C.I.B. UNIGAS - M039140CE
39
OPERATION
z
Choose the typer of fuel by turning the
A
switch, on the burner control panel.
CAUTION:
if the fuel chosen is light oil, be sure the cutoff valves on the feed and return pipes are open.
z
Check the control box is not locked (signalling light
O
, on); if so, reset it by means of the pushbutton
C
.
z
Check the series of thermostats and pressure switches turn the burner to on.
Gas operation
z
Check the gas feeding pressure is sufficient (signalling lamp
G
on).
Burners provided with gas proving system:
the gas proving system test begins; when the test is performed the proving system LED
turns on. At the end of the test, the burner staring cycle begins: in case of leakage in a valve, the gas proving system stops the burner
and the lamp
E
turns on. Reset it, by means of the reset pushbutton on the device, in burners with VPS504 (pushbutton
LB
in picture),
or by the
D
pushbutton on the burner panel if this one is fitted with LDU11 proving system.
NOTE:
if the burner is fitted with Dungs VPS504, the pre-purgue phase starts once the gas proving system is successfully performed.
Since the pre-purgue phase must be carried out with the maximum air rate, the control box drives the actuator opening and when the
maximum opening position is achieved, the pre-purge time counting starts.
z
At the end of the pre-purge time, the actuator drives the complete closing (ignition with gas position) and, as this is achieved the
ignition transformer is energised (LED
L
is on).
z
Few seconds after the gas valves opening, the transformer is de-energised and lamp
L
turns off.
z
The burner is now operating, meanwhile the actuator goes to the high flame position and, after some seconds, the two-stage ope-
ration begins; the burner is driven automatically to high flame or low flame, according to the plant requirements.
Operation in high or low flame is signalled by lamp
N
on the frontal panel.
Light oil operation
z
The fan motor starts and the pre-purge phase as well. Since the pre-purge phase must be carried out at the maximum air rate, the
control box drives the actuator opening and when the maximum opening position is reached, the pre-purge time counting starts.
z
At the end of the pre-purge time, the actuator is in the light oil ignition position: the ignition transformer is energised (lamp
L
on).
Few seconds after the light oil valves opening, the transformer is de-energised and lamp
L
turns off.
z
The burner is now operating, meanwhile the actuator goes to the high flame position; after some seconds, the two-stage operation
begins; the burner is driven automatically to high flame or low flame, according to the plant requirements.
Operation in high or low flame is signalled by LED
N
on the burner control panel.
Modulating burners:
they are provided with the Siemens RWF40 output controller (
Q
-see next picture). As for the controller operation
see the related manual.
ATTENTION:
before starting the burner up, be sure that the manual cutoff valves are open and check that the
pressure upstream the gas train complies the value quoted on paragraph “Technical specifications”. Read care-
fully the “WARNINGS” chapter in this manual.
VPS504
LC
LB
Содержание HP91A
Страница 45: ...C I B UNIGAS M039140CE 45 ...
Страница 53: ...E039140CA Rev 0 12 2009 WIRING DIAGRAMS ...
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 81: ......
Страница 82: ......
Страница 83: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......