Ultra-Aire SD12 Installer’s & Owner’s Manual

FOR HVAC INSTALLER ONLY

3.1B Condensing Unit Location

The condensing unit should be located outside of the conditioned 
space, but as close as possible to the dehumidifier to minimize the 
length of the connecting lines. The maximum line set length is 50 feet. 
In all cases keep the following cautions in mind:
• Install the condensing unit with space to access the top and side pan-
els for maintenance and service. DO NOT INSTALL CONDENSING UNIT 
WITH THE TOP PANEL OR SIDE PANELS INACCESSIBLE (See FIGURE 2 for 
diagram).
• Avoid discharging air directly at people, or over the water near pool 
areas.
• If used near a pool or spa, be certain there is NO chance the  
condensing unit could fall into the water or be splashed and that it is  
supplied by a GROUND FAULT INTERRUPTER. 
• Place the condensing unit where it is protected from extreme outdoor 
weather (rain, wind, etc…)
• Place the condensing unit on a level pad (or bracket) where the unit 
can be securely attached by the base.
• Place the condensing unit at least 1” above ground level
• Place the condensing unit where there is adequate space for the unit 
and the air required by the unit
• DO NOT place the condensing unit where the sound and vibration 
caused by the running unit will cause a nuisance.
• DO NOT use the condensing unit as a bench or table. 
• DO NOT place the condensing unit in direct sunlight.
• The minimum installation clearances for the condensing unit are  
shown below.

 

 ROOF DAMAGE!

 

THIS SYSTEM CONTAINS 

BOTH REFRIGERANT AND OIL. SOME RUBBER ROOFING MATERIAL 
MAY ABSORB OIL AND CAUSE THE RUBBER TO SWELL WHEN IT 
COMES INTO CONTACT WITH OIL. THE RUBBER WILL THEN BUBBLE 
AND COULD CAUSE LEAKS. PROTECT THE ROOF SURFACE TO 
AVOID EXPOSURE TO REFRIGERANT AND OIL DURING SERVICE AND 
INSTALLATION. FAILURE TO FOLLOW THIS NOTICE COULD RESULT  
IN DAMAGE TO ROOF SURFACE.

Mount the base of the condensing unit to a sturdy level pad (or bracket) 
using 3/8” (10mm) bolts. The condensing unit may be mounted to a 
wall (with brackets) or placed on a roof. Ensure the mounting of the 
condensing unit can withstand strong winds and earthquakes when 
mounting above ground level. Vibration dampening material may be 
installed between the condensing unit base and the mounting pad if 
required. The base dimensions of the condensing unit are shown in 
FIGURE 2.

3.2 Electrical Requirements 

 WARNING!

 

ELECTRIC SHOCK HAZARD. CAN CAUSE 

INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE 
WITH NATIONAL AND LOCAL CODES. DISCONNECT ALL REMOTE 
ELECTRIC POWER SUPPLIES BEFORE OPENING ACCESS PANEL.  
UNIT MAY HAVE MULTIPLE POWER SUPPLIES.

Field wiring must comply with the National Electric Code (C.E.C. in 
Canada) and any applicable local codes or ordinances.

 WARNING!

 

DO NOT ALLOW THE YELLOW LEAD TO 

CONTACT THE RED LEAD OR WHITE LEAD FROM THE ULTRA-AIRE 
DEHUMIDIFIER OR THE TRANSFORMER WILL BE DAMAGED.

3.2A Dehumidifier Electrical Power Connections

The Ultra-Aire SD12 Dehumidifier unit plugs into a common 120Vac 
grounded outlet. The Dehumidifier draws less than 2A and can be 
plugged into a shared branch circuit. If installed in a wet area (or 
basement prone to flooding), a ground fault interrupter protected 
circuit is required (See FIGURE 3 for schematic).

4033178

LINE

NEUTRAL

DEHU.

RELAY

BLOWER

RELAY

BLOWER

XFMR

DEHU.

RELAY

COIL

BLOWER

RELAY

COIL

DEFROST

T-STAT

L. PRESS

SWITCH

RUN

CAP.

NC

NO

YEL-6

BLU-7

GRN-5

PNK

-3

WHT

-4

RED-1

YEL-2

BLK-9

BLK-8

BLK

BLK

BLK-3

WHT

-5

BLK-2

BL

U-2

115V

24V

COM

COM

BRN-3

BLK-1

BLK

-1

+24VAC

DEHU

FAN

COM

CUSTOMER

CONTROL

WIRING

BLU

YEL

GRN

RED

BLK

BLK

24VAC TO

COND.

GRN-4

NO

BLK-5

VIO-6

MIN

5.88 IN

MIN

7.88 IN

MIN

23.63 IN

MIN

9.88 IN

10.06

5.62

19.69

5.62

GRAPHIC SHOWS MINIMUM DISTANCE REQUIRED FOR 
CONDENSING UNIT AND THE FOOTING DIMENSIONS

FIGURE 2: MINIMUM DISTANCE REQUIRED FOR CONDENSING 
UNIT AND THE FOOTING DIMENSIONS

FIGURE 3: DEHUMIDIFIER WIRING DIAGRAM

Содержание 4033170

Страница 1: ...gher temperature to provide additional cooling if needed By eliminating the HVAC system s need to control latent load the Ultra Aire SD12 allows the system to work more efficiently Fresh Air Ventilation Optional fresh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and replenish oxygen content in the building The amount of fresh air vent...

Страница 2: ...stallation in an Attic with an Existing Forced Air HVAC System 13 3 9F Installation in a Structure with Two Forced Air HVAC Systems 13 3 9G Installation in a Structure with No Existing Forced Air HVAC System 13 3 10 Quiet Installation 13 3 11 System Start Up 13 4 Controls 13 14 5 Optional Dehumidifier Ventilation System Controller 15 6 Maintenance 16 6 1 Standard Air Filter 16 6 2 High Efficiency ...

Страница 3: ...ly before installing and operating this device Proper adherence to these instructions is essential to obtain maximum benefit from your Ultra Aire SD12 indoor air quality system WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTAINCE CAN CAUSE PERSONAL INJURY LOSS OF LIFE OR DAMAGE TO PROPERTY INSTALLATION AND SERVICE MUST BE PERFORMED BY A LICENSED PROFESSIONAL INSTALLER OR EQUIV...

Страница 4: ...hed living area or above an area where water leakage could cause damage Place the Ultra Aire SD12 on supports that raise the base of the unit 2 5 above the drain pan beneath it Raising the Ultra Aire SD12 will help the dehumidifier drain with gravity flow Do not place the Ultra Aire SD12 directly on structural building members without vibration absorbers or unwanted noise may result The Ultra Aire...

Страница 5: ...T IN DAMAGE TO ROOF SURFACE Mount the base of the condensing unit to a sturdy level pad or bracket using 3 8 10mm bolts The condensing unit may be mounted to a wall with brackets or placed on a roof Ensure the mounting of the condensing unit can withstand strong winds and earthquakes when mounting above ground level Vibration dampening material may be installed between the condensing unit base and...

Страница 6: ... sunlight or near a pool or spa The installer must supply the control wiring between the Ultra Aire SD12 dehumidifier the condensing unit the remote control and any electrical accessories Carefully route the control wiring to prevent damage during installation Be careful not to cross the wires when connecting the Ultra Aire SD12 Dehumidifier and the remote control or damage to the transformer may ...

Страница 7: ...ter use either metal strapping material or anchored heavy nylon wire ties ANCHORED HEAVY NYLON WIRE TIRE OR AUTOMOTIVE MUFFLER TYPE HANGER AUTOMOTIVE MUFFLER TYPE HANGER WALL STUD STRAP LIQUID LINE TO VAPOR LINE LIQUID LINE VAPOR LINE WRAPPED IN ARMAFLEX NON CORROSIVE METAL SLEEVE VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE CALK PVC PIPE FIBERGLASS INSULATION OUTSIDE WALL 8 FEET STRAPPING MATERIA...

Страница 8: ...h stub tubes of condensing unit These service ports can be used to introduce and release nitrogen during brazing Use the following procedure to connect the line set to the Dehumidifier CAUTION THE DEHUMIDIFIER IS SHIPPED FROM THE FACTORY PRESSURIZED WITH A CHARGE OF INERT GAS AND WITH RUBBER PLUGS IN THE LINES PURGE THE INERT GAS FROM THE DEHUMIDIFIER BY REMOVING THE RUBBER PLUGS IN THE LIQUID AND...

Страница 9: ...ECOVERED RESPONSIBLY FAILURE TO FOLLOW THIS WARNING MAY RESULT IN PERSONAL INJURY OR DEATH 1 Connect the HFC 410A manifold gage set high pressure hose to the service port on the suction gas line Note Connecting the high pressure hose to the service port on the gas line will protect the manifold gage set from high pressure damage during leak testing Cap liquid line service port 2 Make sure all of t...

Страница 10: ... to charge the system FOR HVAC INSTALLER ONLY 3 7 Charging the System The condensing unit is pre charged with 42 oz of HFC 410A refrigerant The installer will add HFC 410A refrigerant for the dehumidifier and line set 1 Calculate the amount of HFC 410A required by determining the length of the line set and performing the calculation below i 11oz 2 2oz per every 10 feet of line set length Total cha...

Страница 11: ...eparate supply duct from the Ultra Aire SD12 to each isolated area is recommended DO NOT draw air directly from the kitchen laundry or isolated basement You may draw air from a basement that is open to the home All flexible ducting connected to the Ultra Aire SD12 should be UL listed The inlet of the Ultra Aire SD12 is the 10 diameter hole in the filter enclosure of the unit A 10 round collar is s...

Страница 12: ...lter enclosure of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on the size and occupancy of the residence If you are unsure of your ventilation air requirements consult the factory by calling 1 800 533 7533 for assistance or check your local building codes 3 9D Instal...

Страница 13: ...f the struc ture such as bedrooms den etc By ducting this way the air inside the structure will circulate through the Ultra Aire SD12 to be filtered and dehumidified Avoid discharging all the air from the dehumidifier in one location to prevent overcooling that area 4 diameter duct is recommended for branches to the bedrooms 6 diameter duct is recommended for branches to larger areas Refer to sect...

Страница 14: ...DAMAGE the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green wires Accessory power 24volt AC power supply available for HVAC accessories between yellow and white and or red wire Red and white wires are common with each other FIGURE 15 Ultra Aire DEH 3000 Dehumidification Ventilation Control YELLOW BLUE GREEN WHITE Internal Connections OPTIONAL DAMPER 24...

Страница 15: ...nt 35 min 70 max Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 F Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n Fan Filter Operation n Programmable Ventilation Timer n Large easy to read backlit LCD display n Easy interaction with air handler fan Interlock Lockout n High Temperature Cut Out n Dryout Cycle Timer n Auto...

Страница 16: ...d during the seasons when there are many particles in the outdoor air 6 5 Condensing Unit Maintenance The compressor and fan motor inside the condensing unit are permanently lubricated for many years of normal operation so maintenance is not required Keep the condensing unit clean and free from debris Check the coil and other openings on the condensing unit for debris that will obstruct airflow Th...

Страница 17: ...unplugged or no power to outlet 2 Loose connection in dehumidifier fan circuit 3 Obstruction prevents fan impeller rotation 4 Defective fan 5 Defective fan relay 6 Defective impeller run capacitor Low dehumidification capacity evaporator is frosted continuously Dehumidification is being called for 1 Defrost thermostat loose or defective Sec 7 9 2 Low refrigerant charge 3 Dirty air filter s or dehu...

Страница 18: ...st be replaced if continuity exists across its terminals If there is no needle movement with the meter set on the Rx100000 FOR HVAC INSTALLER ONLY scale the capacitor is open and must be replaced 4 Mark the location of the fan blade on the motor shaft Remove the fan blade from the motor shaft and slide it to the front of the condensing unit 5 Disconnect the fan leads inside the electric box 6 Remo...

Страница 19: ...tor and an over sized liquid line filter In a running burn out install an oversized suction line filter drier be tween the accumulator and compressor Thoroughly flush the accumu lator with refrigerant to remove all trapped sludge and to prevent the oil hole from becoming plugged A standing burn out does not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accur...

Страница 20: ...ing is correct and that voltage is present at the damper motor 2 Check for any obstruction inside the damper If the electric ventilation damper fails to operate after performing these checks it must be replaced 7 11 Condensate Pump Kit An optional condensate pump kit is available from the factory for use with the Ultra Aire SD12 Condensate is automatically pumped to a remote location when the wate...

Страница 21: ...ICE PARTS LIST Condensing Unit Item Part No Qty Description 2 4033211 1 Nut 3 4033212 1 Fan Axial 16 4033213 1 Compressor 20 4033214 1 Capacitor 23 4033216 1 Capacitor Fan Motor 30 4033215 1 Motor 31 4022484 1 Relay Item Part No Qty Description 6 4029508 1 Low Pressure Switch 7 4026657 1 Impeller 8 4033031 07 1 Blower Capacitor Run 15 MFD 370V 9 4020924 2 Blower Relay SPDT 24V 15A 10 4022487 1 XFM...

Страница 22: ...f mounting hardware from inside the rectangle opening Mount the duct collars to the front of the dehumidifier using screws provided Collars and hardware are located here Door Install Insert tab on the bottom of the door in between the foam installation and the metal side Push down on the plastic door latch and swing door shut Once the door is shut release the door latch DOOR AND COLLAR ASSEMBLY 40...

Страница 23: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining war ranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the a...

Страница 24: ......

Отзывы: