DIGITAL DIFFERENTIAL PRESSURE SWITCH & TRANSMITTER

Copyright 

ⓒ 

2003.08  ULFA  TECHNOLOGY  CO.,LTD                                                    http://www.ulfatech.com

3

   

Installation

Wiring

LOCATION

 : Select your site location , Clean and 

dry, no shock and vibration, proper to the ambient 
temperature and humidity in use.

MOUNTING

     

The SIT/SDS Series Digital Pressure Transmitter is 
designed for direct mounting on pipe or other
locations.
You need prepare PT 1/4"(3/8",1/2") female nut 
on pipe or mounting locations.

CAUTION 1

You have to grab sensor housing by use 
spanner to mounting and dismounting SIT/SDS 
Do not hold SIT/SDS body and rotation for 
mount and release.

CAUTION 2

Do not supply shock pressure to pressure port

POWER CONNECTION 

The following procedures are to be used to install  a 
standard 24VDC main power source.

1. Before connection, the user must first confirm that 
  the power specification is DC24V or AC220V. 

2. Verify that the facility's main power source is 
  turned off or disconnected.

3. Connect lead cable to power terminal matching 
  polarity as shown in FIG.2 below. Take care that 
  wrong wiring will damage the Instrument and 
  malfunction (AC220V is not concerned to polarity)

CURRENT OUT CONNECTION(4-20mA)

(SIT only)

The SIT sends a standard 2 wire 4-20mA current 
out

1. Connect  lead cable to current out  terminal 
   matching polarity as shown in FIG.2 below.

2.  Do not run the signal cable along with any high 
   voltage or power cable or put them in the same 
  

 race way. It may cause malfunction due to 

   induction.

 

FIG.1

FIG. 2

SWITCH OUT CONNECTION

SIT/SDS has two switches output. Each switch 
operate individually and has A(normal open) and 
B(normal close) contacts.

Caution : 

Do not use heavy load drive directly over 

the switch contact rating.

Switch contact rating(resist load)

Normal Switching Capacity

 1A 30V DC
 0.5 A 125V AC

Max Switching Power

 30W , 6.25VA

Max Switching Voltage

 110V DC , 125V AC

Max Switching Current

 1A

Содержание SIT Series

Страница 1: ...R Copyright ⓒ 2003 08 ULFA TECHNOLOGY CO LTD http www ulfatech com 1 Instruction Manual Digital Differential Pressure Switch Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration 4 Digit Display 4 20mA Output 2 Level Control ...

Страница 2: ...C 50 60Hz Connections 2 screw terminal block Display 4 Digit LED Warm up Time 15 minutes SWITCH Relay Contact 2 SPDT NC COM NO Contact Rating 1A 30VDC 0 5A 125VAC Connections 6 Screw terminal block Level setting Individual level setting Switch 1 2 TRANSMITTER SIT Range Table Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Model No Range Resolution Loop Resistance 0 1100...

Страница 3: ...he power specification is DC24V or AC220V 2 Verify that the facility s main power source is turned off or disconnected 3 Connect lead cable to power terminal matching polarity as shown in FIG 2 below Take care that wrong wiring will damage the Instrument and malfunction AC220V is not concerned to polarity CURRENT OUT CONNECTION 4 20mA SIT only The SIT sends a standard 2 wire 4 20mA current out 1 C...

Страница 4: ...sent by RS232 or RS485 for option specification ID setting This mode set identification number for communication Over pressure warning SIT SDS displays warning on segment for over pressure positive and negative Upper 4 elements of 7segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of 7segment _ _ _ _ blink for warning when meas...

Страница 5: ...to measure mode Press ENTER for more than 3 seconds to save and exist in the switch level setting mode SWITCH2 OFF LEVEL Switch level setting Press MODE key to select sw2 off level set mode S2 LED is on while into the sw2 off level setting mode 2oFF displayed like left while press mode key in the sw2 off level setting mode Set your switch level use up down key Press ENTER once to save and exit to ...

Страница 6: ...sure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure Press MODE key for more than 3 seconds till sw1 LED is on and appear Int on segment display like left Release MODE key then appear current set time on segment display default set time is 0 5 sec Set your sampling time use up down key Press E...

Страница 7: ...zero span etc Press MODE key for more than 3 seconds till appear Int on segment display Press MODE key once till appear FACt on segment display Press ENTER once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on segm ent to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to SIT SDS ...

Отзывы: