background image

6

User’s operating instructions

6.4 - FROST PROTECTION MODE

The boiler is fitted with a frost protection system which will
operate automatically when the system temperature falls be-
low 6°C: the burner is automatically fired and the pump is
energized until the system’s water temperature has risen to
16°C.

If the temperature detected by the CH sensor falls below 2°C,
burner operation is automatically stopped until the tempera-
ture has risen to 5°C.

D.H.W. production (Summer mode)

Make sure the selector (B) is in position (

)

Position the D.H.W. temperature adjusting
knob (C) on the desired temperature:

COMFORT 

between 38 and 60°C, 

ECO-

COMFORT

 or 

ECO

.

Note:
By adjusting the DHW temperature at a tem-
perature very close to the one actually used
will avoid mixing hot water with cold water,
thus resulting in fuel savings and a signifi-
cant reduction of lime scale formation.

When opening a D.H.W. tap the boiler will start automatically
in order to supply water at the desired temperature.

During all the phase of D.H.W. drawing,
on the display the actual D.H.W.
temperature and the symbol (

) are

shown.

C.H. mode (Winter mode)

In order to have the boiler operating for C.H.
purposes, the pointer of the knob (B) has to
be positioned between 1 (minimum
temperature) and 2 (maximum
temperature).

If the C.H. installation is equipped with a Room thermostat,
position the pointer of the knob (B) in an intermediate position.

During the operation in C.H. mode, on
the display the actual boiler water
temperature and the symbol (

) are

shown.

Put out of operation

In order to put completely out of operation the boiler cut the
power supply to the boiler through the external main switch.

In case of long periods of inactive state of the
boiler close also the gas and cold water cocks.

B

C

To activate the anti-frost protection position the pointer of
knobs (B) and (C) as shown below.

MAX

MAX

6.2 - CHECK LIST BEFORE COMMISSIONING

THE BOILER

Before commissioning the appliance it is recommended to
check the following points:
-

Check that the On-Off gas valve, positioned upstream of
the boiler, is in the On position.

-

Check that any On-Off valves fitted on the flow and return
pipes for servicing purposes are in the On position.

-

Check that any On-Off valves fitted on the cold water inlet
for servicing purposes are in the On position.

-

Check that the pressure relief valve drainage pipe is con-
nected to the sewage system.

-

Check that the boiler is connected to the electrical supply;
the display on the panel board has to be illuminated.

-

Check the heating system pressure,  indicated by the pres-
sure gauge. For correct operation the pressure should be
between 0,8 and 1 bar (with the pump not running).
If the pressure falls below 0,7 bar restore the correct pres-
sure by regulating the filling valve when the system is cold
and the boiler not operating (refer to paragraph 6.5).

6.3 - BOILER  OPERATION

Содержание Alkon 09 R 18

Страница 1: ...00333177 1st edition 06 2009 ALKON 09 R 18 C 18 R 24 C 24 USER SOPERATING INSTRUCTIONS ...

Страница 2: ...or it is essential to carefully follow the instructions indicated in this guide 3 WATER TREATMENT The hardness of the mains water supply conditions the frequency with which the heat exchanger is cleaned In hard water areas where the main water can exceed 15 f total hardness a scale reducing device is recom mended The choice of this device has to be made taking into consideration the water s charac...

Страница 3: ...e held liable for any such injury and or damage 4 INFORMATION TO BE HANDED OVER TO THE USER BY THE INSTALLER 5 SAFETY WARNINGS WARNING The installation adjustment and servicing of this appliance must be carried out by a competent person and installed in accordance with the current standards and regulations Failure to correctly install this applian ce could cause injury to persons animals or damage...

Страница 4: ...ng water temperature which can be adjusted between a minimum of 30 C and a maximum of 85 C D H W temperature controller In the ALKON R models this function is active only if the boiler is connected to an external D H W storage tank Through this knob it is possible to adjust the temperature of the D H W NOTE In the ALKON R models not connected to an external D H W storage tank the pointer of the kn...

Страница 5: ...s shown flashing on the display Reset button By pressing this push button it is possible To restart the boiler after a lockout due to the burner control which has lit on the display the symbol To have the error code shown on the display if the boiler operation was not stopped by this fault To activate the special function for calibration To enter the Service Menu and select the parameters Indicati...

Страница 6: ...mostat position the pointer of the knob B in an intermediate position During the operation in C H mode on the display the actual boiler water temperature and the symbol are shown Put out of operation In order to put completely out of operation the boiler cut the power supply to the boiler through the external main switch In case of long periods of inactive state of the boiler close also the gas an...

Страница 7: ...r Sales Service Centre C Error code Meaning Too low water pressure in the C H circuit Elimination of the fault Restore the correct pressure value by regulating the boiler s filling valve for correct boiler operation the pressure should be between 0 8 and 1 bar When the correct pressure value has been reached the led will switch off automatically and normal boiler operation will be restored DANGER ...

Страница 8: ...al ag info unical ag com The Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press Also reserves the right to bring those changes that it will hold necessary to it own products or profits without jeopardizing its essential characteristics ...

Отзывы: