background image

Touch Screen 

 

41 

N° 

PARAMETER 

MINIMUM 

VALUE 

MAXIMUM 

VALUE 

DEFAULT 

VALUE 

MEASUREMENT 

UNIT 

62 

Regulation temperature in zone 8 “Summer” 
0 = Average temp. of the fancoils of the zone 
1 = Minimum temp. of the fancoils of the zone 
2 = Maximum temp. of the fancoils of the zone 
3 = Temperature measured by the “Touch Screen” control 
panel 

--- 

63 

Regulation temperature in zone 9 “Summer” 
0 = Average temp. of the fancoils of the zone 
1 = Minimum temp. of the fancoils of the zone 
2 = Maximum temp. of the fancoils of the zone 
3 = Temperature measured by the “Touch Screen” control 
panel 

--- 

64  Polling duration 

0.1 

1.0 

0.1 

Seconds 

65  Port for web server 

9999 

80 

--- 

 

Содержание TOUCH SCREEN N

Страница 1: ...USER S AND INSTALLER S MANUAL LCD Touch Screen Centralized Remote Controller TOUCH SCREEN_N...

Страница 2: ...4 SPECIAL FUNCTIONS PAGE 17 3 6 5 CONFIGURATION PAGE 17 3 6 6 HELP PAGE 19 4 MACHINES STATUS AND FUNCTIONS 20 4 1 NEWTORK MANAGEMENT 20 4 2 REMOTE CONTROL CONNECTION WITH MULTIPLE CHILLERS IN THE NETW...

Страница 3: ...4 12 SECONDARY CIRCULATOR 33 4 13 OTHER FUNCTIONS 33 4 14 SPECIAL FUNCTIONS 33 4 14 1 SCREED FUNCTION 33 4 15 PASSWORD AND PROTECTIONS 34 5 REMOTE ACCESS 34 5 1 SECURITY 34 5 2 LOCAL WEB SERVER 34 6...

Страница 4: ...ts and parameters of the first circuit can be displayed 1 2 USE NOT PERMITTED Any use different than that permitted is PROHIBITED 1 3 TECHNICAL DATA Features Nominal Min Max Power supply voltage 12Vac...

Страница 5: ...the screens Do not put the touch screen in contact with other electrical devices Electrostatic discharge may cause a malfunction 2 1 3 DISPLAY The display is a TFT LCD 16 9 format with a diagonal 4 3...

Страница 6: ...1 GNDR Ground touch screen RS 485 Modbus RTU GNDR Comunicazione Modbus X 5 1 R Modbus RTU touch screen signal R X 5 2 R Modbus RTU touch screen signal R 2 4 INSTALLATION The Touch Screen control is u...

Страница 7: ...e The colour saturation indicates that icon is usable when pressed the related function is performed The transparency de saturated indicates that icon is not usable and any touch on it has no resultin...

Страница 8: ...ss to information on the firmware version 6 Configuring the Ethernet network 7 Log out intermittent symbol if it s active 8 Arrow of navigation next page Graphically it also contains information on th...

Страница 9: ...ctly the following information referreing to fancoil units Presence of fancoil unis that are connected to the network if the fancoil symbol appears on the display Figure 8 Fancoil units connected to t...

Страница 10: ...5 Chiller heat pump with working signalling function given by the rotation of the fans from here you access to an additional page of information about that specific chiller 6 Active alarms of the disp...

Страница 11: ...r temperature C Outlet water temperature C Sanitary probe temperature if it s present and configured C Accessing the same page with service or manufacturer access right to enable the access right pres...

Страница 12: ...TARY INTEGRATION RESISTANCE 3 PLANT INTEGRATION RESISTANCE 4 BOILER ENABLEMENT 5 DOUBLE SET POINT 6 DEHUMIDIFYING 7 SLAB FEATURE 8 DEFROST 9 ANTIFREEZE WATER 10 ANTIFREEZE TRAY RESISTANCE Table 1 Orde...

Страница 13: ...the next fancoil unit on the network 3 the name of the zone to which the fancoil belongs and the fancoil identification number are reported every time you press the name area you switch to the next fa...

Страница 14: ...onfigured function but note active Herein below is reported a table with icons that may appear in the scrollable sidebar The presence absence of the icon in the sidebar depends on the status of its co...

Страница 15: ...the system The field 3 indicates the chiller which it refers by pressing on it you progress to the next chiller in the network For each chiller shown you see the readings on the temperature of the wa...

Страница 16: ...STATUS SETUP 2 SET POINT SETUP 3 PROGRAMS AND CHRONO THERMOSTAT In the bottom from the left to right 4 SPECIAL FUNCTIONS 5 CONFIGURATION 6 HELP MENU 3 6 1 STATUS SETUP PAGE Press the button to enter...

Страница 17: ...age From this page you can set separately the weekly program of each chiller and zones of fancoils You can also program the legionella s cycle and the production of hot water if enabled see Paragraph...

Страница 18: ...e pages of the parameters until you find the desired parameter press on the currently set value the present value turns red to indicate that it can be changed by using the up and down arrows Select th...

Страница 19: ...ess the confirmation tick Note If you press outside the confirmation area it returns again the previously value 3 6 5 3 MANUFACTURER MENU To access to the manufacturer menu you must set the manufactur...

Страница 20: ...connect the chiller and the remote control Touch Screen as shown in the drawing In the remote control Touch Screen by setting the parameter Par 8 65 Configuration Service Menu Keyboard related to the...

Страница 21: ...the installation and utilization of the remote control panel for water terminal units management it is recommended to separately power on the water terminal units fancoils each terminal unit must be i...

Страница 22: ...n is not totally configurable by Touch Screen controller It is necessary to act directly on the chiller heat pump on board controller only if present expansion module by setting the parameters H85 to...

Страница 23: ...or the settings related to the function please refer to paragraph AMBIENT THERMOSTAT Note Once the status is set from the Touch Screen control panel you must wait a minute to ensure that communication...

Страница 24: ...SET POINT Management procedure of the set point of the different zones and chillers 1 from the system main page go to Set point setup 2 at this point you find a list of assigned chillers and the areas...

Страница 25: ...e zones in winter mode In addition if is enabled the sanitary mode from System main page Configuration Service menu Parameters Chiller Chiller name H10 sanitary presence 1 you can access to two other...

Страница 26: ...rve that correspondingly to the selected time period you will see a time line bar of the colour of the type of the selected set if normal blue green when in economy mode no bar in Off repeat the above...

Страница 27: ...is respectively Summer sanitary Winter sanitary Only sanitary 4 7 4 3 ZONES AND FANCOILS WEEKLY PROGRAM In a similar way to the scheduling of the chillers it is possible to set the weekly program of e...

Страница 28: ...NT THERMOSTAT The Touch Screen control panel can operate as a typical ambient thermostat The ambient thermostat function for each zone will be enabled disabled using the corresponding button at the bo...

Страница 29: ...SETTINGS PROCEDURE 4 8 1 SETTING OF LANGUAGE AND DATE TIME To set the keyboard language 1 from the system main page go to Configuration 2 then go to User menu 3 enter the user password and press the...

Страница 30: ...ion of humidistat is instead carried out directly by the Touch Screen remote control panel by means of its integrated sensors and the logic internally implemented related to the control of dew point a...

Страница 31: ...for the calculation of the dew point is the Magnus Tetens approximation this approximation is valid for values of Td between 0 C and 50 C therefore if the calculation gives a value out of these limit...

Страница 32: ...o avoid returning immediately in this case it requires a minimum staying in adjustment to the radiant panels still given by Par43 65 Max staying time in dehumidification 4 11 CLIMATIC COMPENSATION It...

Страница 33: ...oiler integration defrosting cycle water side or air side anti freeze heaters etc please refer to chillers and fancoils instructions manuals 4 14 SPECIAL FUNCTIONS From the main menu choosing the icon...

Страница 34: ...unlock the screensaver set by default to 0 and modifiable by accessing to user s parameters see Paragraph 3 6 5 1 5 REMOTE ACCESS The device can interact with the local network by an Ethernet port acc...

Страница 35: ...o shift to next available pages click on the links at the page bottom Figure 38 Touch Screen Ethernet Command page The commands present in the Command page are referred to the entire system The operat...

Страница 36: ...t points set for the winter season water set point economy water set point and if enabled double set point second water set point and second water economy set point appear under Winter while under the...

Страница 37: ...oard USB port For the upgrade copy the upgrade file in the main root of a USB pen drive insert the pen drive into the Touch Screen USB port enter into Configurations User s menu see Paragraph 3 6 5 1...

Страница 38: ...C Heat 20 0 35 0 15 0 C 19 m5 comp Text FC 10 0 10 0 0 0 20 m6 comp Text FC 10 0 10 0 0 0 21 Set2 Text comp CHIL Cool 0 0 50 0 20 0 C 22 Set2 Text comp CHIL Heat 20 0 35 0 10 0 C 23 Second m1 comp Tex...

Страница 39: ...um temp of the fancoils of the zone 2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 50 Regulation temperature in zone 5 Winter 0 Average temp...

Страница 40: ...imum temp of the fancoils of the zone 2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 58 Regulation temperature in zone 4 Summer 0 Average tem...

Страница 41: ...2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 63 Regulation temperature in zone 9 Summer 0 Average temp of the fancoils of the zone 1 Minim...

Страница 42: ......

Страница 43: ......

Страница 44: ...printing errors It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39...

Отзывы: