background image

IMTX200H-03

www.ueonline.com

Re-Ranging

:  Using the HART interface, the range of the TX200H can be 

modified.  This is useful in situations where the exact range transmitter is not 
available.  Re-Ranging is accomplished by changing the lower range value 
and the upper range value to achieve the desired range.  There are limita-
tions on the range adjustment.  The lower/upper range limits must be within 
the upper and lower sensor range (as marked on the transmitter body and 
within the certificate of calibration) and the span must be greater that the 
process variable (PV) minimum span programmed in the device.  The PV min. 
span is 10% of the range of the device for models with a pressure range of 

≥ 100 psi and 20% of the range of the device for models with a pressure 

range < 100 psi.

For example, a 1000 psi transmitter can be re-ranged to be a 100 
psi transmitter.

Multi-Drop Mode

:  Using HART communication it is possible to connect 

up to 15 field devices to a HART master over a single pair of wires.  In this 
topology (see Figure 5) the field device is placed in a fixed current mode and 
all communication occurs over the HART interface.  Each device is assigned a 
unique poll address (1-15).  This serves as a unique address so that the 
master can access the field devices individually.  

NoTE

: The TX200H ships 

from UE with the poll address set to O.  A poll address of 0 indicates the 
device is not in multi-drop mode.

Zone Hazardous Locations Flameproof 

Gap and Joint Details

Electrical conduit fitting threaded connection: M20 x 1.5, 7 threads minimum 
engagement.

Part II - Set-up

Tools Needed

HART Communicator or other Master

Using a HART handheld communicator, or other HART master, 
you can access the many features of the TX200H.

Read Device Information

:  you can read information such as the model 

number and revision, the device I.D. and the range of the sensor.

Device Setup

:  can be used to setup or commission a device prior to placing 

it in service.  These features allow the user to write things like a device tag 

and a device description into the TX200H so that it can be uniquely identified 

over the HART interface.

Basic/Detailed Setup Features Include:

1.  Device Tag:  The device tag identifies where the device will be 

placed into service.  A replacement device can be programmed to 

have the same tag as the device it is replacing prior to installation.  

2.  Process Variable Units:  Allows the user to select the units of mea-

sure (e.g., “wc, “Hg, psi, mbar, bar, kg/cm2, kPa, MPa).  

3.  Process Variable Limits:  Allows the user to read the upper and 

lower sensor limits and to read and adjust the upper and lower 

range of the TX200H within the sensors limits and the allowable 

turn-down range.

4.  Device Description/Message:  The user can program a text field that 

reflects the function of the device. 

5.  Damping:  The user can adjust the level of the damping applied to 

the process variable.  This feature is used to reduce the effect of 

fluctuations in the readings.  The value entered is the time constant 
of the software filter, which adjusts the amount of damping.

Process Variables

:  can be read over the HART interface. Pressure is the 

primary variable.  Temperature is the secondary variable. 

NoTE

: Reported 

temperature is the ambient temperature at the back of the sensor and not 
the process media temperature.

• 

Primary Variable: can be read in pressure units, percent of range or in mA.

• 

Secondary Variable: Available in °F

Diagnostic and Service

: there are several TX200H diagnostic and service 

features available over the HART interface.  
1.  Calibration:  There are two ways to calibrate the TX200H. 

a. If a calibrated pressure source is available, the user can apply a low 

and high pressure and set the low and high range points.

b. If no pressure source is available, the user can manually enter values 

for the upper range limit and the lower range limit.

2.  D/A Trim:  This feature allows the user to calibrate the D/A converter 

that generates the 4-20mA signal.  The output is first set to 4mA.  The 
user must measure and enter the loop current.  The output is then set 
to 20mA.  The user again must measure and enter the loop current.  
The output of the D/A is adjusted for offset and span.

3.  Loop Test:  The loop test feature forces the output current to a user 

specified value.  It can be set to 4mA, 20mA or to another value entered 
by the user.

Figure 5

Red

Black

Red

Black

Red

Black

HART

Master

TX200H

#1

TX200H

#2

TX200H

#15

...

Содержание TX200H

Страница 1: ...m prod_approval PROOF PRESSURE LIMITS STATED IN THE LITERATURE AND ON THE TRANSMITTER HOUSING MUST NEVER BE EXCEEDED EVEN BY SURGES IN THE SYSTEM OCCASIONAL OPERATION OF UNIT TX200H HART Pressure Transmitter UP TO MAXIMUM PRESSURE IS ACCEPTABLE E G START UP TESTING CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE Proof Pressure The maximum pressure to which a pressure sens...

Страница 2: ...ed on the top of the transmitter with 18 AWG 72 length lead wires An external grounding screw and clamp is provided when selecting option M460 see figure 1 The lead wires are color coded as follows Red signal Black signal Green Earth ground Bench Operation To operate the TX200H on the bench it must be connected to a power supply and a load resistor see Figure 2 The HART master e g handheld com mun...

Страница 3: ... the HART interface Basic Detailed Setup Features Include 1 Device Tag The device tag identifies where the device will be placed into service A replacement device can be programmed to have the same tag as the device it is replacing prior to installation 2 Process Variable Units Allows the user to select the units of mea sure e g wc Hg psi mbar bar kg cm2 kPa MPa 3 Process Variable Limits Allows th...

Страница 4: ...0 0 G LM6 Autoclave male 15 16 1 32 33 5 H G 1 4 male 15 16 1 03 26 2 J G 1 2 male 1 3 8 1 78 45 2 Code Range 03 0 to 15 psis 04 0 to 30 psis 05 0 to 50 psis 06 0 to 100 psis 07 0 to 250 psis 08 0 to 500 psis 09 0 to 1000 psis 17 0 to 1500 psis 18 0 to 2000 psis 10 0 to 2500 psis 19 0 to 3000 psis 11 0 to 5000 psis 20 0 to 6000 psis 12 0 to 7500 psis 13 0 to 10 000 psis 14 0 to 15 000 psis 15 0 to...

Страница 5: ...Write Message 18 Write Tag Descriptor Date 19 Write Final Assembly Number 20 Read Long Tag 21 Read Unique Identifier Associated with Long Tag 22 Write Long Tag 38 Reset Configuration Changed Flag 48 Read Additional Device Status Command Number Common Practice Commands Command Function 33 Read Device Variables 34 Write Primary Variable Damping Value 35 Write Primary Variable Range Values 36 Set Pri...

Страница 6: ...town Massachusetts INCOTERMS provided however that this warranty applies only to equipment found to be so defective within a period of 36 months from the date of manufacture by the Seller Seller shall not be obligated under this warranty for alleged defects which examination discloses are due to tampering misuse neglect improper storage and in any case where products are disassembled by anyone oth...

Отзывы: