PART II: INSTALLATION
18
Mounting VD-R & PS-...
1. Gas pressure regulation is possible with VD-R and PS pressure sensor only.
WARNING! For US/CN installation, the output pressure must be monitoried by min. and max. pressure switches set
to +/- 20% of the setpoint.
2. Mounting on pipe. Sensor position: 5x DN according to MBE. Pipe fitting with female thread size ¼, mount sensor with
seal, observe torque.
3. The pressure sensor includes a vent limiter according to UL 353 and ANSI Z21.18/CSA 6.3. No venting required in loca-
tions where vent limiters are accepted by the jurisdiction.
4. Only PS pressure sensors specified by DUNGS are authorised to be connected to the VD-R‘s M12 interface.
5. Only PS cables specified by DUNGS are authorised to be used to connect the PS to the VD-R. Max. cable length 3 m.
The actuator
VD-V
does not need any adjustment (funzione
ON-OFF)
The actuator
VD-R
It must be combined with the
PS
sensor
(include regolatore di pressione)
The
PS sensor
chosen based on the necessary pressure
(there are 3 models)
Actuator
VD-R
Actuator
VD-V
M12 x 5 Pin
VD-R + PS
Содержание LMV2 Series
Страница 38: ......
Страница 39: ......
Страница 41: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 48: ...8 Parameters level heating engineer...
Страница 90: ...50 ERROR CODE TABLE...
Страница 91: ...51...
Страница 92: ...52...
Страница 93: ...53...
Страница 94: ...54...
Страница 95: ...55...
Страница 96: ...56...
Страница 97: ...57...
Страница 98: ...58...
Страница 99: ...59...
Страница 100: ...60...
Страница 101: ...61...
Страница 102: ...62...
Страница 103: ...63...
Страница 104: ...64...
Страница 106: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 109: ......
Страница 110: ......
Страница 111: ......