background image

IMTX200H-03

www.ueonline.com

GENERAL

The TX200H is a registered HART 7 compliant device.  It is a highly accurate, 

rugged, SMART pressure transmitter that can communicate digitally and via 

the 4-20 mA analog signal output.  The TX200H utilizes the HART protocol 

and an internal microcontroller to allow the end-user to easily configure and 

calibrate the pressure transmitter as it provides process variable measure-

ment and device health data.

HART is an acronym for Highway Addressable Remote Transducer and it has 

become the most widely adopted standard for industrial communication.  The 

Hart protocol is based on a standardized set of commands that is maintained 

by the HART Communication Foundation (HCF) and allows any end-user to 

easily integrate devices like the TX200H into their HART enabled system.  The 

TX200H, as a registered HART device has been designed to communicate 

with other HART enabled devices such as a software package running on a 
PC with HART interface or a field portable HART communicator.

BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR 
COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE 
SENSOR AND WETTED PARTS.

MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL 
INJURY. THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND 
UNDERSTOOD BEFORE UNIT IS INSTALLED.

 

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 

1, GROUPS A, B, C AND D; CLASS II, DIVISION 1, GROUPS E, F AND G;  
CLASS III; OR NON-HAZARDOUS LOCATIONS ONLY. -40

˚

C (-40

˚

F) 

  

             TAMB. 

 +85

˚

C (+185

˚

F), ENCLOSURE TYPE 4X.

THIS EQUIPMENT IS ATEX CERTIFIED FOR EQUIPMENT CATEGORY 2. 
SUITABLE FOR APPROPRIATE USE IN GAS ZONE 1 AND DUST ZONE 
21 APPLICATIONS.  

 

  EN 60079-0:2012, EN 60079-1:2007, EN 60079-31:2009 

0539 DEMKO 08 ATEX 0810742X

 

 II 2 G Ex d IIC T5 Gb

 

 II 2 D Ex tb IIIC T90

˚

C Db

    

  IP66

 

 -40

˚

 Tamb. 

 +80

˚

C

UE declarations and third-party issued Agency certifications are available for 

download at www.ueonline.com/prod_approval.

PROOF PRESSURE* LIMITS STATED IN THE LITERATURE AND ON  
THE TRANSMITTER HOUSING MUST NEVER BE EXCEEDED, EVEN 
BY SURGES IN THE SYSTEM. OCCASIONAL OPERATION OF UNIT 

TX200H™ 

HART

®

 Pressure Transmitter

UP TO MAXIMUM PRESSURE IS ACCEPTABLE (E.G. START-UP, TESTING). 
CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER 
RANGE PRESSURE**.

*Proof Pressure
The maximum pressure to which a pressure sensor may be occasionally sub-

jected, which causes no permanent damage (e.g., start-up, testing).

**Over Range Pressure
The pressure value to which a transmitter may be continuously subjected, 

without causing a shift in calibration or damage to the sensor.

THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS. 
ANY SUBSTITUTION OF COMPONENTS MAY IMPAIR UNIT SAFETY AND 
SUITABILITY FOR CLASS I, DIVISION 1.

THE EPOXY RESIN SHALL NOT BE SUBJECTED TO A TEMPERATURE 
GREATER THAN 125

˚

C.

Please refer to product bulletin for product specifications.  Product bulletin 

may be found at www.ueonline.com

Date code format on nameplate is “YYWW” for year and week.

Part I - Installation

 

Tools Needed

Adjustable Wrench

MouNTING 

ALWAYS LOCATE UNITS WHERE SHOCK, VIBRATION AND AMBIENT 
TEMPERATURE FLUCTUATIONS ARE MINIMAL. DO NOT MOUNT IN 
AMBIENT TEMPERATURE AREAS EXCEEDING 185

˚

F / 85

˚

C (IF UL/

cUL APPROVAL IS APPLICABLE) OR 176

˚

F / 80

˚

C  (IF ATEX APPROVAL IS 

APPLICABLE). 

IF SEVERE PRESSURE SURGES ARE EXPECTED, CONSIDER THE USE 
OF A PRESSURE SNUBBER. 

UNIT MAY BE MOUNTED IN ANY POSITION. ALWAYS HOLD A WRENCH 
ON THE SENSOR FLATS (PRESSURE PORT) WHEN MOUNTING UNIT.

Panel Mounting via 1/2” NPTM or M20 Electrical Connection

When panel mounting, mount through 7/8” clearance hole in panel. Hold in 
place with serrated 1/2” or M20 conduit nut. Always support the unit by hold-
ing a wrench on the hex fitting and not the housing body.

Installation and Maintenance 

Instructions

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

IMTX200H-03

HART® is a registered trademark of the 

Hart Communication Foundation

Содержание TX200H

Страница 1: ...m prod_approval PROOF PRESSURE LIMITS STATED IN THE LITERATURE AND ON THE TRANSMITTER HOUSING MUST NEVER BE EXCEEDED EVEN BY SURGES IN THE SYSTEM OCCASIONAL OPERATION OF UNIT TX200H HART Pressure Transmitter UP TO MAXIMUM PRESSURE IS ACCEPTABLE E G START UP TESTING CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE Proof Pressure The maximum pressure to which a pressure sens...

Страница 2: ...ed on the top of the transmitter with 18 AWG 72 length lead wires An external grounding screw and clamp is provided when selecting option M460 see figure 1 The lead wires are color coded as follows Red signal Black signal Green Earth ground Bench Operation To operate the TX200H on the bench it must be connected to a power supply and a load resistor see Figure 2 The HART master e g handheld com mun...

Страница 3: ... the HART interface Basic Detailed Setup Features Include 1 Device Tag The device tag identifies where the device will be placed into service A replacement device can be programmed to have the same tag as the device it is replacing prior to installation 2 Process Variable Units Allows the user to select the units of mea sure e g wc Hg psi mbar bar kg cm2 kPa MPa 3 Process Variable Limits Allows th...

Страница 4: ...0 0 G LM6 Autoclave male 15 16 1 32 33 5 H G 1 4 male 15 16 1 03 26 2 J G 1 2 male 1 3 8 1 78 45 2 Code Range 03 0 to 15 psis 04 0 to 30 psis 05 0 to 50 psis 06 0 to 100 psis 07 0 to 250 psis 08 0 to 500 psis 09 0 to 1000 psis 17 0 to 1500 psis 18 0 to 2000 psis 10 0 to 2500 psis 19 0 to 3000 psis 11 0 to 5000 psis 20 0 to 6000 psis 12 0 to 7500 psis 13 0 to 10 000 psis 14 0 to 15 000 psis 15 0 to...

Страница 5: ...Write Message 18 Write Tag Descriptor Date 19 Write Final Assembly Number 20 Read Long Tag 21 Read Unique Identifier Associated with Long Tag 22 Write Long Tag 38 Reset Configuration Changed Flag 48 Read Additional Device Status Command Number Common Practice Commands Command Function 33 Read Device Variables 34 Write Primary Variable Damping Value 35 Write Primary Variable Range Values 36 Set Pri...

Страница 6: ...town Massachusetts INCOTERMS provided however that this warranty applies only to equipment found to be so defective within a period of 36 months from the date of manufacture by the Seller Seller shall not be obligated under this warranty for alleged defects which examination discloses are due to tampering misuse neglect improper storage and in any case where products are disassembled by anyone oth...

Отзывы: