Installation 

Radiator system and expansion tank     

Filling of the system shall be realized with all valves in open position and the circulation pump shall be 
turned off. The system is carefully ventilated during the filling. When the unit has been running for a 
couple of days ventilation and repeated filling should be made. 

Note! 

See special instructions for filling of water.

             

 

The volume of the expansion tank is chosen in following way:                   
Open system: 5 % of the water volume in the heating system.            
Closed system: The volume of the tank should be made from directions from manufacturer of closed 
tanks.              

 

In the table below examples of suitable expansion tanks for closed systems are shown.        
Open system with 300 litres water volume requires at least 15 litres expansion tank.                    

*

 System volume = boiler  pipe  radiator volume 

System volume (liter)* 

Opening pressure (bar)  Oppression (bar) 

Tank volume (liter) 

 

 

 

70˚C - 90˚C 

Approx. 300 

1,5 

0,5 

18 

Approx. 300 

1,5 

1,0 

35 

 

Firing with pellets and electricity at the same time  

You can fire with both pellets and electricity at the same time. At dimensioning of the expansion pipe 
or safety valve this must be considered.  
Dimensions according to BFS 1988:18, 3:416. 

Planning- and installation work 

The planning 

– and installation work of the unit shall be made in a professional way with special 

attention of common and local regulations and ordinances. .  
The operation pressure is maximum 1,5 bar. Before the unit is put into work, and always at the 
beginning of the combustion season following inspections should be made:  
1. that the heating system is filled with water and ventilated           
2. that the circulation pump is working                                
3. that the valves of the system are open                                    
4. that potential control 

– and safety automatic system is working                     

5. that the chimney has required draft and that the fresh air ventilation is open               

 

Safety valve                 

If a closed expansion tank is installed to the radiator system, the safety valve should be controlled 3-4 
times per year. Activate the valve by pressing or turning the control and then make sure that water is 
entering into the waste pipe that goes from valve to drainage.                                                

 
Maximal hot water capacity                     

If you have a higher setting of the boiler temperature, the better hot water capacity you get 
(recommended setting 

= 85˚C). 

 
Filling of water     

Before connecting of heat, the heating system has to be filled with water.    
The filling of the systems is made in following way:       
1. Open all stop taps, even the shunt valve. The pump shall be turned off.                                  
2 Filling of water to boiler and radiator. Deareation is made on the radiators.       
3 Delivery of cold water to the hot water coil. This is done by opening the stop tap on the cold water 
fittings and ventilation is made by tapping out from a hot water tap.  
4 When the system is completely filled the circulation pump can be started and heating begin.                   
5 When the water inside the boiler has reached set operating temperature, the pump should be turned 
off and another airing be made on the radiators. This should be repeated several times. Keep in mind 
that there is a lot of air inside the tap water. The volume can go up to approx. 8-10% why deaeration 
can take time 

– especially at bigger volumes. Closed systems shall be filled so that the manometer 

stands at the desired system pressure, distance from the manometer to the highest located radiator   
in meter x 0,1 which gives the system pressure in bar. Set the red pointers of the manometer at the 
same value as the big pointer. Preferred hot water temperature is set on the mixing fittings.                                             
 

 

Содержание LAMBDA

Страница 1: ...1 INSTALLATION AND MAINTENANCE OF THE ULMA LAMBDA BOILER 20KW ...

Страница 2: ... diagram 8 6 Installation 9 7 Boiler room and chimney 10 8 Management and maintenance 11 9 Data about pellet firing 12 10 Declaration of conformity 13 12 Test record 14 ULMA AB Energigatan 11 SE 512 53 Svenljunga Sweden Phone 46 0 325 17680 E mail info ulma se www ulma se ULMA AB reserves the right to changes in details and specifications without a preceding message ...

Страница 3: ...on of the burner N B The burner shall be inserted to maximum in the boiler Control this carefully in the future also if the burner is disconnected for example cleaning and service At adjustment of the burner draw limiter shall be adjusted after the draft condition of the chimney The boiler shall be connected electrically via an all pole breaker with at least 3 mm length of break The room giver sho...

Страница 4: ... for combustion of pellets but is also provided with a 6 kW immersion heater Sweeping Regular cleaning of heating surfaces is made from the top by taking off the lid placed in the center on the top of the boiler The boiler is provided with an extra large ash box in the bottom part to facilitate the maintenance The ash box is emptied as required approx 1500 Kg pellet Normally 3 4 times per year is ...

Страница 5: ...n boiler rooms that normally would be considered tight The pipe joints are located on the top of the boiler The electrical installation is easily made via already existing cables and you do not have to demount any parts for this procedure Service of the boiler is easy to make since all connections and components are easily accessible from the front ...

Страница 6: ...me 200 L My chimney area 80 cm2 Connection hole burner Ø 154mm Dept of hearth 350mm Hight of hearth 350 mm Power connection 400 VAC Warranty 5 YEARS My under pressure 1 5 vp Efficiency Approx 90 92 Max effect 20kW Hot water coil 11m Immersion heater 6kW Ash box Approx 48 liters Weight Approx 250 Kg Technical data ...

Страница 7: ...7 Building services installations schedule for ULMA LAMBDA 20kW pellet boiler ...

Страница 8: ...8 Wiring diagram ...

Страница 9: ...he valves of the system are open 4 that potential control and safety automatic system is working 5 that the chimney has required draft and that the fresh air ventilation is open Safety valve If a closed expansion tank is installed to the radiator system the safety valve should be controlled 3 4 times per year Activate the valve by pressing or turning the control and then make sure that water is en...

Страница 10: ... chimney or bricked chimney with flue lining tube will not be as easily damaged of low flue gas temperatures provided that possibly condensate is continuously drained from the lowest point of the chimney This is the responsibility of the installer to control at installation Place the boiler at least 100 mm from the wall bricks to facilitate service Also leave room for possibly existing cleanout do...

Страница 11: ... heating surfaces The tubes shown on this picture without the flue gas break that you can see on the picture to the left O B S Very important to put where flue gas in a proper manner after completion of sweeping See picture above Be extra attentive of to the quality of the pellets at new delivery or change of deliverer At new delivery a flue gas analysis should be made Therefore we recommend a ser...

Страница 12: ...uthorities The carbon dioxide taken up and captured during the growth of the trees is released in the process to once again be taken up by the nature In other words a circuitry Combustion of pellets does not provide the atmosphere extra carbon dioxide which happens at combustion of the fossil fuels oil gas and coal Comparison tables between Svanen market Norsk Pellets and Swedish standard SS 18 71...

Страница 13: ...13 ...

Страница 14: ...tion power to burner 5 Functional inspection immersion heater Grey_____Ω Brown_____Ω Black_____Ω 5 Serial no 6 Control of content in packaging Fiberglass cord Sweeping brush Manual Clutch kit mixing valve relief valve Checked and approved by ______________________________ Name ______________________________ 8 Control of accessories supplied Smoke pipe Draft limiter Checked and approved by ________...

Отзывы: