the ePoxy resIn shall not be subjected to a teMPerature 

greater than 125°c.

thIs Product does not have any fIeld rePlaceable Parts. any 
substItutIon of coMPonents wIll InvalIdate thIrd-Party Issued 
aPProvals and certIfIcatIons, and May IMPaIr suItabIlIty for 
class I, dIvIsIon 1 locatIon.

the 12 series switch utilizes a diaphragm or a piston sensor to detect a pressure 

change.  the response, at a predetermined set point, actuates a sPdt or dPdt  

snap-acting switch, converting a pressure signal into an electrical signal. control set 

point may be varied by turning the internal slotted adjustment screw according to 

procedures outlined in Part II-adjustments. 

Please refer to product bulletin for product specifications.  Product bulletin may be 

found at www.ueonline.com.

date code format on nameplate is “yyww” for year and week.

Part I - Installation

Tools Needed

1-1/6" open end wrench

MouNTINg

always locate the Product where shock, vIbratIon and aMbIent teM-

Perature fluctuatIons are MInIMal. do not Mount In aMbIent teMPera-

ture areas exceedIng 176°f (80 °c).

If severe Pressure surges are exPected, consIder the use of a 

Pressure snubber.

for Pressure Models, Mount usIng Pressure connectIon:  always use a 
wrench on Pressure connectIon wrench flat. (see fIgure 1)

12 Series

Explosion-Proof, Pressure, 

Vacuum, and Differential 

Pressure Switches 

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

IMP12-14

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

gENERAL

MIsuse of thIs Product May cause exPlosIon and Personal Injury.  
these InstructIons Must be thoroughly read and understood 
before Product Is Installed.

thIs Product Is suItable for use In class I, dIvIsIons 1 & 2, grouPs 
a, b, c and d; class II, dIvIsIons 1 & 2, grouPs e, f and g; class III; or 
non-hazardous locatIons only. -

50 °C (-58 °F) ≤ Tamb. ≤ 80 °C (176 

°f), enclosure tyPe 4x.

thIs Product Is atex and Iecex certIfIed for equIPMent category 
2. suItable for aPProPrIate use In gas zone 1 and dust zone 21 
aPPlIcatIons. 

 

     

en 60079-0:2012, en 60079-

1:2007, en 60079-31:2009

Iec 60079-0:ed.6, Iec 60079-

1:ed.6, Iec 60079-31:ed.2

0539 deMko 08 atex 0717128x

II 2 g ex d IIc t6 gb

II 2 d ex tb IIIc t80°c db

IP66

-50°c < tamb. < +80°c

Iecex ul 14.0072x

ex d IIc t6 gb

ex tb IIIc t80°c db

IP66

-50°c < tamb. < +80°c

ue declarations and third-party issued agency certifications are available for 

download at www.ueonline.com.

PrIor to InstallatIon, check the wetted Parts MaterIal for 
coMPatIbIlIty to the Process MedIa.

the dual seal devIce Method of PrIMary seal faIlure annuncIatIon Is 
vIsIble leakage froM the enclosure.  dePendIng uPon MedIa sensed, 
addItIonal Methods of leak detectIon May be requIred.

Proof Pressure* lIMIts stated wIthIn the lIterature and PrInted 
onto the Product housIng Must never be exceeded, even by 
surges In the systeM.  occasIonal oPeratIon of the Product uP to 
Proof  Pressure Is accePtable (e.g., start-uP, testIng).  contInuous 
oPeratIon should not exceed the desIgnated over range Pressure** 
or workIng Pressure range***.

*Proof Pressure - the maximum pressure to which a pressure sensor may be occasionally 

subjected, which causes no permanent damage (e.g., start-up testing).  the product may 

require set-point adjustment after reaching proof pressure.
**over range Pressure - the pressure value to which a pressure sensor may be 

continuously subjected without causing damage and while maintaining set point 

repeatability.
***working Pressure range - the pressure range within which two opposing sensors can 

be safely operated while maintaining set point repeatability.

DUAL SEAL

CERTIFIED

Do NoT TuRN

switch

 

housing

MouNT VIA

pressure

  

connection

Figure 1

Содержание 12 Series

Страница 1: ...t is installed This product is suitable for use in Class I Divisions 1 2 Groups a B C and D Class II Divisions 1 2 Groups E f and G class III or non hazardous locations only 50 C 58 F Tamb 80 C 176 F Enclosure Type 4X This product is ATEX and iecex certified for equipment category 2 Suitable for appropriate use in gas zone 1 and dust zone 21 applications EN 60079 0 2012 EN 60079 1 2007 EN 60079 31...

Страница 2: ...ot be exceeded overload on a switch can cause failure on the first cycle DIN connector option M515 figure 4 is not approved for Class I Div 1 Hazardous Locations Flameproof atmospheres for atex installation an External grounding screw option M460 is required for non metallic conduit systems SEE figure 2 for atex installation in hazardous locations tHE WIRING TO THE PRESSUrE SWITCH MUST ONLY BE CON...

Страница 3: ... 1 16 27 0 M526 HM4 autoclave 1 4 male 1 3 32 8 1 1 16 27 0 M527 HF6 Autoclave 3 8 female 1 4 36 1 1 1 16 27 0 M528 HM6 Autoclave 3 8 male 1 5 37 6 1 1 16 27 0 XP112 1 2 NPT female 0 6 15 2 1 1 16 27 0 XP113 1 2 NPT female 0 6 15 2 1 1 16 27 0 XP114 1 4 NPT female 0 6 15 2 1 1 16 27 0 XP115 1 4 NPT female 0 6 15 2 1 1 16 27 0 Type 2 3 5 Type 4 6 8 P0 P9 Type 7 9 Type K4 K6 Type K1 K3 Types K1 K3 a...

Страница 4: ...allation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery free from defects in material and workmanship and that any such product which is found to be defective in such workmanship or material will be repaired or replaced by Seller Ex works Factory Watertown Massachusetts INCOTERMS provided howeve...

Отзывы: