4. BOILER ADJUSTMENT AND PRELIMINARY SETTING 

4.1.   Introductory remarks 
The purchased boiler is adjusted by the manufacturer according the parameters needed for the type of gas, which is listed 
on  the  rating  plate  of  the  boiler  and  in  its  documents.  If  it  is  necessary  to  change  the  parameters  or  adapt  the  boiler  to 
another type of gas; the process of adjusting the boiler and setting the parameters should be performed only by qualified 
service team or person. It is allowed to perform above mentioned operations if: 

 

the  tightness  of  the  gas  system  connections  was  checked  after  the  boiler  installation  and  it  was  confirmed  with  the 
signature and the stamp of the installer,   

 

the electrical installation was made in accordance with applicable regulations, 

 

the correctness of connections between the boiler and the chimney was checked and confirmed by a qualified chimney 
service. 

 

4.2.    Adjusting the boiler to combust another type of gas 
4.2.1.   Selecting the type of gas on the boiler controller 
If it is necessary to change the adjustment of the boiler from the natural gas into liquefied gas the parameter P4 needs to 
be changed respectively (see section  5.7). 

 

4.2.2.   Changes in the gas system of the boiler 

The boiler supplied by the manufacturer is designed to combust gas type specified on the rating plate. 
The boiler can be adjusted to combust another type of gas but only for this one which the boiler is certified for.The types 
of gases are given on the rating plate - in the index designation:

 

 

 

Category II

2E3PB/P

 

Group 2 – natural gas-

es: 

2E-G20 

Group 3 – liquefied 

gases:   

3B/P-G30 

Adapting a boiler to another type of gas involves replacing the burner nozzles dedicated to specified type of gas and ad-
justing the minimum and maximum gas pressure range on the modulator (fig.4.2.2.1). Also the regulation of gas pressure 
for the start power and maximum power of the boiler control panel (see description in section 4.2.2.3, 4.2.2.4 and 5.7.). The 
dimensions of the nozzles and pressure for operation of boilers are given in table 4.2.2.5.    

 

Example of completed label 

s.a 

After adapting the boiler to combust another type of gas: 
 

 

Cross out on a rating plate the type of gas to which the boiler was adapted by 
the manufacturer, 

 

Write down the symbol of the gas, to which the boiler has been adjusted and 
the set heat load on the appropriate label that is attached bulk to the user ma-
nual. The entrymust be writtenlegibly and indelibly. 

 

Label filled in as above should be sticked on the cover near rating plate. 

 

Set for gas:

 

Liqu-
efied

 

Gas symbol 

3B/P-
G30 

Gaspressu-
re 
[mbar]

 

37 
.............
......

 

Set the nominal heat load 
........................... [kW]

 

 

Adapting the boiler to combust another type of gas can be performed only by a qualified service team. This operation 
is not included in the warranty repairs.

 

 

 

1.   Main cut-off valve. 
2.   Cut-off valve . 
3.   Measuring point of inlet gas pressure.  
4.   Measuring point of outlet gas pressure. 
5.   Regulation of gas pressure on the modulator: 

A.  A maximum pressure adjustment screw of modulator (hexagonal 10 mm 

wrench). 

B.  A minimum pressure adjustment screw of modulator (screwdriver). 
C.  Protective cap. 

6.  Connection to the gas system. 

 
 

Fig. 4.2.2.1  Gas valve with modulator 

 
 

4.2.2.2. Gas flow regulation in the boiler 
Gas flow regulation  should be only performed if the boiler is being adjusted to combust another type of gas or during the 
replacement  of  gas  unit  and  also  for  test  purposes  during  first  launch.  All  the  regulations  should  be  performed  in  accor-
dance to boiler data included in the table 4.2.2.5. 

Содержание ELEGANCE GCO-13-00

Страница 1: ...UniCO uniCO GCO 29 16 type GCO 24 01 13 GCO 24 00 type GCO 13 00 GCO 24 01 21 GCO 24 01 24 GCO 24 01 29 ...

Страница 2: ...ill not be repaired under guarantee Central heating system must be thoroughly cleaned and rinsed the procedure is described on p 3 5 2 To avoid malicious calcification process of flue gas water heat exchanger and also for reduce a risk of other items damage there should be the proper water preparation in C H circuit according to p 3 5 2 Proper water parameters in C H system allows for long term op...

Страница 3: ...em 18 5 5 2 Indication of operation of frost protection function in STANDBY mode 18 5 5 3 Display of water pressure in the CH system 18 5 5 4 Displaying parameters 18 5 6 CHANGING THE TEMPERATURE SETTING OF CH OR DHW 18 5 6 1 CH setting 18 5 6 2 DHW setting 18 5 7 CONTROLLER CONFIGURATION SETTING OF THE PARAMETERS OF THE BOILER 19 5 7 1 Enter programming mode 20 5 8 BREAK IN OPERATION OF THE BOILE...

Страница 4: ... Such kind of boiler ismarked with B11BS symbol Boilers with closed combustion chamber type C takeair for combustion process from outside the room they are in stalled and they lead the flue gases outside All these types of boilers are suitable for operation with domestic water tanks available in Termet s offer Storage tank is not included in boiler equipment 2 BOILER DESCRIPTION 2 1 Technical spec...

Страница 5: ...efied gas 3B P G30 30 37mbar m3 h kg h 0 5 1 5 0 3 1 1 0 8 2 7 0 6 2 0 0 85 1 3 0 6 1 1 0 85 2 0 0 6 1 8 0 85 2 7 0 6 2 0 1 0 3 3 0 7 2 4 1 15 3 3 0 85 2 42 1 Consumption of different types of gases are given for reference gases in the reference conditions dry gas 15 C pressure 1013 mbar with respect to the given boiler efficiency Nominal kinetic pressure ahead of the boiler for gas 2E G20 3B P G3...

Страница 6: ... explosive switch on of the gas ssure increase 1 st degree Protection against drop of water pressure Protection against water pressure increase 2 nd degree Protectionagainstwateroverheating Protection of the correctness of the fan operation in the C Anti freezing protection of the boiler Protection against chimney draft loss in the B type boilers Protectionagainst pumpblockade Protection against c...

Страница 7: ...w the heating water to a short circuit while giving a signal to the spark generator and gas valve item 8 with temperature described by parameter P16 default 75 C flows through the coil of tank short circuit prior to reaching the maximum temperature of heating water the gas flow modulator that regulates the amount of gas supplied to the combustion to the burner keeping constant the temperature is a...

Страница 8: ...the boiler from the power source In order to connect the boiler to the junction box it is recommended to cut the power cord to a suitable length for connection to the box pull off cable insulation put the cable end sleeve with the appropriate diameter This prepared cables connect according to the following diagram Fig 3 1 3 1 Wire colors L brown N blue PE yellow green 3 2 Preliminary check activit...

Страница 9: ...s the boiler min 220 Flue stub end internal diameter G3 4 G3 4 G3 4 m in 5 3 300 B C 671 5 E 670 5 to the connector 113 113 111 103 178 Flue pipe external diameter A D ca 100 ca 100 ca 2000 mm A B C D E uniCo 13 Ø 110 360 321 114 700 uniCo 24 Ø 130 360 321 132 700 uniCo 29 Ø 130 475 436 132 713 Fig 3 3 1 Installation dimensions of B type boiler Fig 3 3 1 Installation dimensions of C type boiler ...

Страница 10: ...he boiler and central heating system so that the boiler could be dismounted without draining the system Do not install any thermostatic valves on radiators in the room where the thermostat is installed The temperature controller takes over the function of temperature control and it cooperates with the boiler Do not install a thermostatic valve on at least one of radiators of the central heating sy...

Страница 11: ...al connections of the tank should be made according section 3 10 The tank connection may be made only by an authorized person 3 7 Flue gas outlet Remove the plug from the fan before installing the air flue gas system for the boiler Flue gas outlet from the boiler must be made in accordance with applicable regulations and this instruction manual accord ing to the type of boiler B or C and it needs ...

Страница 12: ...bows connection to the boiler type C 3 7 1 1 The air flue gas system 60 100 coaxial Table 3 7 1 1 1 The elements of the coaxial system Elbow 90º Ø 60 100 Elbow 45º Ø 60 100 Coaxial adapter with the container for condensate Ø 60 100 TubeL 500 мм Ø 60 100 TubeL 1000 мм Ø 60 100 ...

Страница 13: ...nder the cover screw on the adapter 80 80 according the below table in place of the removed cover and seal the connection with the kept gasket screw on the adapter 60 80 according the above table in place of flue gas outlet in the upper part of combustion chamber slide the lower part of the adapter on a fan connector and seal the connection with a gasket number 000617 Note Horizontal air pipe shou...

Страница 14: ...f the controller there are two flaps under the right flap there is hidden the access to electrical terminals To connect the temperature control unit the appropriate length of wire must be purchased and connected to the terminals marked with RT which are situated under right flap of control panel after removal of an electrical short circuiting bridge containing RT poles To connect an additional dev...

Страница 15: ...is recommended to place the external temperature sensor on the north side of the building and not to expose it o the sun 3 10 Electrical connection of the tank to the boiler To connect the tank you should NTC sensor wire should be connected in accordance with information label Figure 3 8 1 to the terminals marked CZ after removing the resistor connected to the CZ terminals The other end of the wir...

Страница 16: ... involves replacing the burner nozzles dedicated to specified type of gas and ad justing the minimum and maximum gas pressure range on the modulator fig 4 2 2 1 Also the regulation of gas pressure for the start power and maximum power of the boiler control panel see description in section 4 2 2 3 4 2 2 4 and 5 7 The dimensions of the nozzles and pressure for operation of boilers are given in table...

Страница 17: ... ce function is active for 10 minutes Early termination of it follows by pressing the 4 2 2 2 Adjustment of the maximum outlet pressure in the boiler ressure of gas in the boiler must be carried out in the following order fig 4 2 2 1 loosen half turn the safety plug on the measuring point of outlet gas pressure 4 fig 4 2 2 1 o the measuring point for example micromanometer set the service function...

Страница 18: ...kW 7 9 13 15 17 19 20 21 23 24 Gasconsumption l min 4 5 1 7 3 8 4 9 5 10 5 11 11 5 12 5 13 The pressure in the burner Pa 220 355 701 910 1143 1398 1524 1654 1943 2150 Boiler type GCO 13 00 for gas 2E G20 inlet pressure 20mbar nozzle indication 115 Power of boiler kW 4 5 6 7 8 9 10 11 12 13 13 5 Gasconsumption l min 7 8 9 7 11 6 13 5 15 4 17 3 19 2 21 1 22 9 24 8 25 7 The pressure in the burner Pa ...

Страница 19: ... power is switched on display shows successively b1 symbol and control board software version number b2 symbol and display software version number 1F or 2F or 3F or 4F marking indicating the type of configuration 1F UNICO 2F MINITERM 3F MAXITERM 4F MINIMAX Afterwards controller switches to the readiness to accept user commands The symbol on the display Signaling Notes CONTROLLER RE START The contr...

Страница 20: ...tart of the heating in the circuit of CH or DHW system At the start of the heating in C H or DHW circuit for 4 seconds CH or DHW flashing set temperature value is displayed Also the temperature symbol and the symbol of circuit in which the heating function is performed is flashing 5 5 2 Indication of operation of frost protection function in STANDBY mode f anti freezing function in the C H system ...

Страница 21: ...00 100 Parameter visible for P10 1 P15 C H off hysteresis 0 10 refers to software version 15 0 15 refers to software version 16 5 P16 CH water temperature for tank heating 70 89 C 75 Parameter visible for P6 0 P17 The value of the parallel displacement of the heating curve of weath er regulator 0 20 0 Parameter visible for P19 1 or P19 2 P18 Limit value for flow temperature 40 85 C forP08 0 35 55 ...

Страница 22: ...n of the gas ignition process the burner power will be the same as the displayed value button to cancel the change use the reset button Return from the programming mode follows automatically after a set period of inactivity or by holding the 2 seconds leave the boiler connected to the electricity mains leave the gas valve and water valve of CH opened set the mode on STANDBY section 5 4 1 In such c...

Страница 23: ...ler with blockade after unsuccessful attempts to gas The reason for failure may be the lack of gas Check if the gas cocks are opened and the gas The water temperature in the gas water heat exchanger reaches a value C Follows the turning off the boiler with a blockade In the chimney there is no underpressure or there is a break in the circuit closing the gas valve symbol E 03 is displayed after 15 ...

Страница 24: ...ld be regularly serviced and subjected to maintenance At least once a year it is recommended to perform a service and the boiler should be reviewed before heating season All service and maintenance works should be performer by an authorized person Only original parts should be used for At every service and maintenance works the tightness of the gas units and gas installation and correctness of the...

Страница 25: ... Checking of the temperature limiter item 16 consists in measuring the resistance between the contacts of the limiter after the wire removal The resistance of the limiter should be 0 Ω at the room temperature and Ω at the temperature above 65 o C 6 2 3 Checking the protection controlling the proper fan operation in C type boilers Boilertype Gastype Return pressure Boiler with the fan 40W 1700 08 0...

Страница 26: ...res with a resistance greater than 24000 Ω which corresponds to the heating water temperature lower than 8 C The boiler should automatically start and heat the water Then connect a resistor parallel connection with a resistance of 17575 Ω which corresponds to the heating water temperature greater than 25 o C Connecting this resistor should cause the boiler switch off 6 2 7 Checking the room temper...

Страница 27: ...Supply voltage from the control board 5 Fan W961250050 GOLD Power 40W 230VAC 7 Pump Power 84W 230VAC 8 Gas unit valve Valvecoilresistance Power supply of valve coil 230VAC 15 Temperature limiter Contact 18VDC 16 Temperature limiter Contact 18VDC 18 C H water temperature NTC sensor 10K 25 C β 3977 Not exceeding 5VDC 19 Heating waterpressure sensor Output voltage 0 5V do 3 5V 0 bar 4 bar 18VDC param...

Страница 28: ...alve 1140 34 00 00 1 GCO 24 01 GCO Not included in the boiler equipment PURCHASE RECOMMENDED TO IMPROVE COMFORT OF THE BOILER USE 6 Roomtemperaturethermostat 1 GCO 24 01 GCO Not included in the boiler equipment 7 Externaltemperature sensor WKC 0564 00 00 00 1 8 Kit for open circuit WKR 0771 00 00 00 1 GCO 24 00 GCO 24 01 WKR 0772 00 00 00 1 GCO 29 16 WKR 0773 00 00 00 1 GCO 13 00 PURCHASE NECESSAR...

Страница 29: ...Długa 13 58 160 Świebodzice Poland Export Department tel 74 856 06 75 http www termet com pl termet termet com pl export termet com pl ...

Отзывы: