Instruction for the installer
Setting parameter 00 (BC)
-
Reaching the
TSP
under- parameters (View previous
page)
-
Press the button
OK
to display the first parameter
00
(BC)
of
TSP
-
Press the button
OK
: The ! symbol appears, select the
desired value using the buttons
-
Press the button
OK
to confirm
00 (BC) = identifier code eBUS
value to be set:
0 x Master Module
1 to 95 x slave module
If more modules SATAL PLUS C are added
(max 95 1 master) in the building, you
must change the parameters:
-
03 (ES)
enable external probe (master only)
-
00 (BC)
Identification code eBUS
-
01 (BS)
Power eBUS
Connection Cascading of more
SATAL PLUS R
caldofreddo
If you need to install multiple modules Satal in the same
building, the communication between modules is ensured
by connecting the terminals (E-Bus Y3 1-2-3) between the
modules.
This allows to have a single external sensor for all local
units.
It is necessary to observe the polarity.
Setting parameter 03 (ES)
(View previous page)
01 (BS) = Power eBUS
value to be set:
0 x modules average
1 x the two extreme module
Setting parameter 01 (BS)
-
Reaching the
TSP
parameters (View previous page)
-
Press the button
OK
to display the first under-
parameter
00
of
TSP
-
Select the under- parameter to change
01 (BS)
of
TSP
using
-
Press the button
OK
: symbol
!
is displayed, select
the desired value using the buttons
-
Press the button
OK
to confirm
module MASTER
BC = 0
BS = 1 (extreme)
ES = 1 (sensor
authorized)
module SLAVE 1
BC = 1
BS = 0 (middle)
ES = 0
module SLAVE 2
BC = 2
BS = 1 (extreme)
ES = 0
1
2
3
4
5
Y3
Y1
1
2
3
4
5
6
Y2
1
2
SIGNAL
COMUNE
SHIELD
e-BUS
1
2
3
4
5
Y3
1
2
3
4
5
Y3
Y1
1
2
3
4
5
6
Y2
1
2
1
2
3
4
5
Y3
Y1
1
2
3
4
5
6
SE
SHIELD
COMUNE
SIGNAL
1
2
3
4
5
Y3
Y1
1
2
3
4
5
6
Y2
1
2
1
2
3
4
5
Y3