10 

 

Iron (Fe) 

< 0,3 ppm 

 

 

Alkalinity (HCO3) 

70 – 300 ppm 

Chloride ions (Cl-) 

< 50 ppm 

sulfate ions (SO4) 

< 50 ppm 

Sulfide ion (S) 

None 

Ammonium ions (NH4) 

None 

Silica (SiO2) 

< 30 ppm 

5.4.2

 

Drainage connection 

All the units of series have been designed to use their own base as a drain pan; a plastic pipe fitting is standard provided to be 

installed onto the lower part of the unit in the special housing enabling the connection of a drainage pipe. 

 

Each unit is also provided, on the basement of the hydronic kit (at the heat exchanger side), with a hole that can allow to drain any 

condensed water can leach from plumbing pipes.  As the pipes must be well-insulated, the production of condensed water is 

however very low and therefore the connection of a drainage pipe to that hole is not very required. 

5.4.3

 

Plant circuit charging 

 

WARNING: Verify all the charging/topping up operations. 
WARNING: Before beginning the charging/topping up operation of the plant circuit, disconnect the unit for the 

electric power supply. 

WARNING: The charging/topping up of the plant circuit must always be done under controlled conditions of 

pressure (max 1 bar). Make sure that you have installed on the line of charging/topping up a pressure 

reducerdevice and a relief valve. 

WARNING: The water on the charging/topping up pipe must be suitably pre-filtered from any impurities and 

suspended particles. Make sure that you have installed a cartridge filter removable. Make sure that an extractable 

cartridge filter and a dirt separator have been installed. 

WARNING: It is required to proceed by air purging periodically in order to eliminate the accumulated air in the 

plant circuit system. 
WARNING: Make sure to install an automatic air vent valve at the highest point of the system. 

 

 

 

5.4.4

 

Plant drainage system 

When it is necessary to drain the plant, close at first the inlet and outlet manual gate valves (not supplied) and then remove the 

pipes that are disposed externally on the water inlet and on the water outlet in order to spill away the liquid contained in the unit 

 

 

 

Drainage pipe fitting 

Drainage pipe fitting housing 

Drainage pipe fitting connected to the unit 

 

 

During loading / reintegration operations, the vent valve cap must be partially 

unscrewed to allow air to flow freely outside the valve. 

 

(1) breather valve cap 

ATTENTION. The air vent is a manual valve. Periodically it is necessary to perform 

the air purge operations that accumulate in the system as just described. 

 

You can use the service valve, when it is necessary to refill the plant or adapt the 

concentration of glycol. Unscrew the cap of the service valve and connect to the 

hose a pipe of 14 mm or  (inner diameter  size  -  check the faucet model that is 

installed on your own  unit) connected to the water network, and then load the 

system by unscrewing the knurled nut. When the operation is concluded, retighten 

the knurled nut and screw on the cap. In any case, we recommend you to use for 

the water loading of the plant an external tap whose arrangement is by the 

installer. 

Cap with gasket 

 

Knurled nut 

Содержание HP OWER ONE 70

Страница 1: ...User s and Installer s Manual 70 90 120 140 160 ONE...

Страница 2: ...3 Plant circuit charging 10 5 4 4 Plant drainage system 10 5 4 5 Hydraulic circuit 11 5 5 REFRIGERANT DIAGRAM OF HP_OWER ONE 70 90 11 5 6 REFRIGERANT DIAGRAM OF HP_OWER ONE 120 12 5 7 REFRIGERANT DIA...

Страница 3: ...6 3 MODELS HP_OWER ONE 140 160 37 16 4 ACCESS PROCEDURE TO THE INTERNAL PARTS OF THE UNIT 38 16 4 1 Mod HP_OWER ONE 70 90 38 16 4 2 Mod HP_OWER ONE 120 38 16 4 3 Mod HP_OWER ONE 140 160 39 17 REGISTER...

Страница 4: ...trained to update the manuals for previous versions of machines It s recommended that the user must follow the instructions contained in this booklet especially those concerning the safety and routine...

Страница 5: ...afety Operators have to know how to use personal protective devices and have to know the accident prevention guidelines contained in national and international laws and norms 4 1 WORKERS HEALTH AND SA...

Страница 6: ...ed to use the following personal protective equipment Protective clothing Maintenance men and operators have to wear protective clothing that complies with the basic safety requirements currently in f...

Страница 7: ...for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier than air and can cause suffo...

Страница 8: ...PERSONNEL Before any operation on the unit make sure the power supply is disconnected WARNING MOVING PARTS RISK OF DEATH Disconnect the power supply and ensure that the fan is stopped before opening t...

Страница 9: ...ssel have a limited volume The installator have to provide a further expansion vessel if it is necessary WARNING Unit water inlet pipe have to be in correspondence with the connection labelled WATER I...

Страница 10: ...able Make sure that an extractable cartridge filter and a dirt separator have been installed WARNING It is required to proceed by air purging periodically in order to eliminate the accumulated air in...

Страница 11: ...valve G Safety valve D High efficiency circulating pump with H Pressure gauge 5 5 REFRIGERANT DIAGRAM OF HP_OWER ONE 70 90 IN OUT DT ST LP HP 4WV LR EEV FL FL C CLS Pr PV PV MF SE M P C COMPRESSOR CLS...

Страница 12: ...differential circuit breakers for each electric line proper grounding for the plant etc Power cables electric protections and line fuses have to be sized according to the specifications listed in the...

Страница 13: ...unication X 5 1 Modbus RTU signal connection for remote control panel R X 4 1 Modbus RTU ground reference connection for remote control panel GNDR X 12 1 Remote control panel power supply 12V 50Hz 500...

Страница 14: ...ion and locked with fastening screws before start up WARNING The unit must be connected to the electrical network and should be in STAND BY mode powered closing the general switch in order to operate...

Страница 15: ...ause serious wounds Be very careful when operating in their surroundings After maintenance operations re install the cover panels and fix them by means of screws The refrigerant circuits must not be f...

Страница 16: ...or too high water pressures are not recommended and will not be recognized WARNING The aluminum fins are thin and sharp Be very careful to use appropriate PPE to avoid cuts and abrasions Properly pro...

Страница 17: ...phase by the manufacturer Risk due to Attentions Corrections Handling The handling may always be at risk of falling or tipping the unit Follow the instructions in the Handling paragraph and all the pr...

Страница 18: ...54 8 01 8 81 4 69 12 1 12 7 5 5 13 76 15 1 7 10 15 21 15 90 Power input 3 kW 1 47 1 85 2 89 3 2 3 45 COP 3 W W 4 47 4 33 4 19 4 3 4 41 Thermal capacity min nom max 4 kW 2 24 6 15 6 76 2 85 7 92 8 71...

Страница 19: ...h 5665 kWh warmer climate conditions 1252 kWh 1493 kWh 2164 kWh 2603 kWh 2774 kWh average climate conditions 5535 kWh 5647 kWh 6963 kWh 10090 kWh 9906 kWh colder climate conditions 8177 kWh 8823 kWh 9...

Страница 20: ...C COPd 5 11 Tj bivalent temperature Pdh 5 3 kW Tj bivalent temperature COPd 2 68 Tj Operation limit temperature Pdh 5 0 kW Tj Operation limit temperature COPd 2 34 For air to water heat pump Tj 15 C i...

Страница 21: ...C COPd 5 12 Tj bivalent temperature Pdh 5 5 kW Tj bivalent temperature COPd 2 62 Tj Operation limit temperature Pdh 5 1 kW Tj Operation limit temperature COPd 2 33 For air to water heat pump Tj 15 C...

Страница 22: ...2 C COPd 6 78 Tj bivalent temperature Pdh 7 4 kW Tj bivalent temperature COPd 2 73 Tj Operation limit temperature Pdh 6 6 kW Tj Operation limit temperature COPd 2 38 For air to water heat pump Tj 15 C...

Страница 23: ...C COPd 6 70 Tj bivalent temperature Pdh 9 7 kW Tj bivalent temperature COPd 2 50 Tj Operation limit temperature Pdh 8 9 kW Tj Operation limit temperature COPd 2 20 For air to water heat pump Tj 15 C...

Страница 24: ...2 C COPd 5 42 Tj bivalent temperature Pdh 9 8 kW Tj bivalent temperature COPd 2 55 Tj Operation limit temperature Pdh 8 7 kW Tj Operation limit temperature COPd 2 22 For air to water heat pump Tj 15 C...

Страница 25: ...kWh colder climate conditions 19616 kWh 18458 kWh 23346 kWh 31913 kWh 32713 kWh warmer climate conditions 4051 kWh 4679 kWh 7107 kWh 9036 kWh 9699 kWh average climate conditions 3 06 3 17 3 23 3 01 3...

Страница 26: ...2 C COPd 6 02 Tj bivalent temperature Pdh 4 5 kW Tj bivalent temperature COPd 1 57 Tj Operation limit temperature Pdh 4 3 kW Tj Operation limit temperature COPd 1 45 For air to water heat pump Tj 15 C...

Страница 27: ...12 C COPd 6 18 Tj bivalent temperature Pdh 5 0 kW Tj bivalent temperature COPd 1 72 Tj Operation limit temperature Pdh 4 4 kW Tj Operation limit temperature COPd 1 44 For air to water heat pump Tj 15...

Страница 28: ...12 C COPd 5 27 Tj bivalent temperature Pdh 6 7 kW Tj bivalent temperature COPd 2 00 Tj Operation limit temperature Pdh 5 7 kW Tj Operation limit temperature COPd 1 59 For air to water heat pump Tj 15...

Страница 29: ...2 C COPd 6 30 Tj bivalent temperature Pdh 9 3 kW Tj bivalent temperature COPd 1 80 Tj Operation limit temperature Pdh 8 3 kW Tj Operation limit temperature COPd 1 51 For air to water heat pump Tj 15 C...

Страница 30: ...12 C COPd 6 50 Tj bivalent temperature Pdh 9 1 kW Tj bivalent temperature COPd 1 65 Tj Operation limit temperature Pdh 7 4 kW Tj Operation limit temperature COPd 1 30 For air to water heat pump Tj 15...

Страница 31: ...abel stuck on right side panel of the unit 13 HYDRAULIC CIRCUIT AVAILABLE HEAD PRESSURE Below the characteristic curves corresponding to Head pressure Water flow without head losses of the hydronic ki...

Страница 32: ...32...

Страница 33: ...33...

Страница 34: ...feasibility study and evaluation of changes to be made according to your requests The maximum temperature that can be maintained at the outlet of the evaporator is 25 C Higher temperatures up to a ma...

Страница 35: ...35 Below the operation limits are graphed in the case of air conditioning and sanitary hot water production WATER CHILLER HEAT PUMP MODES DOMESTIC HOT WATER MODE...

Страница 36: ...low rate and pressure drop correction factors are to be applied directly to the values given for operation without glycol The water flow rate correction factor is calculated in order to get the same t...

Страница 37: ...37 464 9 454 8 393 4 912 5 120 1 173 8 IN 106 1 146 6 673 1046 7 139 5 OUT 16 3 MODELS HP_OWER ONE 140 160 IN OUT 1 M...

Страница 38: ...and those positioned on the battery side of the unit To remove the side panel pull it up in order to free the tab of the base coupling which is indicated as C in detail B and remove it 16 4 2 Mod HP_...

Страница 39: ...the front panel and then push the panel downward to remove the interlocking tab Detail A pull the panel forward to remove it 3 Twist off the screw number 12 and those placed of the battery side of the...

Страница 40: ...40 17 REGISTER OF OPERATIONS OF MAINTENANCE...

Страница 41: ...41 4 5...

Страница 42: ...a...

Страница 43: ...a...

Страница 44: ...It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 inf...

Отзывы: