![Unigas PN91 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/unigas/pn91/pn91_manual-of-installation-use-maintenance_4060607026.webp)
C.I.B. UNIGAS - M039196CC
26
Adjustment by the Siemens SQL33.. actuator
1
with the electrical panel open, prime the oil pump acting directly on the related contactor (see next picture): check the pump motor
rotation (see “Fan-pump motor direction” on page 10) and keep pressed for some seconds until the oil circuit is charged;
2
bleed the air from the
M
pressure gauge port (Fig. 21) by loosing the cap without removing it, then release the contactor.
Fig. 21
3
Before starting the burner up, drive the high flame actuator microswitch matching the low flame one (in order to let the burner ope-
rates at the lowest output) to safely achieve the high flame stage.
4
Turn the burner on by means of its main switch
A
(see next picture): if the burner locks (LED
B
on in the control panel) press the
RESET button (
C
) - see chapter “OPERATION”.
5
Start the burner up by means of the thermostat series and wait until the pre-purge phase comes to end and that burner starts up;
6
the burner starts up with the actuator on the ignition position, set it to the
MAN
(manual mode), by the
MAN/AUTO
selector (ignition
position= read on the air damper index
ID
);
7
disconnect the
TAB
thermostat removing the wire from the terminal no. 6 or by setting MAN on the RWF40 modulator or by setting
0 by means of the
CMF
switch (only for fully-modulating burners);
8
set the actuator to the manual mode (MAN) by means of the MAN/AUTO switch (see next pictures).
9
manually drive the adjusting cam
SV
to the high flame position and set the actuator to the AUTO mode (by means of the related
switch - see picture) to lock the adjusting cam.
Suntec TA..
Danfoss KSM..
SQL33.. actuator cams
AB = High flame
BF = Low flame
B = plastic cam
G = cam locking lever
VR
M
M
VR
A
C
B
MAN
AUT
AB
B
G
BF
Содержание PN91
Страница 18: ...C I B UNIGAS M039196CC 18 HYDRAULIC DIAGRAMS Fig 13 Hydraulic diagram 3ID0023 Single burner configuration...
Страница 19: ...C I B UNIGAS M039196CC 19 Fig 14 Hydraulic diagram 3ID0014 Two or more burners configuration...
Страница 37: ...C I B UNIGAS M039196CC 37...
Страница 45: ......
Страница 46: ......
Страница 47: ......