1.  Connect the power cord to a verifi ed grounded 3-wire receptacle.

2. Turn on the power switch of EBPU, the green and yellow LED will be lit indicating AC utility voltage 

is present.

3.  Charge the batteries for 10hours before use. You may use the EBPU immediately without recharging, 

but the backup time may be less than the rating.

4.   Connect your computer to the output receptacles of the UPS.

5.   To Test backup function, you may disconnect the power cord of the EBPU from wall outlets. The red 

LED will fl ash, and buzzer will beep every 5 seconds.

6.   When the battery approaches low level, buzzer will beep twice per second until unit shuts down.

7.   4 conditions that cause the EBPU to shut down automatically:

 

•  Battery Low

 

•  Short Circuit

 

•  Overload

 

•  EBPU Fault

Caution

• 

The EBPU contains voltage that is potentially hazardous. All repairs should be performed by 

qualifi ed service personnel.

• 

The EBPU has its own internal energy source (battery). The output receptacles may be alive when 

the EBPU is not connected to an AC supply.

• 

The EBPU is designed for electronic supply for applications such as electronic patient equipment 

and hospital beds containing a substantial rectifi er or capacitive load. It is not suitable for signifi cant 

inductive loads.

• 

Be sure to operate within the power rating of the EBPU. Below 1/2 or 1/3 of the rated power is 

recommended for longer backup time and battery life.

• 

Do not place the EBPU near excessive humidity, direct sunshine, or close to heat-emitting sources. 

If the EBPU is out of order, detach power cord and consult your supplier right away. Do not remove 

the cover, there are no serviceable parts inside.

• 

The unit should be supplied by a grounded source. Do not operate the unit without a ground source.

• 

Do not plug the EBPU’s power cord into itself. That will result in a safety hazard.

Содержание Emergency Bed Power Unit

Страница 1: ...Emergency Bed Power Unit EBPU Instruction Safety Manual Please read this manual before operation for maintenance instructions and safe usage The enabling power of applied knowledge...

Страница 2: ...er If there is no damage to the shipping carton unpack the unit inspect the unit for damage The EBPU is designed for installation in a protected environment with a temperature range of 0 40 C and rela...

Страница 3: ...UPS in normal mode OFF OFF FLASHING EVERY 5 SEC Mains fail running on battery OFF OFF FLASHING TWICE PER SEC Low battery prepare to switch o OFF OFF SOLID TWICE PER SEC Overload remove load OFF OFF SO...

Страница 4: ...ci cations Ratings Voltage Amperes VA 600 1000 1400 Input Rated AC Input Voltage 230V 25 AC Input Voltage Window 165 275V Input Frequency 40 70Hz Output AC Output Voltage Typical 230V AC Output Voltag...

Страница 5: ...EBPU contains voltage that is potentially hazardous All repairs should be performed by quali ed service personnel The EBPU has its own internal energy source battery The output receptacles may be ali...

Страница 6: ...LA Service Life 3 5 years depending on use Battery Recharge 90 8 hours Autonomy 6minutes load dependent General Net Gross Weight kg 6 10 9 12 1 Dimensions LxWxH 95x312x158 124x372x223 124x372x223 Encl...

Страница 7: ...6 T 08 9351 7500 E info unicarehealth com au W www unicarehealth com au...

Страница 8: ...PO Box 82 Bentley WA 6982 T 08 9351 7500 F 08 9350 5299 info unicarehealth com au www unicarehealth com au Authorised Distributor...

Отзывы: