6. INSTALLATION / WIRING / COMMISSIONING

CAUTION

Risk of Electric Shock. All servicing should be performed by qualified service personnel. To reduce 

the risks of electric shock disconnect power connections before servicing.

• 

BT-PP20-A shall be mounted to a listed light fixture or electrical junction box or panel with an opening that can fit a 

½” threaded nipple

• 

Product must be installed in accordance with local electrical codes

• 

Install device into place and fix into position using lock ring washer

• 

For installation with field installed conductors of 60°C minimum rating.

• 

The following wire connections are provided:

• 

0-10V connection (violet / grey): #20AWG

• 

Line Voltage/Relay connection (black / white / red): #14AWG

• 

Connect wires as shown on diagram.

• 

NOTE: for Emergency lighting, an Emergency Power Source (i.e. Generator / Battery Backup) that is capable 

of maintaining 120VAC / 277VAC / 347VAC (depending on the application) for a MINIMUM of 30 minutes is 

required.

• 

Use appropriate sized wire-nuts to connect field installed conductors.

• 

Download free Douglas Lighting Controls Smartphone App: BT-APP.

• 

Commission as required

Emergency Test

• 

The BT-PP20 Emergency operation can be tested using a Smartphone loaded with the free Douglas Lighting Controls 

Smartphone App: BTCC.

• 

To test Emergency operation, perform the following steps:

1.  Ensure the emergency circuit is connected to the BT-PP20 and is energized.
2.  Use the BTCC “Room Setup” function on the commissioning mobile device (eg. iPod) or use a Douglas Lighting 

Controls Bluetooth switch to turn OFF the BT-PP20 under test.

3.  Use the BTCC “System Setup” function on the commissioning mobile device to navigate to the commissioned 

devices list and select the settings cogwheel for the BT-PP20 under test.

4.  In the settings page for the BT-PP20, select the “Test Emergency Mode” button. The BT-PP20 will turn on to 

100% brightness for approximately 30 seconds and then will return to its previous OFF state.

5.  Use the “Cancel” button to exit the BT-PP20 Settings page WITHOUT saving the configuration parameters.

It is recommended to test devices configured for Emergency operation on a monthly basis.

A UDLA Company

A UDLA Company

Содержание Douglas Lighting Controls BT-PP20-A

Страница 1: ...Douglas Lighting Controls Bluetooth Controller BT PP20 A Installation Manual Patent Pending A UDLA Company A UDLA Company ...

Страница 2: ...AD AND FOLLOW ALL SAFETY INSTRUCTIONS Do not use outdoors Do not mount near gas or electric heaters Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Wireless device...

Страница 3: ...ESCRIPTION 4 2 DESIGN FEATURES 4 3 SPECIFICATIONS 5 POWER 5 LOAD RATINGS 5 OUTPUTS 5 WIRELESS RANGE 5 OPERATING ENVIRONMENT 5 APPROVALS 5 WARRANTY 5 4 DIMENSIONS 6 5 INSTALLATION FEATURES 6 6 INSTALLATION WIRING COMMISSIONING 7 A UDLA Company A UDLA Company ...

Страница 4: ...th enabled devices occupancy sensors gateways and wall station switches via the Bluetooth mesh network Commissioning is conveniently done at deck level with our free smartphone App using Bluetooth communication smartphone must have Bluetooth capability 2 DESIGN FEATURES Tinned and snipped colour coded wires Threaded knockout chase nipple with lock ring washer Bluetooth enabled for deck level confi...

Страница 5: ...tion and environment Additional devices may be required at time of commissioning to ensure Bluetooth network integrity Operating Environment Indoor stationary non vibrating non corrosive atmosphere and non condensing humidity Operating Temperature 32 F to 104 F 0 C to 40 C Approvals ETL Listed Conforms to UL STDS 508 1310 and 924 Certified to CSA STD C22 2 14 and 223 ETL Classified Conforms to UL ...

Страница 6: ...unted into a knockout in a listed light fixture or electrical junction box or panel with an opening that can fit the threaded chase nipple Tinned and snipped colour coded flying leads Threaded knockout chase nipple with lock ring washer Bluetooth enabled for deck level configuration and wireless mesh networking A UDLA Company A UDLA Company ...

Страница 7: ...e nuts to connect field installed conductors Download free Douglas Lighting Controls Smartphone App BT APP Commission as required Emergency Test The BT PP20 Emergency operation can be tested using a Smartphone loaded with the free Douglas Lighting Controls Smartphone App BTCC To test Emergency operation perform the following steps 1 Ensure the emergency circuit is connected to the BT PP20 and is e...

Страница 8: ...ent 100mA based on dimming control Single Fixture Fixture Fixture Fixture Fixture Red relay Red relay Multiple Fixture Violet Violet Gray Gray White Neutral White Neutral White Neutral Black Hot White Neutral Black Hot Wiring Wiring A UDLA Company A UDLA Company ...

Страница 9: ...d relay Supplied by Others Violet Gray White Neutral White Neutral Black Hot Black White Hot Neutral Wiring Wiring Example for Emergency Lighting Line Power Emergency Power Transfer Switch A UDLA Company A UDLA Company ...

Страница 10: ...re those of their respective owners DOUGLAS LIGHTING CONTROLS 3605 Gilmore Way Suite 280 Burnaby BC V5G 4X5 Canada CUSTOMER SERVICE 877 873 2797 ext 0 English 514 342 6581 French TECHNICAL SUPPORT 877 873 2797 ext 1 English 514 342 6581 French WEBSITE douglaslightingcontrols com EMAIL lighting douglaslightingcontrols com It s EASY to REACH US A UDLA Company A UDLA Company ...

Отзывы: