5
Ultra-Aire SD12 Installer’s & Owner’s Manual
FOR HVAC INSTALLER ONLY
3.1B Condensing Unit Location
The condensing unit should be located outside of the conditioned
space, but as close as possible to the dehumidifier to minimize the
length of the connecting lines. The maximum line set length is 50 feet.
In all cases keep the following cautions in mind:
• Install the condensing unit with space to access the top and side pan-
els for maintenance and service. DO NOT INSTALL CONDENSING UNIT
WITH THE TOP PANEL OR SIDE PANELS INACCESSIBLE (See FIGURE 2 for
diagram).
• Avoid discharging air directly at people, or over the water near pool
areas.
• If used near a pool or spa, be certain there is NO chance the
condensing unit could fall into the water or be splashed and that it is
supplied by a GROUND FAULT INTERRUPTER.
• Place the condensing unit where it is protected from extreme outdoor
weather (rain, wind, etc…)
• Place the condensing unit on a level pad (or bracket) where the unit
can be securely attached by the base.
• Place the condensing unit at least 1” above ground level
• Place the condensing unit where there is adequate space for the unit
and the air required by the unit
• DO NOT place the condensing unit where the sound and vibration
caused by the running unit will cause a nuisance.
• DO NOT use the condensing unit as a bench or table.
• DO NOT place the condensing unit in direct sunlight.
• The minimum installation clearances for the condensing unit are
shown below.
ROOF DAMAGE!
THIS SYSTEM CONTAINS
BOTH REFRIGERANT AND OIL. SOME RUBBER ROOFING MATERIAL
MAY ABSORB OIL AND CAUSE THE RUBBER TO SWELL WHEN IT
COMES INTO CONTACT WITH OIL. THE RUBBER WILL THEN BUBBLE
AND COULD CAUSE LEAKS. PROTECT THE ROOF SURFACE TO
AVOID EXPOSURE TO REFRIGERANT AND OIL DURING SERVICE AND
INSTALLATION. FAILURE TO FOLLOW THIS NOTICE COULD RESULT
IN DAMAGE TO ROOF SURFACE.
Mount the base of the condensing unit to a sturdy level pad (or bracket)
using 3/8” (10mm) bolts. The condensing unit may be mounted to a
wall (with brackets) or placed on a roof. Ensure the mounting of the
condensing unit can withstand strong winds and earthquakes when
mounting above ground level. Vibration dampening material may be
installed between the condensing unit base and the mounting pad if
required. The base dimensions of the condensing unit are shown in
FIGURE 2.
3.2 Electrical Requirements
WARNING!
ELECTRIC SHOCK HAZARD. CAN CAUSE
INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE
WITH NATIONAL AND LOCAL CODES. DISCONNECT ALL REMOTE
ELECTRIC POWER SUPPLIES BEFORE OPENING ACCESS PANEL.
UNIT MAY HAVE MULTIPLE POWER SUPPLIES.
Field wiring must comply with the National Electric Code (C.E.C. in
Canada) and any applicable local codes or ordinances.
WARNING!
DO NOT ALLOW THE YELLOW LEAD TO
CONTACT THE RED LEAD OR WHITE LEAD FROM THE ULTRA-AIRE
DEHUMIDIFIER OR THE TRANSFORMER WILL BE DAMAGED.
3.2A Dehumidifier Electrical Power Connections
The Ultra-Aire SD12 Dehumidifier unit plugs into a common 120Vac
grounded outlet. The Dehumidifier draws less than 2A and can be
plugged into a shared branch circuit. If installed in a wet area (or
basement prone to flooding), a ground fault interrupter protected
circuit is required (See FIGURE 3 for schematic).
4033178
LINE
NEUTRAL
DEHU.
RELAY
BLOWER
RELAY
BLOWER
XFMR
DEHU.
RELAY
COIL
BLOWER
RELAY
COIL
DEFROST
T-STAT
L. PRESS
SWITCH
RUN
CAP.
NC
NO
YEL-6
BLU-7
GRN-5
PNK
-3
WHT
-4
RED-1
YEL-2
BLK-9
BLK-8
BLK
BLK
BLK-3
WHT
-5
BLK-2
BL
U-2
115V
24V
COM
COM
BRN-3
BLK-1
BLK
-1
+24VAC
DEHU
FAN
COM
CUSTOMER
CONTROL
WIRING
BLU
YEL
GRN
RED
BLK
BLK
24VAC TO
COND.
GRN-4
NO
BLK-5
VIO-6
MIN
5.88 IN
MIN
7.88 IN
MIN
23.63 IN
MIN
9.88 IN
10.06
5.62
19.69
5.62
GRAPHIC SHOWS MINIMUM DISTANCE REQUIRED FOR
CONDENSING UNIT AND THE FOOTING DIMENSIONS
FIGURE 2: MINIMUM DISTANCE REQUIRED FOR CONDENSING
UNIT AND THE FOOTING DIMENSIONS
FIGURE 3: DEHUMIDIFIER WIRING DIAGRAM