34

ROUTINE YEARLY VERIFICATION OPERATIONS

COMPONENT:

VERIFY:

CONTROL/INTERVENTION 

METHOD:

FL  

(domestic hot water 

priority flow switch 

( 2 )

Is the minimum domestic hot water

flow rate 3 l/min.? 

The burner must ignite with an 

intake above or equal to: 3 l/min.

VG 

(Gas valve) 

( 3 )

Does the valve modulate properly? 

Open a hot water tap at maxi-

mum flow rate and then at min

-

imum. Make sure that the flame 

modulates.

SR (heating sensor)

( 11 )

 

SS (domestic hot water sensor) 

( 1 )

SSR (return sensor) 

( 22 )

Do the sensors maintain the 

original characteristics? 

12571 ohm at 20° C / 1762 ohm 

at 70° C.

Measurement to be taken with 

the wires disconnected (see 

table Res/Temp).

E ACC/RIV.  (ignition/detection 

electrode) 

( 4 )

Does the discharge of sparks before

putting the boiler in safe conditions last 

less than 10 sec.?

Detach the electrode ionisation 

wire and check the securing 

time.

TL (anti-overheating 

limit thermostat) 

( 10 )

Does the TL put the boiler in safety 

conditions when overheating?

Heat  the TL  until  it  intervenes 

at 95°C and check that it inter-

venes at 95°.

DK (safety pressure switch 

against water deficiency) 

( 13 )

Does the pressure switch block the 

boiler

if the water pressure is below 0.4 bar?

Without request: close the shut-

off valves of the heating circuit, 

open the drain valve to make the 

water pressure decrease. Before 

pressurising again, check the 

pressure of the expansion vessel.

Expansion vessel 

( 8 )

Does  the  vessel  contain  the  right 

amount

of air?

Check the pressure in expansion 

vessel  (1  bar  when  the  boiler 

is  empty).  Pressurise  the  boiler 

(open  the  pump  automatic  vent 

valve).  Open  the  heating  circuit 

closing valves.

Condensation drain trap 

(26)

Has the trap got deposits on the 

bottom? 

Clean the trap with water.

Domestic hot water flow rate 

Filter in cold water inlet 

( 2 )

Clean  the  filter  with  limescale 

remover.

Heat exchanger body 

(24 )

1) Measure the Thermal Capacity 

using a meter and compare the val

-

ue with that contained in table 3.12. 

The data measured indicates if the 

exchanger needs cleaning.   

2) Check that the space between 

the rungs of the exchanger are not 

clogged

 

It is recommended to use the 

products purposely created by 

Unical  (see system protection 

ACCESSORIES sect. in the 

domestic price list), being care-

ful to wash the area with most 

rungs  first  (lowest  part  visible 

from above) and then the upper 

part if necessary.

Burner 

( 5 )

Check the state of cleanliness of the 

burner mesh

Remove  any  deposits  using 

compressed air, blowing from 

the mesh side.

( Num ) = 

see key Par. 2.2

Содержание KONm Series

Страница 1: ...E N G L I S H INSTALLATION AND SERVICING MANUAL R 18 C 18 R 24 C 24 R 28 C 28 R 35 C 35 KONm...

Страница 2: ...It can be taken to a special recycling centre managed by the local authorities or to a dealer who offers this service Separate disposal of a domestic appliance avoids possible negative consequences fo...

Страница 3: ...3 4 1 Inspection and maintenance instructions 33 4 2 Parameters that can be edited from the control panel 35 4 3 Adaptation to the use of other gas 36 4 5 Wiring diagram 39 4 6 Error codes 41 3 INSTAL...

Страница 4: ...t was expressly designed Any other use is to be considered improper and therefore dangerous 1 1 general warnings The instruction booklet is an integral and essential part of the product and must be ke...

Страница 5: ...ser as well as other documents concerning the appliance inserted in the envelope inside the packaging The user must keep this documentation safe for future consultation Inform the user about the impor...

Страница 6: ...h affect the operating safety of the appliance Attention To tighten or loosen the screwed fittings use only appropriate fixed spanners Incompliant use and or inappropriate tools can cause damage e g w...

Страница 7: ...T max Max domestic hot water temperature C Electrical characteristics 21 Electrical power supply 22 Consumption 23 Protection rating D Countries of destination 24 Direct and indirect countries of dest...

Страница 8: ...atment of the supply water allows to prevent inconveniences and maintain the functionality and efficiency of the generator over time The ideal water pH in heating systems must be within To minimise co...

Страница 9: ...ting and domestic hot water services MAX M I N MAX MIN 1 8 BOILER ANTIFREEZE PROTECTION This protection can intervene only if the electricity and gas supplies are connected If one of the two is not av...

Страница 10: ...2 TECHNICAL FEATURES AND DIMENSIONS 2 1 TECHNICAL FEATURES 2 2 VIEW WITH THE INDICATION OF THE MAIN COMPONENTS AND DIMENSIONS KONm C18 KONm C24 23 27 19 NOTE For further details refer to the Technical...

Страница 11: ...inium Heat Exchanger Ca pacitor 25 Vent valve 26 Condensation drain trap 27 SL Condensate level sensor C Domestic hot water outlet G G Gas inlet G KONm C28 KONm C35 2 3 1 23 22 24 18 25 4 26 15 17 20...

Страница 12: ...12 345 0 1 2 3 4 bar MAX M I N MAX MIN bar service EA D 700 420 125 205 225 125 131 70 61 130 60 56 43 207 247 C F G R M Svs Rc Scond Sc 67 KONm C18 KONm C24 View from above View from below...

Страница 13: ...tures E N G L I S H 0 1 2 3 4 bar MAX M I N MAX MIN bar service EA D 700 420 345 251 5 168 5 142 194 131 70 61 130 60 56 43 104 137 207 247 C F G R M Svs Rc Scond Sc KONm C28 KONm C35 View from above...

Страница 14: ...2 3 DIAGRAM OF FLOW RATE PRESSURE AVAILABLE FOR INSTALLATION Flow rate l h Flow rate l h Avaible Head m c a metres of water Avaible Head m c a metres of water MODULATING PUMP DIAGRAM OF FLOW RATE PRES...

Страница 15: ...S OF GAS 2 5 GENERAL FEATURES KONm R 18 C 18 R 24 C 24 R 28 C 28 R 35 C35 Appliance category II2H3P II2H3P II2H3P II2H3P Minimum heat circuit output t 20 C l min 1 2 1 2 1 7 1 7 Minimum heating circui...

Страница 16: ...boiler YES NO SI SI SI SI Auxiliary electricity consumption At full load elmax kW 0 085 0 085 0 116 0 116 At part load elmin kW 0 012 0 012 0 012 0 012 In stand by mode PSB kW 0 003 0 003 0 003 0 003...

Страница 17: ...room the appliance must be protected suitably and must be able to operate independently from the air in the room Attention Only mount the appliance on a closed wall made of non flammable materi al fla...

Страница 18: ...ob jects due to failure to comply with the instruction above H P L As well as the appliance the packaging contains A DOCUMENTATION ENVELOPE System booklet User operating instructions booklet Instruct...

Страница 19: ...pliance must only be installed on a vertical and solid wall which can support its weight The wall must not be made of flammable material Since the temperature of the wall on which the boil er is insta...

Страница 20: ...lues of bends terminals extensions you get the value if 0 OK POSSIBLE configuration if 0 NO WRONG configuration Please note these values relate to exhausts made by means of rigid pipes and smooth orig...

Страница 21: ...ting of two pipes one for combustion air intake and the other one for combustion products evacuation coaxial or double C63x C63 Boiler intended for connection to a combustion air intake and combustion...

Страница 22: ...pipes The supplier will have no contractual or extra contractual liability for damage caused due to incorrect installation and use and in any case failure to comply with the instructions provided by...

Страница 23: ...2 F COLD 1 2 Sc BOILER DRAIN S cond CONDENSATION DRAIN Rc FILLING VALVE Svs SAFETY VALVE DRAIN Provide a drain pipe with funnel and a trap that lead to a suitable drain in cor respondence of Svs This...

Страница 24: ...the system connections have been completed the circuit can be filled This operation must be performed carefully respect ing the following phases open the radiator vent valves and make sure the automa...

Страница 25: ...jumper ON OFF room thermostat connection RT OT A3 4 32 1 6 5 SE TA 1 OT TA 2 WH WH Y Y BK BK TA ON OFF Danger Only a qualified technician may per form the electrical installation Before performing co...

Страница 26: ...connection must be made up to standard as required the regulations in force Remember that a bipolar switch must be nstalled on the boiler power line with over 3 mm between contacts easy to access maki...

Страница 27: ...stopped Has the condensate drain trap been installed correctly as indicated in chapter 3 7 are any system shut off gate valves open does the gas to be used correspond to the boiler calibration gas oth...

Страница 28: ...OF THE calibration function 3 11 2 Positioning the probes 1 ACTIVATION By pressing the button D for 3 seconds the calibration function is activated Release it when the SERVICE symbol appears Do not p...

Страница 29: ...value corresponds to that indicated in the table NOZZLES PRESSURE Correct it if needed by turning with a screwdriver the screw R CLOCKWISE to increase it ANTI CLOCKWISE to decrease it ADJUSTMENT SCREW...

Страница 30: ...adjustment Operate the boiler in calibration mode at MAXI MUM OUTPUT see 3 11 1 Once the burner is on check that the CO2 MAXIMUM value corresponds to that indicated in the table NOZZLES PRES SURE if...

Страница 31: ...rmal kW Capacity Supply Press mbar Fan speed rpm Collector diaphragm n holes Diaphragm VG CO2 levels Con sump tion Con sumption Start up power IG min max min max min max Nat gas G20 4 3 27 2 4 4 28 0...

Страница 32: ...s possible to adjust the maximum thermal capacity in heating mode by decreasing the burner output value 3 12 1 ADAPTATION OF THE POWER TO THE HEATING SYSTEM Act on parameter HP par 4 2 parameters that...

Страница 33: ...let valve if closed previously Vent and if necessary restore the heating pres sure until reaching a pressure of 0 8 1 0 bar Open the gas shut off valve Switch the boiler on Make sure the appliance is...

Страница 34: ...he water pressure is below 0 4 bar Without request close the shut off valves of the heating circuit open the drain valve to make the water pressure decrease Before pressurising again check the pressur...

Страница 35: ...LT 0 TA 0 5 TA 5 30 TA 30 0 TA 0 MAXIMUM HEATING OUTPUT VALUES FROM TO DEFAULT 0 Min 99 Max 99 PREHEATING VALUES FROM TO DEFAULT 0 1 0 EXTERNAL PROBE TEMPERATURE VALUES FROM TO DEFAULT 0 20 C 30 10 C...

Страница 36: ...is new type of gas ATTENTION Indications for propane gas fired ap pliances Make sure that the gas tank has been deaerated before installing the appliance For state of the art deaeration of the tank co...

Страница 37: ...conversion kit Access the modulation board contained in the electric panel and position the jumper in the position corresponding to the new type of gas indicated in the figure Ending of gas transforma...

Страница 38: ...on Close the electric panel and restore the appliance s electric power supply Check the pressure value upstream of the gas valve see table NOZZLES PRESSURE and adjust the CO2 as indicated in paragraph...

Страница 39: ...connection terminals Model KONm 18 KONm 24 4 5 WIRING DIAGRAM COLORS BL BLUE BR BROWN BK BLACK G GREEN GR GREY L BL LIGHT BLUE OR ORANGE PK PINK R RED Y YELLOW YG YELLOW GREEN WH WHITW VI VIOLET MDV...

Страница 40: ...rminals COLORS BL BLUE BR BROWN BK BLACK G GREEN GR GREY L BL LIGHT BLUE OR ORANGE PK PINK R RED Y YELLOW YG YELLOW GREEN WH WHITW VI VIOLET MDV MDV 230 V 50 Hz L1 N GND P N L1 R YG BL BR 1 2 A8 3 4 5...

Страница 41: ...wiring if needed replace the external probe 14 1 RETURN PROBE Auxiliary SRR sensor inter rupted Check the wiring if needed re place the auxiliary sensor 22 30 2 SERVICE PARAMETERS Service parameters a...

Страница 42: ...XCHANGER FREEZING 24 Exchanger freezing is detected If the heating sensor detects a temperature below 2 C burn er ignition is inhibited until the sensor detects a temperature above 5 C Disconnect the...

Страница 43: ...chimney intake or exhaust is obstructed if there is no obstruction press reset button on the panel 19 22 FLAME CONTROL Flame control damaged Replace the board CONDENSATE SENSOR LE VEL 27 SL condensate...

Страница 44: ...ors of transcript or press Also reserves the right to bring those changes that it will hold necessary to it own products or profits without jeopardizing its essential characteristics 46033 casteldario...

Отзывы: