PART III: OPERATION
34
position. Laboratory tests have shown that this is the optimal configuration to assure flame stability. If different settings are required, it
is possible to change the position: loosen the VB screw and slightly move the combustion head backwards, turning clockwise the knob
VRT. Fasten VB screw when the adjustment is accomplished.
Depending on the boiler application, it is possible to act on the holes (figure B) to improve the flame stability and NOx, CO emission
values. If necessary, close/open the holes in figure “B” using the screws kit given with the burner.
Attention! if it is necessary to change the head position, repeat the air and fuel adjustments described above.
VRT
VB
“all-ahead” position
“all-backwards” head position
X
x = 10 mm
A
B
A
B
Содержание G270X