PART I: SPECIFICATIONS
7
Technical specifications
NOTE:
Choosing the nozzle for light oil, consider Hi equal to 42.7 MJ/kg.
BURNERS
RG91
RG92
RG93
Output
min - max kW
698 - 2093
849 - 2558
550 - 4100
Light oil rate
min - max kg/h
59 - 176
72 - 215
46 - 345
Fuel
Light oil
Viscosity
cSt @ 40 °C
2 - 7,4
Density
kg/m
3
840
Oil train pressure inlet
bar max
4
Power supply
400V 3N ~ 50Hz
Fan motor
kW
4
5,5
7,5
Pump motor
kW
1,1
1,1
1,1
Total power consumption
kW
5,6
7,
1
9,
1
Index of protection
IP40
Approx. weight
kg
220
220
230
Operation
Progressive - Fully modulating
Operating temperature
°C
-10 ÷ +50
Storage temperature
°C
-20 ÷ +60
Working service *
Continuous
BURNERS
RG510
RG515
RG520
RG525
Output
min - max kW
1314 - 3953
1628 - 4884
2326 - 6977
2000 - 8000
Fuel
Light oil
Light oil rate
min - max kg/h
111 - 333
137 - 411
196 - 588
169 - 674
Viscosity
cSt @ 40 °C
2 - 7,4
Density
kg/m
3
840
Oil train pressure inlet
bar max
4
Power supply
400V 3N ~ 50Hz
Electric motor
kW
7,5
11
15
18,5
Pump motor
kW
1,1
1,5
1,5
3
Total power consumption
kW
9,1
13
17
22
Operation
Progressive - Fully modulating
Index of protection
IP40
Operating temperature
°C
-10 ÷ +50
Storage temperature
°C
-20 ÷ +60
Working service
Continuous
WARNING:
Burners are suitable only for indoor operation with a maximum relative humidity of 80%
Содержание RG91
Страница 41: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 48: ...8...
Страница 49: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 52: ...12 2 2 LMV5x program structure...
Страница 79: ...39...
Страница 86: ......
Страница 87: ......
Страница 88: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 90: ...Annex1 Example for motor cable...
Страница 91: ......
Страница 92: ...Annex 2 Example for sensor cable...
Страница 93: ......
Страница 94: ......
Страница 98: ......