background image

IM800-06

www.ueonline.com

800 Series

Indicating Temperature Controls

Types 800, T800, 802

Please refer to IMT120 for Explosion Proof Types

820E and 822E

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

IM800-06

GENERAL 

Temperature variations are sensed by a liquid filled sensing bulb which 
hydraulically transmits motion through a mechanism which rotates the indi-
cating pointer and actuates precision snap-acting switch(es).  Control set 
point(s) are varied by turning the external adjustment knob(s), according to 
procedures outlined (See Part II - Adjustments).  Thermometer type T800 
provides temperature indication only with no snap-acting switch.

MAXIMUM TEMPERATURE* STATED IN LITERATURE AND ON 
NAMEPLATE MUST NEVER BE EXCEEDED, EVEN BY SURGES IN 
THE SYSTEM.  OCCASIONAL OPERATION OF UNIT UP TO MAX.  

TEMPERATURE IS ACCEPTABLE (E.G., START-UP, TESTING).  CONTINUOUS 
OPERATION SHOULD BE RESTRICTED TO THE DESIGNATED ADJUSTABLE 
RANGE.

Maximum Temperature - the highest temperature to which a sensing element 
may be occasionally operated at, without adversely affecting set point calibra-
tion and repeatability.

Please refer to product bulletins for product specifications.  Product bulletins 
may be found at www.ueonline.com.

Part I -Installation

Tools Needed 

Phillips screwdriver to secure  

customer supplied screws 

5/64” Allen Wrench

INSTALL UNIT WHERE SHOCk, VIBRATION AND TEMPERATURE FLUC-
TUATIONS ARE MINIMAL. DO NOT MOUNT UNIT IN AMBIENT TEMPERA-
TURES EXCEEDING PUBLISHED LIMITS. ORIENT UNIT SO THAT MOIS-

TURE IS PREVENTED FROM ENTERING THE ENCLOSURE. 

PREVENTATIVE MAINTENANCE / PERIODIC TESTING (6 MONTHS OR SOONER 
AS DICTATED BY THE ENVIRONMENT) IS NECESSARY TO ENSURE OPERATION 
OF THE PRODUCT TO SPECIFICATION. LUBRICATE ALL PIVOT POINTS AND 

MOVING PARTS, TO PREVENT CORROSION, WITH COMPATIBLE DRY LUBRICANTS OR LIGHT 
GREASE.

When mounting 800 or 802 type controls, it may be necessary to remove 
adjustment knob and front cover.  The knob is secured with a 5/64” Allen 
Setscrew. The cover is secured by four phillips screws at the corners.

MouNTING

The controller may be mounted in any position to either a surface or panel 

(1/4” thick maximum).  Locate it where vibration, shock and ambient tempera-
ture fluctuations are minimal.  It is recommended that mounting the unit with 
the conduit connection on the top be avoided.

To Flush Mount

  

Cut out the panel as shown in Figure 1A.  Mount to the panel using the two 
holes located on the flange of the enclosure.

To Surface Mount

Attach 2 mounting ears found in separate package to recessed areas on 
back side of enclosure by means of 2 self-tapping screws.  Mount to surface 
per Figure 1B. 

Mounting Bulb and Capillary

Fully immerse the bulb and 6” of capillary in the control zone.  For best con-
trol it is generally desirable to place the bulb close to the heating or cooling 
source in order to sense temperature fluctuations quickly.  Be sure to locate 
the bulb so it will not be exposed to temperature beyond the instruments 
range limits.

Try to place any remaining capillary adjacent to the control head so it will 
sense the same ambient temperatures (control is ambient temperature com-
pensated).

Unless otherwise specified, factory calibration, allows  for 6” of capillary tube 
in the control zone.  If longer lengths are required recalibration may be nec-
essary.  Follow the procedure outlined in PART II - Adjustments. 

Avoid bending or coiling the capillary tube tighter than 1/2” radius.

Exercise caution when making bends near the capillary ends. 

If a separable well or union connector is used follow separate instructions 

included with them.

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

CLEARANCE FOR #8 
SCREW  - (2) PLACES 

Figure 1A - 

Flush Mounting

Clearance for #10 

screw - (2) places

Figure 1B - 

Surface Mounting

Содержание 800 Series

Страница 1: ... When mounting 800 or 802 type controls it may be necessary to remove adjustment knob and front cover The knob is secured with a 5 64 Allen Setscrew The cover is secured by four phillips screws at the corners Mounting The controller may be mounted in any position to either a surface or panel 1 4 thick maximum Locate it where vibration shock and ambient tempera ture fluctuations are minimal It is r...

Страница 2: ...hten adjustment A Note Switch 1 green pointer cannot be set to operate at a higher setting than switch 2 red pointer Connect test lights to indicate switch operation or listen for the individual switch clicks The separation between switches is the difference between the high and low set points The set points are determined by setting individual adjustment pointers and may be separated up to 100 of...

Страница 3: ...eading with the head and sensor at room temperature Loosen the two thermal assembly mounting screws Re position the housing index against the calibration on the instrument case or skeleton casting at a rate of 1 division line per capillary length listed in the following column Move to the left if capillary is to be added to the process or to the right if capillary is to be removed from process Mod...

Страница 4: ...ot be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery free from defects in material and workmanship and that any such produ...

Отзывы: