PS-R-01
Outdoor Temperature Sensor
Installation and Operation Manual
The PerfectSense
™
PS-R-01 Outdoor Sensor is designed to sense
temperature at remote outdoor locations and send this information to
the PerfectSense Thermostat. This sensor can be used with the PS4000
and PS5000 thermostat models. The sensor can be used as a stand alone
sensor or as part of an averaging network. Once a sensor is connected to
the thermostat, the thermostat’s built-in sensor is no longer used. The
thermostat’s installer set-up parameters should be modified to tell the
thermostat that a remote outdoor temperature sensor is being used. The
temperature reading on the thermostat’s display will be the temperature at
the remote sensor location
.
Please take time to read and understand these instructions as proper
installation of the PS-R-01 will ensure an accurate and reliable
temperature sensor.
IMPORTANT SAFETY INFORMATION
WARNING: ELECTRICAL SHOCK HAZARD – Turn off power
at the main power source by unscrewing fuse
or switching circuit breaker to the OFF position
before installing, removing, or cleaning this
thermostat/sensor.
WARNING: FIRE AND ELECTRIC SHOCK HAZARD – This
device should be installed by a qualified
service technician with due regard for safety
as improper installation could result in a fire
and electric shock hazard.
WARNING: FIRE AND ELECTRICAL SHOCK HAZARD – This is
a 24V AC low-voltage thermostat. Do not install
on voltages higher than 30V AC.
• Do not switch system to cool if the temperature is below 50°F (10°C).
This can damage your cooling system and may cause personal injury.
• Do not short (jumper) across terminals on the gas valve or at the system
control to test installation. This will damage the thermostat and void
the warranty.
• All wiring must conform to local and national building and electrical
codes and ordinances.
• Use this thermostat and sensor only as described in the manual.
OVERVIEW
The PS-R-01 temperature sensor includes the sensor with lead wires
attached. Use an appropriate mounting clip to attach the sensor to the
surface. The PS-R-01 temperature sensor is connected to a thermostat as
an external sensor. The thermostat must be configured appropriately.
When installing this product:
1.
Read these instructions carefully. Failure to follow them could damage
the product or cause a hazardous condition.
2.
Check the ratings given in the instructions and on the product to make
sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4.
After installation is complete, check out the product operation as
provided in these instructions.
WARNING: ELECTRIC SHOCK HAZARD – Can cause electrical
shock or equipment damage. Disconnect power
supply before connecting wiring.
SET-UP
Mount the sensor where there is good air circulation so it can measure
true outdoor ambient temperature. Be sure the mounting surface is flat
and the wire distance between the PS-R-01 and the thermostat is less
than 200 feet, Figure 1.
1.49 in (38mm)
0.1
7in
(4.2
m
m )
R1.6
in.(4
mm
)
1.82 in (46.3mm)
R0
.04
in
(1m
m)
R0
.09
8
in
(2.5
m
m
)
1.10 in (28.1mm)
0.62
in
(16m
m
)
1.56 in .(39.7mm)
0.24 in
(6.2mm)
0.44 in
(11.2mm)
R0.0
98
in
(2.5
mm
)
0.08 in
(2mm)
Figure 1. Typical locations
for outdoor sensor
Figure 2. Mounting clip
Do NOT mount the sensor in direct sunlight or where hot or cold air blows
on the sensor. Discharge from an outdoor compressor unit, vent or fan
causes inaccurate temperature readings. Do not mount where snow, ice
or debris can cover it.
Mark the area on the location selected for attaching the sensor mounting
clip. Use an appropriate mounting clip, Figure 2, and mount the clip.
WIRING
ATTENTION : ELECTRICAL INTERFERENCE (NOISE) HAZARD
Can cause erratic temperature readings and
system operation.
Keep wiring at least one foot away from large inductive loads such as;
motors, line starters, lighting ballasts and large power distribution panels.
Use shielded cable to reduce interference when rerouting is not possible.
Make certain the wiring connections are secure.
WARNING: ELECTRIC SHOCK HAZARD – Can cause electrical
shock or equipment damage. Disconnect power
supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and regulations.
Wire the PS-R-01 outdoor sensor to S1 and S2 terminals on the
thermostat. If the lead wire provided is not long enough (9.48 ft [3 m]),
run a color-coded, 18 gauge 2-wire to the mounting location, refer to
Figure 3. Pigtail wiring may be used.
Mount the PS-R-01 in its mounting clip. Plug the wiring hole using non-
hardening caulk or putty.
Wiring hole through structure
Figure 3. Wire routing
OPERATION
Once installed and the Thermostat Installer Setup Number 0340 is set to
1 or 2 (3 for indoor mounting), the outside temperature can be displayed
on the thermostat.
TUE
AM
Room
Running As SCHED
Set To
SYSTEM
HEAT
MORE SCHED HOLD CLOCK SCREEN
AUTO
FAN
Outside
Figure 4. PS4000 display
SPECIFICATIONS
Mounting
38mm spaced
Sensor
10K ohm NTC type II
Operating temperature
-40°F to 170°F (-40°C to 80°C)
Display range
32°F to 99°F (0°C to 37°C)
Sensor accuracy
+/- 1.5°F at 77°F (25°C)
Operating relative humidity 5% to 95% non-condensing
Dimensions
Outdoor sensor with 9.84 ft (3m) leadwires
Transmitter power
<0.1 watt
Warranty
5 Years
CHECKOUT
The PS-R-01 outdoor temperature sensor converts outdoor ambient
temperature to a resistance that the thermostat can interpret.
The PS-R-01 has a negative temperature coefficient (NTC), which means
that resistance decreases as the temperature increases. Refer to Tables 1
and 2, Sensor resistance at room temperature.
With an accurate thermometer [+/- 1°F (0.5°C)] measure the temperature
at the sensor location, allowing time for the thermometer to stabilize
before reading.
To verify sensor resistance, remove one wire from the PS-R-01 remote
sensor. Use an ohmmeter to measure the resistance across the sensor.
Then verify the sensor accuracy with the temperature/resistance in
Table 1. Any difference in the temperature readings may be offset using
the thermostat’s settings.
CALIBRATION
The PS-R-01 outdoor sensor is calibrated at the factory and cannot be
recalibrated in the field.
Table 1. Sensor resistance at room temperature - °F
Room
Temperature
Ohms of
Resistance
Room
Temperature
Ohms of
Resistance
Room
Temperature
Ohms of
Resistance
℉
℉
℉
-1
88610
44
23394
89
7471
0
86041
45
22760
90
7307
1
83266
46
22146
91
7107
2
80679
47
21565
92
6954
3
78068
48
21006
93
6783
4
74850
49
20548
94
6645
5
72214
50
19914
95
6481
6
70705
51
19395
96
6318
7
68855
52
18881
97
6185
8
66584
53
18388
98
6040
9
64620
54
17904
99
5917
10
62636
55
17432
100
5764
11
60723
56
16983
101
5649
12
58858
57
16553
102
5522
13
57092
58
16124
103
5426
14
55351
59
15696
104
5314
15
53744
60
15310
105
5184
16
52229
61
14923
106
5075
17
50603
62
14536
107
4940
18
49087
63
14160
108
4834
19
47619
64
13801
109
4719
20
46202
65
13475
110
4626
21
44825
66
13110
111
4519
22
43553
67
12831
112
4430
23
42308
68
12504
113
4324
24
41098
69
12154
114
4230
25
39901
70
11868
115
4153
26
38757
71
11556
116
4066
27
37640
72
11300
117
3992
28
36568
73
11001
118
3901
29
35538
74
10760
119
3821
30
34548
75
10478
120
3724
31
33603
76
10259
121
3660
32
32670
77
10000
122
3589
33
31762
78
9736
123
3490
34
30865
79
9518
124
3420
35
31014
80
9267
125
3343
36
29200
81
9064
126
3279
37
28455
82
8828
127
3206
38
27667
83
8636
128
3146
39
26853
84
8409
129
3076
40
26145
85
8242
130
3026
41
25396
86
8049
131
2970
42
24717
87
7835
132
2893
43
24043
88
7661
133
2832
by Uni-Line®
by Uni-Line®
par Uni-Line®
by Uni-Line®
PS-R-01
Capteur intérieur de température
Manuel d’installation et de fonctionnement
Le capteur extérieur PS-R-01 de la série PerfectSense™ est conçu pour
relever la température extérieure sur un site distant et envoyer cette
information au thermostat PerfectSense™. Ce capteur peut être utilisé avec
les modèles de thermostat PS4000 et PS5000. Ce capteur peut fonctionner
de façon autonome ou faire partie intégrante d’un réseau de surveillance.
Une fois qu’un capteur est connecté à un thermostat, le capteur intégré à
ce dernier n’est plus utilisé. Les paramètres de configuration du thermostat
doivent être modifiés pour qu’il sache qu’un capteur de température
extérieur distant est utilisé. La valeur de température affichée sur l’écran du
thermostat correspondra à celle relevée à l’endroit où se trouve le capteur
distant.
Prendre le temps de lire et d’assimiler ces instructions car une bonne
installation du PS-R-01, garantira que le capteur puisse détecter la
température de façon fiable et précisément.
INFORMATIONS IMPORTANTES CONCERNANT LA SÉCURITÉ
AVERTISSEMENT:
RISQUE D’ÉLECTROCUTION - Couper le
courant secteur en retirant le fusible
ou en coupant le disjoncteur avant
d’installer, d’enlever ou de nettoyer ce
thermostat/capteur.
AVERTISSEMENT:
RISQUES D’INCENDIE ET
D’ÉLECTROCUTION – Cet appareil doit
être installé par un technicien qualifié
dans le strict respect des consignes de
sécurité, car une mauvaise installation
pourrait comporter un risque d’incendie
et d’électrocution.
AVERTISSEMENT:
RISQUES D’INCENDIE ET
D’ÉLECTROCUTION - Cet appareil est
un thermostat basse tension en 24V
AC. Ne pas installer si les tensions sont
supérieures à 30V AC.
• Ne pas indiquer au système de rafraîchir si la température est
inférieure à 50 °F (10 °C). Cela peut endommager le système de
climatisation et causer des lésions corporelles.
• Ne pas court-circuiter les bornes (cavalier) de la soupape à
gaz ni au niveau du régulateur pour tester l’installation. Cela
endommagerait le thermostat et annulerait la garantie.
•
L’ensemble du câblage doit être conforme aux codes et décrets
locaux et nationaux de la construction et de l’électricité.
• N’utiliser ce thermostat que de la manière indiquée dans ce
manuel.
APERÇU
Le capteur de température PS-R-01 inclut le capteur avec les fils
conducteurs attachés. Utiliser un clip de montage approprié pour attacher
le capteur à la surface. Le capteur de température PS-R-01 est connecté
au thermostat comme un capteur externe. Le thermostat doit être
configuré correctement.
www.robertshaw.com
©2016 Robertshaw
8/16 – 352-00257-001
Robertshaw®, Uni-Line® and PerfectSense
™
are trademarks of
Robertshaw, its subsidiaries and/or affiliated companies. All other brands
mentioned may be the trademarks of their respective owners.
Customer Service Telephone 1.800.304.6563
[email protected]
For Technical Service
Telephone 1.800.445.8299
Table 2. Sensor resistance at room temperature - °C
Room
Temperature
Ohms of
Resistance
Room
Temperature
Ohms of
Resistance
Room
Temperature
Ohms of
Resistance
℃
℃
℃
-21
105084
13
17312
47
4014
-20
99077
14
16510
48
3862
-19
93449
15
15751
49
3716
-18
88175
16
15030
50
3588
-17
83229
17
14347
51
3443
-16
78590
18
13698
52
3315
-15
74238
19
13083
53
3192
-14
70152
20
12499
54
3075
-13
66316
21
11944
55
2963
-12
62712
22
11416
56
2855
-11
59325
23
10916
57
2752
-10
56141
24
10440
58
2653
-9
53147
25
10000
59
2558
-8
50330
26
9556
60
2467
-7
47679
27
9147
61
2380
-6
45184
28
8757
62
2297
-5
42833
29
8386
63
2216
-4
40619
30
8033
64
2139
-3
38533
31
7697
65
2065
-2
36565
32
7377
66
1994
-1
34710
33
7072
67
1926
0
32960
34
6781
68
1861
1
31308
35
6503
69
1798
2
29748
36
6239
70
1737
3
28276
37
5987
71
1679
4
26884
38
5746
72
1623
5
25570
39
5516
73
1569
6
24327
40
5297
74
1518
7
23152
41
5088
75
1468
8
22040
42
4888
76
1420
9
20988
43
4697
77
1374
10
19993
44
4514
78
1330
11
19050
45
4340
79
1287
12
18158
46
4173
80
1246