33
ENGLISH
Installation Instructions
3.13.1 - ADAPTATION OF THE POwER TO THE HEATING SYSTEM
E.g.:
KON 1 C35
to decrease the output of the
boiler to 24 kW, edit parameter
HP (about 68)
.
E.g.:
KON 1 C28
to decrease the output of the
boiler to 20,5 kW, edit parameter
HP (about 68)
.
E.g.:
KON 1 C24
to decrease the output of the
boiler to 17,5 kW, edit parameter
HP (about 68)
.
ATTENTION!
Function reserved for Authorised
Assistance Centres only.
It is possible to adjust the maximum thermal capacity
in heating mode, by decreasing the burner pressure
value.
Act on parameter
HP
(par. 4.2 SE parameters list)
to achieve the value corresponding to the desired
output.
The user is NOT authorised to activate the func-
tion described below.