![ubbink 0882250 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/ubbink/0882250/0882250_manual_832423019.webp)
1 = Basic pcb
2 = Multiple switch (option)
3 = Humidity sensor (option)
4 = USB connector
5 = USB stick for updating software
(not supplied with appliance)
6 = Service connector
7 = Laptop with installed service tool (not supplied)
8 = Touchscreen on appliance
9 = Valve motor bypass valve
10 = Air temperature sensor
11 = Exhaust fan*
12 = Internal preheater incl. maximum security
13 = Supply fan*
14 = Power supply 230V 50Hz
15 = Air Control (option)
16 = CO
2
sensor eBus (option)
17 = Heater eBus (option)
18 = Zone valve demand-driven ventilation 2.0 (option)
19 = Plus pcb (option)
20 = Connection on ModBus system (option)
21 = X12 is Jumper terminating resistance (120 W)
ModBus (remove if terminating resistance has
already been placed in ModBus system). With Mod
bus application remove the jumpers X121 & X122;
when using external Bus place the jumpers X12, X121
& X122; remove Jumper X07 from Plus pcb when a
Plus pcb is applied.
* The control cables of the fans can be switched with no problem; when
the power is switched on the appliance determines itself which is the
supply and exhaust fan! When the appliance detects another fan
(for example when a fan is replaced during service activities), then a
“wizard” starts up automatically; follow the instructions on the display
for the correct connection of the fan cables.
Basic print
X15 = externalBus/ModBus
X16 = 24V
X17 = eBus
X18 = 24V (max 5VA)
X19 = Signal Output
Plus print
X03 = 24V
X04 = externalBus
X06 = ModBus
X08 = Contact input 1
X09 = Contact input 2
X10 = Relais output 1
X11 = Relais output 2
X12 = Analog input (0 tot 10 V)
X13 = Analog input (0 tot 10 V)
X14 = Analog output (0 of 10 V)
X15 = Analog output 2 (0 of 10V)
X16 = NTC 10K
X17 = LAN
Wire colours
C1 = brown
C2 = blue
C3 = green/yellow
C5 = white
C8 = grey
C10 = yellow
C11 = green
C17 = purple
11 Electrical connections accessories
11.1 Connecting position switch
A multiple switch must be connected to the modular connector type X14. This modular connector X14 is
accessible from the rear of the control. With an appliance with Plus pcb the cover fi rst has to be removed
in order to gain access to this modular connector . Depending on the type of multiple switch that is
connected, one can use either an RJ11 or RJ12 plug.
It is best to use a 4-way switch with fi lter indication; always install an RJ12 connector in combination with
a 6-core modular cable.
When using a 3-way switch without fi lter indication always install an RJ11 connector in combination with a
4-core modular cable.
36 | Art.-nr.:
616711-A
Ubifl ux Vigor W225 | 37