background image

Contact Position

Condition

K-1 Load Relay

Contacts

3 - 4        3 - 5

Red

Lamp

On Shelf (Figure 3).

Open

Closed

Off

Power Applied;
Differential Pressure above

Set Point  (Immediate).

Open

Closed

Off

Power Applied; Differential
Pressure above Set Point

(After 8 seconds).

Closed

Open

Off

Power Applied; Differential
Pressure below Set Point

(Immediate).

Closed

Open

On

Power Applied; Differential
Pressure below Set Point

(After 8 seconds).

Open

Closed

On

Model AFS-952 in Standard NEMA-1 rated housing:

• Coated steel finish.

• Shipping  Weight: 

 5 lbs.

K1

L

2

1

TD-1

TD - 1

(8 SEC)

C

NC

NO

LOW

PRESSURE

HIGH 

PRESSURE

4

3

5

CONTROL

WITH

DELAY

10 A  MAX  720 VA
@ 120 vAC

K1

  Figure 3: "Shelf" Condition

CLEVELAND CONTROLS

DIVISION OF UNICONTROL INC.

MODEL AFS-952-B

Remove Plug Button to Adjust

Turn Clockwise to Increase

Operating Set Point.

TD -1

K - 1

Load

Relay

Red 
Signal
 Lamp

Enclosure

Cover

Low Pressure Inlet
¼ NPT

High Pressure Inlet
¼ NPT

0.281” (7 mm)
mounting holes (4)

AFS-952

.875" hole

accepts

.5" conduit

Plug Button
to access
adjusting
screw

1.75"

(44 mm)

4.38"

(111 mm)

3.59"

(91 mm)

5.88"

(149 mm)

5.25"

(133 mm)

1.00"

(25 mm)

6.00"

(152 mm)

2.31"

(59 mm)

1.25"

(32 mm)

8.00"

(203 mm)

3.56"

(90 mm)

1.44"

(37 mm)