REFRIGERATED AIR DRYER INSTRUCTION MANUAL

Ultra Air Refrigerated Dryers

201 Series Instruction Manual

Air cooled models

Cooling air flows from the front to the back of the dryer. Air must be drawn from a clean source in order to
reduce dust and dirt accumulation on the condenser coils. Air temperature should not exceed 110ºF
(43ºC).

Fan motor rotation check (this check applies only to air cooled models)

Locate the rotation decals. These may be on each motor or on the condenser. Observe the refrigerant
compressor cooling fans. Rotation should be in accordance with the fan rotation shown on the decals.
Cooling air should exhaust through the condenser coils away from the fan motors.

WARNING

Disconnect electrical services from the unit whenever it is necessary to make

adjustments on timers or when servicing drain valves.

Initial Startup Procedures

The following procedure must be followed. Failure to do so could damage your dryer and invalidate the
warranty. Before starting...

1. Be sure dryer ‘on/off’ switch is in the ‘off’ position

and disconnect all power to dryer.

2. If refrigerant gauges read below 40 PSIG (2.75 

bar), do not start the dryer. Contact your 
Ultra Air distributor or the factory 

directly.

3. Make sure the air inlet and outlet piping is piped 

correctly and piping is supported correctly. Do 
not use the dryer in and out connections as sup-
ports.

4. Make sure condensate lines are run properly 

and to the correct locations.

5. Set drain ‘on’ and ‘off’ times. During periods of 

high humidity it is recommended that ‘off’ time is 
decreased and ‘on’ time is increased. During 
periods of low humidity, increase ‘off’ time and 
decrease ‘on’ time.

6. Check that there is adequate ventilation on all 

air cooled units.

7. For water cooled units, make sure cooling water 

is being supplied to the unit.

8. Confirm proper inlet air pressure, temperature, 

and flow to the dryer.

9. Connect power to dryer. This will energize 

crankcase heater(s). Allow the unit to stand for 
24 hours before continuing (3 phase only).

10. Check lights. The ‘power on’ lights should be lit.
11. Pressurize the unit by opening an air inlet valve 

with the bypass valve open and the air outlet 
valve closed (3 valve bypass is option offered 
by Ultra-Air).

12. Press the rocker switch to “on” position. The 

‘dryer on’ light will illuminate and the 
compressor will start. Shortly after startup, the 
suction press gauge will read 56-62 PSIG on 
R22 units or 28-32 PSIG for R134a units.

13. Open the optional air outlet valve to pass 

through dryer and close the bypass valve.

Shutdown Procedures

1. Press the rocker button to the ‘off’ position.
2. 10-15 minutes after the unit shuts down, cooling water can be shut down (water cooled units only).
3. Turn off main disconnect if necessary.

Содержание UA201-10A

Страница 1: ...201 Series Refrigerated Air Dryer Models UA201 10 through UA201 2000 Installation Operating Maintenance Manual A Division of Numatics ...

Страница 2: ...4A or R22 Service personnel must be certified to handle R134A and R22 and comply to all local state and federal regulations concerning refrigerant when per forming maintenance or service on this dryer Never operate this dryer above the maximum rated operat ing conditions Operating above specified conditions will result in inferior performance and could damage the unit and or cause personal injury ...

Страница 3: ...cts refrigerated dryer from oil coating on interior walls as oil acts as an insulator and reduces the efficiency of the dryer 4 UA201 Series refrigerated air dryer Lowers compressed air dewpoint 5 Heavy duty coalescer 1 0 micron Drain Connections All separators on the UA201 models and prefilters on models UA201 125 and up are equipped with a timer actuated solenoid valve drain system Prefilters on...

Страница 4: ... Refrigerated Dryers 201 Series Instruction Manual 3 Electrical Schematic Models UA201 10 through UA201 20 115V 1PH 60Hz Models UA201 25 through UA201 100 115V 1PH 60Hz REFRIGERATED AIR DRYER INSTRUCTION MANUAL ...

Страница 5: ...ir Refrigerated Dryers 201 Series Instruction Manual 4 Electrical Schematic continued Models UA201 125 UA201 150 115V 1PH 60Hz Models UA201 125 UA201 150 230V 1PH 60Hz REFRIGERATED AIR DRYER INSTRUCTION MANUAL ...

Страница 6: ...Ultra Air Refrigerated Dryers 201 Series Instruction Manual 5 Electrical Schematic continued Model UA201 200 230V 1PH 60Hz REFRIGERATED AIR DRYER INSTRUCTION MANUAL ...

Страница 7: ...Ultra Air Refrigerated Dryers 201 Series Instruction Manual 6 Electrical Schematic continued Models UA201 250 through UA201 2000 230V through 575V 3PH 60Hz REFRIGERATED AIR DRYER INSTRUCTION MANUAL ...

Страница 8: ...diagram 1 Compressor 2 Roto lock valve 2 3 Air cooled condensor 4 Liquid line filter 5 Thermo expansion valve 6 Heat exchanger 7 Suction line roto lock valve 8 Coalescing filter 9 Separator 10 Electronic drain valve 11 Suction line pressure gauge 12 Hot gas bypass valve 13 Receiver 14 Discharge pressure gauge 15 Liquid sight glass UA201 400 through UA201 2000 Air and refrigerant flow diagram 1 Com...

Страница 9: ...alve feeds a small amount of high temperature gas from the high side directly into the air refrigerant heat exchanger to enable easier control of the dryer at light or no load conditions As the load increases the evaporator temperature and pressure begin to rise The increase of temperature causes the expansion to open and let more refrigerant into the evaporator As this occurs the increased pressu...

Страница 10: ... at regular intervals Table 2 Model H P Water Water reg GPM connect City 75ºF Tower 85ºF 200 1 3 8 FPT 3 2 6 3 250 1 1 2 3 8 FPT 2 5 300 1 1 2 3 8 FPT 2 5 400 2 3 8 FPT 3 5 8 500 2 1 2 1 2 FPT 4 10 625 3 1 2 FPT 5 5 14 800 4 3 4 FPT 5 5 14 1000 5 3 4 FPT 8 5 22 1200 6 3 4 FPT 8 5 22 1600 9 1 FPT 14 35 1750 9 1 FPT 14 35 2000 9 1 FPT 14 35 REFRIGERATED AIR DRYER INSTRUCTION MANUAL Controls A High l...

Страница 11: ...iped correctly and piping is supported correctly Do not use the dryer in and out connections as sup ports 4 Make sure condensate lines are run properly and to the correct locations 5 Set drain on and off times During periods of high humidity it is recommended that off time is decreased and on time is increased During periods of low humidity increase off time and decrease on time 6 Check that there...

Страница 12: ...cessary to use a combination of acid and scale disolver For optimal performance it is important that the water cooled condenser be cleaned regularly ideally every 2000 hours of operation Auto Drain Information All UA 201 Series dryers 125 2000 models are equipped with two electronic auto drain valves One is connected to the prefilter the other is connected to the separator The open and close time ...

Страница 13: ...uld restart automatically 4 condenser 4 Improve and ensure proper water flow and temp 5 Low voltage 5 Contact electrician for repair Compressor will not start 1 Compressor windings opened or shortened 1 Contact certified refrigeration mechanic for repair 2 Compressor burned out 2 Replace compressor 3 Internal mechanical failure 3 Contact certified refrigeration mechanic for repair High evaporator ...

Страница 14: ...oard Warranty All UA201 Series standard refrigerated air dryers model UA201 10 through UA201 2000 manufactured by Ultra Air Products Inc are warranted to be free from defective materials and workmanship for a period of two years from date of shipment from Ultra Air s factory Said warranty covers all parts and labor this excludes routine preventative maintenance and adjustments In addi tion to the ...

Страница 15: ...or becomes defective open or shorted or a temperature is out of range the corresponding display for that temperature will read Err Each temperature can be calibrated individually When switch 2 located on the back of the board is turned on it puts the dryer in calibrate mode causing the temperature display to flicker The mode select switch is used to select the temperature to be calibrated using th...

Страница 16: ...DR MD50 5 30 DR MD50 5 30 DR MD50 60 5 30 DR MD50 5 30 DR MD50 60 5 30 Heat Exchanger HEX CD 117 AD HEX CD 125 AD HEX CD 125 AD HEX CD 145 AD HEX CD 226 AD HEX CD 234 AD HEX CD 234 AD HEX CD 234 AD HEX CD 234 AD REV DATE 2 26 03 UA201 125A UA201 125B UA201 150A UA201 150B UA201 200B UA201 250B UA201 250C 115 1 60 230 1 60 115 1 60 230 1 60 230 1 60 230 1 60 230 3 60 Part Description Part Number Pa...

Страница 17: ...TE 2 26 03 UA201 400D UA201 400E UA201 500B UA201 500C UA201 500D UA201 500E UA201 625B UA201 625C 460 3 60 575 3 60 230 1 60 230 3 60 460 3 60 575 3 60 230 1 60 230 3 60 Part Description Part Number Part Number Part Number Part Number Part Number Part Number Part Number Part Number Condensing Unit SUB CU 22 4 2R SUB CU 22 4 2R SUB CU 28 1 2R SUB CU 28 3 2R SUB CU 28 4 2R SUB CU 28 4 2R SUB CU 36 ...

Страница 18: ... FI F900H 20G FI F900H 20G FI F900H 24G FI F900H 24G FI F900H 24G FI F900H 24G FI F900H 24G FI F900H 24G Inlet Filter Element FRL EKF9020H FRL EKF9020H FRL EKF9024H FRL EKF9024H FRL EKF9024H FRL EKF9024H FRL EKF9024H FRL EKF9024H On Off Switch ELE SI 65 88 PI ELE SI 65 88 PI ELE SI 65 88 PI ELE SI 65 88 PI ELE SI 65 88 PI ELE SI 65 88 PI ELE SI 65 88 PI ELE SI 65 88 PI Ref Discharge Guage GAG PR 2...

Страница 19: ...18 REFRIGERATED AIR DRYER INSTRUCTION MANUAL Ultra Air Refrigerated Dryers 201 Series Instruction Manual Operator s Log ...

Страница 20: ...Ultra Air Products 3309 John Conley Drive Lapeer MI 48446 phone 810 667 6800 fax 810 667 3902 www ultra air com 2002 Ultra Air Inc All rights reserved LT201DRYMAN 1 EAM10 02 xxx AP xx xx ...

Отзывы: