background image

15

ELECTRICAL CONNECTIONS

To execute the electrical connections, proceed as follows:
find the pulg or the plugs, according to the model, that comes out from the burnrer:

7 pins plug for the power supply (for all models);

4 pins plug (double-stage burners);

Connectors identification

Respect the basic safety rules. make sure of the connection to the earthing system. do not reverse the phase and 

neutral connections. fit a differential thermal magnet switch adequate for connection to the mains.
ATTENTION: before executing the electrical connections, pay attention to turn the plant’s switch to OFF and be 

sure that the burner’s main switch is in 0 position (OFF) too. Read carefully the chapter “WARNINGS”, and the 

“Electrical connections” section.

WARNING: if the cable that connects the thermostats and the control box should be longer than 3 meters, insert a 

sectioning relay following the attached electrical wiring diagram.

Burner power supply connector

HIGH/LOW flame connector

Single stage burner connector

Double-stage burner connectors

7-pins connector

7-pins and 4-pins connectors

Key

C1

LOW FLAME TIME METER

C2

HIGH FLAME TIME METER

FU1

FAN MOTOR LINE FUSE

FU3

LINE FUSE

IL

BURNER LINE SWITCH

IM

FAN MOTOR LINE SWITCH

KM1

FAN MOTOR CONTACTOR

LAF

BURNER IN HIGH FLAME INDICATOR LIGHT

LB

INDICATOR LIGHT FOR BURNER LOCK-OUT

LBF

BURNER IN LOW FLAME SIGNALLING LAMP

MV

FAN MOTOR

ST

THERMOSTATS O PRESSURE SWITCHES SERIE

TAB

HIGH LOW FLAME THERMOSTAT/PRESSURE SWITCH

TS

SAFETY THERMOSTAT/PRESSURE SWITCH

CONN-MOTORE FAN MOTOR CONNECTOR
CONN-LINEA BURNER POWER SUPPLY CONNNECTOR
CONN-TAB HIGH-LOW FLAME CONNECTOR

($)

IF "TAB" USED REMOVE THE BRIDGE BETWEEN TERMINALS 

T6-T8

WARNING: the burner is fitted with a bridge between terminals T6 and T8 on CN2-TAB connector (external side link,

male connector); remove this bridge before thermostat connection.

Содержание LG70 L-.TN 10 Series

Страница 1: ...M039135CG Rev 6 2 07 2020 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES Idea Series Gas burners MANUAL OF INSTALLATION USE MAINTENANCE LG NG70 LGX NGX70 LG NG90...

Страница 2: ...e employed exclusively for the use for which it was designed Before connecting the burner make sure that the unit rating is the same as delivery mains electricity gas oil or other fuel Observe caution...

Страница 3: ...ixtures DIRECTIVES AND STANDARDS Gas burners European directives Regulation 2016 426 UE appliances burning gaseous fuels 2014 35 UE Low Tension Directive 2014 30 UE Electromagnetic compatibility Direc...

Страница 4: ...quipment of machi nes EN 60335 2 Electrical equipment of non electric appliances for house hold and similar purposes Safety requirements Burner data plate For the following information please refer to...

Страница 5: ...2 9 0 Gas pressure min max mbar see Note 2 Power supply 230V 1N ac 50 Hz Total power consumption kW 0 40 Electric motor kW 0 10 Protection IP40 Approx weight kg 14 Valves size Gas connection 3 8 Rp1...

Страница 6: ...upply 230V 1N ac 50 Hz Total power consumption kW 0 40 Electric motor kW 0 10 Protection IP40 Approx weight kg 14 Valves size Gas connection 3 8 Rp1 2 1 2 Rp1 2 1 2 Rp1 2 1 2 Rp1 2 Operation High low...

Страница 7: ...NL I2ELL DE I2Er FR Only for I2EK the appliance was configured for the appliance category K I2K and is suitable for the use of G and G distribution gases according to the specifications as included in...

Страница 8: ...8 299 78 5 NG70 L 1 2 443 34 157 287 410 365 75 291 80 95 99 162 218 M8 155 86 138 110 285 408 118 241 168 14 438 299 78 5 NG90 S 1 2 365 34 70 295 331 365 75 291 80 95 102 162 218 M8 155 86 138 110 2...

Страница 9: ...andard LGX NGX70 383 76 76 299 299 304 14 291 80 98 99 145 218 M8 153 96 120 108 296 296 130 130 167 7 438 291 Extended LGX NGX70 451 66 149 294 377 304 14 291 80 98 99 145 218 M8 153 96 120 108 292 3...

Страница 10: ...URE IN CCOMBUSTION CHAMBER mbar LG90 L TN kW LG90 L AB kW 1 0 5 0 0 5 1 1 5 2 2 5 3 20 30 40 50 60 70 80 1 0 5 0 0 5 1 1 5 2 2 5 3 10 20 30 40 50 60 70 80 1 0 5 0 0 5 1 1 5 2 2 5 3 30 40 50 60 70 80 9...

Страница 11: ...3 h GAS PRESSURE mbar NG90 M TN Gas rate Stm3 h NG90 M AB Gas rate Stm3 h L P G Burners GAS PRESSURE mbar LG70 L TN Gas rate Stm3 h LG70 L AB Gas rate Stm3 h 1 0 5 0 0 5 1 1 5 2 2 5 3 35 45 55 65 75 1...

Страница 12: ...f 22300 kcal Stm3 15 C 1013 mbar and a density of 2 14 kg Stm3 When the calorific value and the density change the pressure values should be adjusted accordingly 2 4 6 8 10 12 14 16 18 1 1 5 2 2 5 3 3...

Страница 13: ...lolts D completely 9 seal the space between the blast tube and the refractory lining with appropriate insulating material ceramic fibre cord or refractory cement Matching the burner to the boiler The...

Страница 14: ...Once the train is installed connect the gas valves group plug Fig 3 Key a Heat output in kW b Length of the flame tube in meters c Flame tube firing intensity in MW m3 d Combustion chamber diameter m...

Страница 15: ...ger than 3 meters insert a sectioning relay following the attached electrical wiring diagram Burner power supply connector HIGH LOW flame connector Single stage burner connector Double stage burner co...

Страница 16: ...or 230V phase phase without a neutral as fas as the Siemens LME2 control box the RC Siemens RC466890660 filter must be inserted between terminal 2 and the earth terminal on the board Key C Capacitor 2...

Страница 17: ...Measuring the gas pressure in the combustion head In order to measure the pressure in the combustion head insert the pressure gauge probes one into the generator s pressure outlet Fig 4 2 to get the p...

Страница 18: ...lorific value of 22300 kcal Stm3 15 C 1013 mbar and a density of 2 14 kg Stm3 When the calorific value and the density change the pressure values should be adjusted accordingly Gas pressure in combust...

Страница 19: ...e maximum output high flame first by means of the air damper and the valves group pressure stabiliser respectively Gas pressure in combustion head LG70 L Gas rate Stm3 h LG90 L Gas rate Stm3 h ATTENTI...

Страница 20: ...ards the MIN position rotating clockwise the VRT screw Fig 5 go on adjusting air and gas flow rates check continuosly the flue gas analisys as to avoid combustion with little air dose the air accordin...

Страница 21: ...u smetns are accomplished close screw A Fig 8 in the measuring nozzle The air flow rate can be adjusted by means of the V screw The air damper position is shown on the graduated indes I where 0 refe r...

Страница 22: ...g the round plate C turn clockwise to decrease the gas rate or counterclockwise to increase it The index S shows the opening angle of the butterfly valve 8 If it was necessary to change the low flame...

Страница 23: ...follows Be sure that the filter is clean Remove the transparent plastic cap While the burner is operating at the maximum output test the gas pressure on the pressure port of the minimum gas pressure s...

Страница 24: ...L LEADS OPENING THE GENERATOR DOOR DISMANTLING OF PART OF THE BURNER NEVER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE OPERATE ONLY THE MAIN SWITCH WHICH THROUGH ITS EASY ACCESSIBILITY AND RAPIDITY...

Страница 25: ...DLE 405 412 Check the filter at least once a year Change the filter if the pressure difference between pressure connection 1 and 3 Fig 16 Fig 17 is p 10 mbar Change the filter if the pressure differen...

Страница 26: ...on head To remove the combustion head proceed as follows 1 remove the burner cover 2 unscrew the VT fixing screws 3 disconnect the ignition cable CA unscrew the fixing nuts D and shift the combustion...

Страница 27: ...ue shown check the position of the detection electrode the electrical contacts and if necessary replace the detection electrode Seasonal stop To stop the burner in the seasonal stop proceed as follows...

Страница 28: ...MAIN SWITCH OPEN LACK OF GAS MAXIMUM GAS PRESSURE SWITCH DEFECTIVE IF PROVIDED THERMOSTATS PRESSURE SWITCHES DEFECTIVE OVERLOAD TRIPPED INTERVENTION AUXILIARIES FUSE INTERRUPTED CONTROL BOX FAULTY DEF...

Страница 29: ...EAD 8 2 FLANGE 7 2 AIR DAMPER ASS Y 8 3 BUTTERFLY VALVE INDEX ASS Y 7 3 FAN WHEEL 8 4 INSPECTION GLASS 7 4 PRESSURE SWITCH 8 5 BUTTERFLY VALVE 7 5 MOTOR 8 6 COMBUSTION HEAD 7 6 AIR DAMPER INDEX ASS Y...

Страница 30: ...30...

Страница 31: ...lamp LGB LMG LME SIEMENS control box MA Burner power supply terminal board MV Fan motor N Neutral PA Air pressure switch PG Minimum gas pressure switch ST Thermostats or pressure switches group TA Ign...

Страница 32: ...flame indicator light LGB22 LMG22 LME22 SIEMENS control box MV Fan motor PA Air pressure switch PG Minimum gas pressure switch STA4 5B0 37 63N30L BERGER actuator ST Thermostats or pressure switches s...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ...with the LME22 fan motor M will be started tw Waiting time During the waiting time air pressure monitor LP and flame relay FR are tested for correct contact positions t11 Programmed opening time for a...

Страница 40: ...d time for air pressure signal t11 Programmed opening time for actuator SA t12 Programmed closing time for actuator SA SB R W GP AL M LP BV1 Z FS tw t1 t3n TSA t4 7 t10 EK2 12 10 3 7 4 6 1 8 t3 A B B...

Страница 41: ...W Limit thermostat pressure switch Z Ignition transformer LME22 connection diagram NT PC control RESET EK FSV ION 1 2 3 M 4 BV1 5 7 Z 10 AL T 12 R W GP STB 9 7101 24 0606 pa 6 LP 8 EK 11 K1 K2 1 K3 K...

Страница 42: ...r code table the device repeats the blinks for regular intervals During diagnostics the control outputs are deactivated the burner remains shut down external fault indication is deactivated fault stat...

Страница 43: ......

Страница 44: ...ia L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors a...

Страница 45: ......

Страница 46: ......

Отзывы: