UWX550 and UWX440

Installation Guidelines

®

Содержание UWX550

Страница 1: ...UWX550 and UWX440 Installation Guidelines...

Страница 2: ...ining professional information using representative graphs charts and tables Manufacturers specifications must be consulted for specific guidelines and performance data Unicla published data specific...

Страница 3: ...and screen 7 12 Oil injector 8 13 Discharge line analysis pressure and temperature 8 14 Refrigerantcharging 9 15 Compressor operation analysis report 10 Note This booklet is designed to assist the ins...

Страница 4: ...solid particle and chemical contamination before compressor fitting Solid particle contamination will cause direct compressor damage and starvation due to blocked system filters and screens see sectio...

Страница 5: ...the bolt then pull out Fig A Fig B Fig C 3 Fitting of discharge hose manifold Install the gasket Install Manifold Valve this is right hand view M10 x L60 Bolt Tightening tension 34 3 Nm 355 kg cm Con...

Страница 6: ...nd this amount is excluded from the quantities recommend above Note Oil quantity calculations are contained in the Unicla Service Handbook Total system oil requirement is based on 20 and 30 of refrige...

Страница 7: ...rvation of the compressor Warranty is void if these guidelines are not followed Unicla Oil Type Alternative Unidap 6 POE 68 Unidap 7 PAG 46 Recommended alternatives for Unicla Lubricant 6 Oil type and...

Страница 8: ...point Oil Green colouration exposure to copper oxidation Operation OK Recommendation Monitor oil condition and change if necessary Sight Glass Oil level low half point Oil Normal clean and transparen...

Страница 9: ...e Unicla inline mesh screen and filter insert should be used whenever there is risk of debris and fine particles entering the compressor through the suction line In the case of older systems where the...

Страница 10: ...ual is required or reference to additional technical information for specifications and faults regarding condensing to air differentials NR not recommended as a continuous running phase superheat may...

Страница 11: ...peration b If it is not possible to access the system at the evaporator or roof level then service points in suction and discharge lines away from the compressor are the next best option c If refriger...

Страница 12: ...ut oC Discharge Temp oC Pressure Drop Temp Difference oC Liquid Line Temp oC Suct LineTemp at Comp oC Discharge Superheat oC Evap Temp oC Condensor m s Subcooling oC Suct LineTemp at Evap oC Evap Duct...

Страница 13: ...Notes...