INSTRUCTIONS FOR AUTOMATIC TEST 

(SELF DIAGNOSTICS /SELF-TEST FUNCTION OF EMERGENCY LIGHTING) 
 

Battery charging time: 24h 

 
 

1 ) Install the lighting fixture according to the installation manual 

 

 

2 ) After switching on the unit, it automatically carries out the following self-test: 
 

24 hours after the installation 

Performing a 3 hours long term test

 

Each 10 seconds: 

 

Performing a quick test to check if the battery is connected

 

Weekly:  

 

 

Performing a 5s function test, check for battery interruption, charger error, lamp failure or led driver failure

 

Yearly:   

 

 

Performing a 3 hours long term test 

 
All test functions are preset at the factory and do not have to be adjusted on site. If needed all the parameters can be adjusted through the DALI line.

 

 

 

3 ) Meaning of the two colors LED status displays 

 

         Green

 

lights up 

ready/ normal operation 

flashes   

Test mode 

 

         Red

 

Maintenance required 

 

Green 

Fast flashing, 
0.1 second On / 0.1 second Off 

Function test 

Green

 

Slow flashing 
1 second On / 1 second Off 

Long term test 3h 

Green 

Double pulsing 

Inhibit Mode, can be activate through the DALI line. In this mode the unit is disabled for DC 
operation. Useful if the unit is temporary not used for emergency when the power cut off but 
the tests are maintained and the battery remains used. (good for the battery) 

Red

 

Lights up 

Circuit board failure Charger failure, short circuit 

Red

 

Slow flashing 
1 second On / 1 second Off 

Battery failure 

No LED 

No LED 

In battery operation, DC mode 

        / 

Flashing red then green 

During DALI Addressing process 

 

Technische Änderungen vorbehalten  /  Les détails techniques sont sujet à des changements. 
Technical Details are subject to change. 