatura di scarica massima
Maximum discharge temperature
-15°C / +60°C
Temperatura di scarica consigliata
Recommended discharge temperature
-10°C / +45°C
Temperatura di carica massima /
Maximum charge temperature
0°C / +60°C
Temperatura di carica consigliata
Recommended charge temperature
+5°C / +40°C
INSTALLATION / USE
The battery has two cables, one red (positive) and a
black one (negative), with which it will be possible to
load and unload it also.
The battery is supplied without connector, available
only on request.
Use a connector with adequate capacity for the
application.
•
During installation, make sure that the battery is off.
•
Respect the polarities (red +, black -).
•
Use cables with a suitable section for the application,
if necessary, ask the manufacturer.
•
The favourite mounting position is the spontaneous
one with handles on top. For any different positions
ask for manufacturer's authorization.
•
Secure the battery in case of movement or
vibration. Use the appropiate
threaded inserts (1)
provided on the container.
During use:
•
It is strongly recommended that you turn on the
battery first and then the load.
•
Connect/disconnect only when the battery is not
used (no flashing led).
•
The battery has an
ON/OFF button (2)
for
switching the BMS on and off (in OFF there is no
voltage on the poles).
•
Five LEDs
(3)
indicate the level of charge (S.o.C.) and
the battery status.
•
One connector (4)
to plug: the specific display
to view all the battery parameters (RS485).
2.ON/OFF
4.RS485
6.Display
3.S.o.C. indicators