NOVA AND NOVA PRO
Measurements
32
•
Test current of 5
I
ΔN
,
•
Test current started with the positive half-wave at 0
0
.
Measurement normally trips an RCD within allowed time period. The following menu
is displayed:
Figure 5-22: Step 3 RCD autotest results
After re-activating the RCD the autotest sequence automatically proceeds with
step 4.
4.
Trip-out time measurement with the following measurement parameters:
•
Test current of 5
I
ΔN
,
•
Test current started with the negative half-wave at 180
0
.
Measurement normally trips an RCD within allowed time period. The following menu
is displayed:
Figure 5-23: Step 4 RCD autotest results
After re-activating the RCD the autotest sequence automatically proceeds with
step 5.
5.
Trip-out time measurement with the following measurement parameters:
•
Test current of ½
I
ΔN
,
•
Test current started with the positive half-wave at 0
0
.