PART I: SPECIFICATIONS
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Fuel
The burner technical specifications, described in this manual, refer to natural gas (calorific net value Hi = 9,45 kWh/Stm
3
, density
ρ
=
0,717 Kg/Stm
3
). For different fuel such as LPG, town gas and biogas, multiply the values of flow and pressure by th corrective factors
shown in the table below.
For example, to obtain the flow and pressure values for the biogas:
Type
H500X
Model
M-.
MD.
SR.
*.
A. 1.
65.
ES
/
EF
.FGR
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
1 BURNER TYPE
H365X, H440X, H500X
2 FUEL
B- Biogas
C - Off-gas
L - LPG
M - Natural gas
3 OPERATION (Available versions)
MD - Fully modulating
4 BLAST TUBE
S - Standard L - Extended
SR = Standard blast tube + ABS polymer (silenced) air intake
LR = Extended blast tube + ABS polymer (silenced) air intake
LP = Extended blast tube + aluminum air intake
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard
Y - Special
7 EQUIPMENT
1 = 2 gas gas proving system
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION
50 = Rp2 65 = DN65
80 = DN80 100 = DN100
9 MICRO-PROCESSOR CONTROL
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
EI = with no O
2
trim control, with VSD control
EK = with O
2
trim control, with VSD control
9 FGR:Flue gas recirculation
EF = Medium-large burners complete with electronic cam LMV5x and tem-
perature-compensated flue gas recirculation FGR, without O
2
monito-
ring, without inverter.
EG = Medium-large burners complete with electronic cam, inverter and
temperature-compensated flue gas recirculation, without O
2
monito-
ring
ER = Medium-large burners complete with electronic cam, inverter and tem-
perature-compensated flue gas recirculation, with O
2
monitornig
10 FGR:
FGR:Flue gas recirculation
Fuel
Hi
(KWh/Stm
3
)
ρ
(kg/Stm
3
)
f
Q
f
p
LPG
26,79
2,151
0,353
0,4
Town gas
4,88
0,6023
1,936
3,3
Biogas
6,395
1,1472
1,478
3,5
ATTENTION! The combustion head type and the settings depend on the fuel. The burner must be used only for its
intended purpose specified in the burner data plate .
ATTENTION! The corrective factors in the above table depend on the gas composition, so on the calorifc value
and the density of the gas. The above value can be taken only as reference.
Q
biogas
Q
naturalGas
1 478
=
p
biogas
p
naturalGas
3 5
=
Содержание H365X
Страница 46: ......
Страница 47: ......
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......