To access advanced settings, in power off state, press and hold          and tap       .    Press         to move through the symbol settings.  To adjust settings 

use  

 

, tap

       

to confirm and to move to next symbol setting. 

 

Touch+ Programmable Thermostat 

         

                                            

 

Power Supply: AC220~240V, 50/60HZ 

 

Load Current: 3A(Water Heating) 

 

Accuracy: ±0.5°C                   

 

Room Temperature Range: 5°C - 60°C 

 

Remote Limit Temperature Range: 5-99°C 

 

Consumption: <0.3W              

 

Temperature Sensor: NTC 

 

Size: 86*86*17mm (H*W*D) 

 

Technical Data 

Advanced Settings 

No. 

Symbol 

Item 

Parameter Setting Function 

Factory Default Setting 

5E

n

 

Sensor Reading Option 

0: Room Sensor 
1: Remote Sensor 
2: Room & Remote Sensor 

0: Room Sensor 

05U 

Remote Temperature Setting 

5-99°C 

42°C 

dIF 

Remote Temperature Difference Limit  -  
Difference between Target Temperature and Calling For Heat 

1 -9 °C 

2 °C 

5UH 

Temperature High Limit Setting 

5-99°C 

35°C 

5UL 

Temperature Low Limit Setting 

5-99°C 

5°C 

AdJ 

Temperature Calibration 

Measure temp - Calibrate if necessary 

0.1 

F

r

Frost Protection 

00: Off 
01: On 

00: Off 

Pon 

Memory 

00: Off 
01: On 

00: Off 

FAC 

Factory Default 

00: To Restore Factory Settings 

08: Default Display Number (no meaning) 

08: Default  Display Number 

 

Notes 

ELECTRICIAN / ENGINEER INSTRUCTIONS 

Temperature  can  be  temporally  adjusted  using 

or 

.  The  hand  will  flash  to  show  the  temporary 

temperature  adjustment  but  will  disappear  and  return  back  to  auto  when  your  next  scheduled 
temperature setting starts.  

 Setting temperature to 00.0°C will shut down the scheduled setting 
 The thermostat offers a choice of room sensor, remote sensor or alternatively both together 
 When set to room sensor the display shows ROOM TEMP when set to remote sensor temperature the 

display shows OUT TEMP 

 When using dual sensors, to check floor temperature setting – in power on state, press and hold         

then tap         once 

 Display will show

 Er

 if the remote sensor has been set but it is not actually connected or if it is 

damaged 

 

 

   

POWER WIRING DIAGRAM 

 

 

 

 

 

 

 

 

 

To open, push a flat screwdriver 
in to both slots in the bottom of 
the thermostat 

Push the back from the front 

as shown, remove connecting 

plug 

Connect up wiring as 
indicated putting actuator 
live on terminal

 2 

 

Screw thermostat back 

plate to 35mm wall box 

with screws provided 

Re connect plug and 

snap thermostat on   

to lugs 

INSTALLATION 

 

INSTALLATION DIMENSIONS 

 

  

 

   