option M421, M423 & M513 Junction Boxes 

option M430 Adjustment Cover Lock

Surface Mounting Bracket (Kit P/N 62169-13)

U N I T E D   E L E C T R I C   
C O N T R O L S

180 dexter avenue, P.o. box 9143
watertown, Ma  02471-9143   usa
telephone: 617 926-1000    fax: 617 926-2568
http://www.ueonline.com

RECoMMENDED PRACTICES AND WARNINgS

united electric controls company recommends careful consideration of the following 
factors when specifying and installing ue pressure and temperature units. before 
installing a unit, the Installation and Maintenance instructions provided with unit must be 
read and understood. 

• To avoid damaging unit, proof pressure and maximum temperature limits stated 

in literature and on nameplates must never be exceeded, even by surges in the 
system. operation of the unit up to maximum temperature is acceptable on a limited 
basis (i.e., start-up, testing) but continuous operation must be restricted to the 
designated adjustable range. excessive cycling at maximum temperature limits could 
reduce sensor life.

•  A  back-up  unit  is  necessary  for  applications  where  damage  to  a  primary  unit 

could endanger life, limb or property. a high or low limit switch is necessary for 
applications where a dangerous runaway condition could result.

• The adjustable range must be selected so that incorrect, inadvertent or malicious 

setting at any range point cannot result in an unsafe system condition. 

•  Install unit where shock, vibration and ambient temperature fluctuations will not 

damage unit or affect operation. orient unit so that moisture does not enter the 
enclosure via the electrical connection. when appropriate, this entry point should 
be sealed to prevent moisture entry.

• Unit must not be altered or modified after shipment. Consult UE if modification is 

necessary.  

• Monitor operation to observe warning signs of possible damage to unit, such as 

drift in set point or a faulty display.  check unit immediately.

• Preventative maintenance and periodic testing is necessary for critical applications 

where damage could endanger property or personnel.

• For all applications, a factory set unit should be tested before use.
•  Electrical  ratings  stated  in  literature  and  on  nameplate  must  not  be  exceeded. 

overload on a switch can cause damage, even on the first cycle.  wire unit 
according to local and national electrical codes, using wire size recommended in 
installation sheet.

 • Do not mount unit in ambient temp. exceeding published limits.

LIMITED WARRANTY

seller warrants that the product hereby purchased is, upon delivery, free from 
defects in material and workmanship and that any such product which is found to 
be defective in such workmanship or material will be repaired or replaced by seller 
(ex-works, factory, watertown, Massachusetts. IncoterMs); provided, however, that 
this warranty applies only to equipment found to be so defective within a period of 36 
months from the date of manufacture by the seller. seller shall not be obligated under 
this warranty for alleged defects which examination discloses are due to tampering, 
misuse, neglect, improper storage, and in any case where products are disassembled 
by anyone other than authorized seller’s representatives. excePt for the lIMIted 
warranty of rePaIr and rePlaceMent stated above, seller dIsclaIMs all 
warrantIes whatsoever wIth resPect to the Product, IncludIng all IMPlIed 
warrantIes of MerchantabIlIty or fItness for any PartIcular PurPose.

LIMITATIoN oF SELLER’S LIABILITY

seller’s liability to buyer for any loss or claim, including liability incurred in connection 
with (i) breach of any warranty whatsoever, expressed or implied, (ii) a breach of 
contract, (iii) a negligent act or acts (or negligent failure to act) committed by seller, 
or (iv) an act for which strict liability will be inputted to seller, is limited to the “limited 
warranty” of repair and/or replacement as so stated in our warranty of product.  In 
no event shall the seller be liable for any special, indirect, consequential or other 
damages of a like general nature, including, without limitation, loss of profits or 
production, or loss or expenses of any nature incurred by the buyer or any third party.

ue specifications subject to change without notice.

cP04135000

M421 - EAC only

M423 - ATEX only

(Not cuLus approved)

Cover not shown

M513 - cuLus only; does not 

meet Enclosure Type 4X

Cover not shown

1/32" 

MIN. SPACE

Option M430: 
Cover Lock

Adjustment
Cover

Note

: a 1/32” min. space must 

be maintained between the 
bottom of the cover lock and 
the top of the adjustment cover 
to ensure proper dual seal an-
nunciation and venting.

Figure 5

Mounting Bracket

Adjustment
Cover

Figure 6

Shown with optional Cover 

Lock (M430)

3/4-NPT (Male) Con-
duit Plug, 1/2” 
Square Socket

3/4-14 NPT 
(Female) Port, 
2 PLCS

Internal Ground 

Screw

5 9/6” [141mm]

Ø21/64
[8.33 mm]

6 5/16”
[160mm]

3 3/32”
[79mm]
Typ.

1/2” NPT (Female) 
Ports, 2 PLCS

External 

Ground 

Screw

Internal Ground Screw

No Access 

Sealed Port

1/2” NPT (Male) 

Conduit Plug 10mm 

HEX Drive

4” [102mm]

4” 

[102mm]

Содержание 12 Series

Страница 1: ...t is installed This product is suitable for use in Class I Divisions 1 2 Groups a B C and D Class II Divisions 1 2 Groups E f and G class III or non hazardous locations only 50 C 58 F Tamb 80 C 176 F Enclosure Type 4X This product is ATEX and iecex certified for equipment category 2 Suitable for appropriate use in gas zone 1 and dust zone 21 applications EN 60079 0 2012 EN 60079 1 2007 EN 60079 31...

Страница 2: ...ot be exceeded overload on a switch can cause failure on the first cycle DIN connector option M515 figure 4 is not approved for Class I Div 1 Hazardous Locations Flameproof atmospheres for atex installation an External grounding screw option M460 is required for non metallic conduit systems SEE figure 2 for atex installation in hazardous locations tHE WIRING TO THE PRESSUrE SWITCH MUST ONLY BE CON...

Страница 3: ... 1 16 27 0 M526 HM4 autoclave 1 4 male 1 3 32 8 1 1 16 27 0 M527 HF6 Autoclave 3 8 female 1 4 36 1 1 1 16 27 0 M528 HM6 Autoclave 3 8 male 1 5 37 6 1 1 16 27 0 XP112 1 2 NPT female 0 6 15 2 1 1 16 27 0 XP113 1 2 NPT female 0 6 15 2 1 1 16 27 0 XP114 1 4 NPT female 0 6 15 2 1 1 16 27 0 XP115 1 4 NPT female 0 6 15 2 1 1 16 27 0 Type 2 3 5 Type 4 6 8 P0 P9 Type 7 9 Type K4 K6 Type K1 K3 Types K1 K3 a...

Страница 4: ...allation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery free from defects in material and workmanship and that any such product which is found to be defective in such workmanship or material will be repaired or replaced by Seller Ex works Factory Watertown Massachusetts INCOTERMS provided howeve...

Отзывы: