13 Setting values
13.1 Setting values standard appliance
The below setting values are for a Ubiflux Vigor W325-appliance
without
Plus pcb.
Step
No
Description
Factory settings
Setting range
Comment
1
Flow rate
1.1
Air flow rate setting 0
50 m³/h
0 or adjustable between 50 m³/h and 325
m³/h (never higher than step no. 1.2)
1.2
Air flow rate setting 1
100 m³/h
Adjustable between 50 m³/h and 325
m³/h (not higher than step no. 1.3 or
lower than step no. 1.1)
1.3
Air flow rate setting 2
150 m³/h
Adjustable between 50 m³/h and 325
m³/h (not higher than step no. 1.4 or
lower than step no. 1.2)
1.4
Air flow rate setting 3
250 m³/h
Adjustable between 50 m³/h and 325
m³/h (not lower than step no. 1.3)
1.5
Imbalance permissible
Yes
Yes / No
1.6
Imbalance (Open fireplace)
0%
0% / +20%
1.7
Offset supply
0%
-15% / +15% fan setting
Value calculated
back to set flow
rate, see screen
1.8
Offset exhaust
0%
-15% / +15% fan setting
1:19 Default fan setting
1
0 or 1
2
Bypass
2.1
Mode Bypass
Automatic
- Automatic
- Bypass closed
- Bypass open
2.2
Bypass temperature "from
dwelling"
24 °C
15 °C / 35 °C
2.3
Bypass temperature “from
outside”
10°C
7 °C / 15 °C
2.4
Bypass hysteresis
2 °C
0 °C / 5 °C
2.5
Mode Bypass boost
Off
On / Off
2.6
Fan setting selection Bypass
boost
3
0 / 3
3
Frost protection
3.1
Frost temperature
0 °C
-1,5 °C /1,5 °C
3.2
Minimum intake temperature
10 °C
7 °C /22 °C
4
Filter message
Ubiflux Vigor W325 615743-G
Ubbink / 51