UNI-T UT581 Скачать руководство пользователя страница 2

P/N:110401104493X

3.4  Operational Voltage: 230VAC/50Hz  (Voltage Range: 

                                        195 – 253 V)

3.5  Working Environment: Temperature: 0

~40

       Relative Humidity: ≤80%RH  
       Altitude: ≤2000 meter
3.6  Storage Condition: 
       Temperature: -20

~60

       Relative Humidity:  ≤75%RH
3.7  Product Size: 160mmx70.5mmx100mm
3.8  Product Net Weight: About 500g
3.9  Standard Accessories:
       Test Leads(1.5 meter)        1 pc
       English Mnaual  

                         1 pc

       Carrying Case  

                           1 set

4. Tester Description (See Figure 1, 2)

Figure  1

Figure  2

① 

LCD Display

② 

PHASE Button

③ 

I

n

 Button

④ 

TEST Button

⑤ 

Wiring LED Indicators

⑥ 

Rotary Switch

⑦ 

Test Terminals

⑧ 

Test Leads

 Red (Live)
Green ( Earth )
 Blue ( Neutral )

5. Making Measurements 

 

 

 

6. Maintenance & Repair

This operating manual is subject to change without notice.

** END **

(1) Test Lead Connections

     Insert three connectors of test leads respectively into three termi

     -nals of the Tester: Red to L, Green to E, Blue to N, and then 

     connect another end of test leads to tested circuit (power socket 

     230V/50Hz).

                                               Danger

 ● Do not touch any exposed metal or conductor during these 

     test operations.

 ● Relative components in the Tester may get hot during the 

    operation, if the Tester continues to work for a long time, it 

    may cause damage to the unit or other hazards. Therefore 

    the Tester is recommended not to use for a long-time and 

    continuous tests on production lines in RCD factories .It is 

    only suitable for sampling precision tests.

 ● The time interval between each test with trip current 300mA

    /500mA(large current trip test) should be ensured up to 5 

    minutes.

6.1 Cleaning the Casing: 

Clean the surface of the Tester with dry soft cloth; No alcoholic and 

solvent is allowed, for it may cause corrosive damage to the LCD; 

Protect the Tester from any moisture.

6.2 Repair

 Please contact our after-sale service center or agents if following 

 issues happen:

A. The Tester casing is broken or the components are damaged;

B. LCD display works abnormally;

C. Unexpected data occur under normal use;

D. The buttons don’t function normally; 

E. Noise happen during tests. 

(4) Taking RCD Tests

4.1 Set the rotary switch to test parameters

● Non-Tripping -------------------×1/2: Max. trip time up to 1000ms;

● Tripping -------------------------×1: Max. trip time up to 1000ms (Except 

                                                500mA);

● Tripping -------------------------×1(500mA): Max. trip time up to 300ms ;        

● Fast Tripping------------------- ×5( only 10, 20, 30mA ): Max. trip time 

                                                up to 1000ms;

● Fast Tripping--------------------250mA: Max. trip time up to 40ms (for 

                                                UT581 only);

● AUTO RAMP Test: for UT582 only, 20%~110% of rated trip current

   (I

n), Max. trip time up to 300ms.

4.2 Press TEST button

● Non-Tripping Test -------The RCD should not trip.

● Tripping --------------------The RCD should trip.

● ×5 Fast Tripping: ----------- The RCD should trip.

● 250mA Fast Tripping: -------The RCD should trip (for UT581 only).

● AUTO Ramp Test: ---------- The RCD should trip, and trip time and 

   trip current are displayed simultaneously (for UT582 only).

4.3 Press PHASE (0 /180 ) button to set the phase angle and repeat 

      4.2 to determine the fastest trip time.

4.4 Press to change the phase angle and repeat 4.2

4.5 When the tests finish, disconnect the test lead from the tested 

      circuit immediately.

                            

(2) Wiring Check

     Check the wiring status by identifying three LEDs. If P-E and P-N 

     green LEDs are on and red LED is off, it indicates the wiring is 

     correct, otherwise wiring is wrong due to reverse connection 

     between L and N terminals or bad grounding. Please unplug the 

     test leads, check and correct the relative circuits until right wiring 

     indication is obtained.

    

 

(3)

 Press I

n button to adjust the trip current(I

n) the same as the 

     rated trip current marked on RCD. The set trip current will show 

     on lower part of LCD.

 Default value: I

n----------------- 30mA

                        0 /180 ----------- 0

Caution:

 Reverse connection between L and N terminals during  

 wiring check may cause RCD to trip, so please check and correct   

 the circuits until the wiring indication is obtained and before you   

 proceed into next operation.

                                               

                                                   Danger

    Do not proceed into next operation (press TEST button) if the 

    wiring is incorrect, otherwise it may cause error to the result or 

    other hazards.