PART IV: MAINTENANCE
37
5.5
Matching the combustion heads and the control boxes
The combustion head is made of four heads: one is provided with a detection electrode connected to the Siemens LMV control box ;
the other three heads are provided with electrodes connected to the Krom-Schroeder IFW15 flame detectors .
5.6 Checking the detection current (natural gas)
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
Device
Flame detector
Minimum detection signal
Siemens LMV2x/3x
Ionization probe
4 µA (values on display: 30%)
C
B
D
A
A
B
C
D
Protective earth PE
Ionization probe (ION)
QRB.../ QRC... signal voltage
QRB... GND
1
2
3
4
5
L
X10-05
Detection electrode
R91, R92, R93, R515
Ignition electrode
Earth electrode
Содержание R91
Страница 16: ...PART II INSTALLATION 16 Fig 5 H a 0 50 mm...
Страница 46: ......
Страница 47: ......
Страница 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 56: ...8 Parameters level heating engineer...
Страница 98: ...50 ERROR CODE TABLE...
Страница 99: ...51...
Страница 100: ...52...
Страница 101: ...53...
Страница 102: ...54...
Страница 103: ...55...
Страница 104: ...56...
Страница 105: ...57...
Страница 106: ...58...
Страница 107: ...59...
Страница 108: ...60...
Страница 109: ...61...
Страница 110: ...62...
Страница 111: ...63...
Страница 112: ...64...
Страница 114: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 117: ......
Страница 118: ......
Страница 119: ......