Adjusting Thermometer Type T800

Use the in-process adjustment to check the control.  Differences between the 
test instrument and the thermometer can be corrected by turning the zero 
adjustment “C” per Figure 3 on the thermal assembly.  Turning in lowers 
indicated reading.

Note:  Indicating Pointer Deflection: 

The indicating pointers will read slightly low when the bulb temperature is 
15° above the controller setting.  This deflection is normal and repeatable 
(approximately 0.5% of scale range on single switch models) and is due to 
the transference of the switching mechanism load to the thermal system.  It 
can be measured by moving the setting pointer from the high to the low end 
of the scale and observing the resultant indicating pointer deflection.

Correction of Capillary

If the length of capillary immersed in the process differs from the amount 
immersed at the factory calibration bath, a calibration shift will occur.  The 
error may be corrected as follows:

Move set pointer to the highest temperature setting. Note indicating scale 
reading with the head and sensor at room temperature. Loosen the two 
thermal assembly mounting screws.  Re-position the housing index against 
the calibration on the instrument case (or skeleton casting) at a rate of 1 
division line per capillary length listed in the following column.  Move to the 
left if capillary is to be added to the process, or to the right if capillary is to 
be removed from process.

Model Number

Range

Cap Length/Division*

1

-180 to 120°F

2 ft

2

-125 to 350°F

1 1/2 ft

3

-125 to 500°F

1 ft

4

-40 to 120°F

4 ft

5

-40 to 180°F

3 ft

6

0 to 250°F 

2 1/2 ft

7

0 to 400°F

2 ft

8

50 to 650°F

2 ft

* Added to or taken away from the process.

Tighten the two thermal assembly mounting screws.  Note change indicated 
scale reading (if any).
Turn zero adjustment “C” to bring indicating pointer reading back to the origi-
nal reading noted before.  Turning in lowers indicated reading.

Note:

  The thermal assembly can be returned to its original position by align-

ing its flange with

 

the line scribed on the instrument case.

COMPENSATOR

SWITCH 1

SWITCH 2

Figure 3

Figure 4

 

Dimension A

Model 

Inches   mm

1BS  3-3/4 95.3
2BS  2-5/8 66.7
3BS  2-1/8 54.0
4BS  6-3/4 171.5
5BS 5  127.0
6BS  4-1/2 114.3
7BS 3  76.2
8BS  3-1/4 82.6

SET POINT

ADJUSTMENT

POINTER

(RED)

Dimensions

General Layout

Содержание 800 Series

Страница 1: ... When mounting 800 or 802 type controls it may be necessary to remove adjustment knob and front cover The knob is secured with a 5 64 Allen Setscrew The cover is secured by four phillips screws at the corners Mounting The controller may be mounted in any position to either a surface or panel 1 4 thick maximum Locate it where vibration shock and ambient tempera ture fluctuations are minimal It is r...

Страница 2: ...hten adjustment A Note Switch 1 green pointer cannot be set to operate at a higher setting than switch 2 red pointer Connect test lights to indicate switch operation or listen for the individual switch clicks The separation between switches is the difference between the high and low set points The set points are determined by setting individual adjustment pointers and may be separated up to 100 of...

Страница 3: ...eading with the head and sensor at room temperature Loosen the two thermal assembly mounting screws Re position the housing index against the calibration on the instrument case or skeleton casting at a rate of 1 division line per capillary length listed in the following column Move to the left if capillary is to be added to the process or to the right if capillary is to be removed from process Mod...

Страница 4: ...ot be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery free from defects in material and workmanship and that any such produ...

Отзывы: