U.S. Boiler Company SERIES 3 Скачать руководство пользователя страница 7

7

User Maintenance

A

.

 

General Housekeeping (Continuous).

1.  Keep boiler area clear and free of combustible 

materials and obstructions to the free flow of 

combustion and ventilation air to the boiler.

2.  Do not store or use gasoline, other flammable 

vapors, liquids or sources of hydrocarbons in the 

vicinity of the boiler or any other appliance.

3.  Do not store or use halogen-containing products 

(bleaches, cleaners, fabric softeners, refrigerants, 

chemicals, etc.) in the vicinity of the boiler. 

B.

 

Inspect Inlet Air and Vent System (Monthly).

 Check 

the following. If corrective action is required contact 

qualified service agency.
1.  Blocked vent switch must be attached to the canopy.
2.  Vent pipe must be full round shape, showing no 

damage from impact or excessive temperature.

3.  All vent pipe joints must be secure.

4.  Horizontal runs must not sag.

5.  The vent system must be free of corrosion and other 

deterioration.

6.  Supports must not be loose or broken.

C.

 

Inspect Pilot and Main Burner Flames (Monthly).

1.  Remove jacket front panel. 
2.  View flames through burner access panel.  See 

Figure 1.

3.  Adjust thermostat to highest setting.
4.  Check pilot flame. See Figure 4. The pilot produces 

three (3) flames. The center flame should be steady, 

medium hard blue enveloping 

3

/

8

 to ½ inch of 

sensing probe. If flame is yellow and lazy, follow 

instructions TO TURN OFF GAS TO APPLIANCE 

(see Figure 2), and contact qualified service agency.

5.  Check main burner flames. See Figure 5. Flame 

should have clearly defined inner cone with no 

yellow tipping. Orange-yellow streaks caused 

by dust should not be confused with true yellow 

tipping. If yellow flames are observed, follow 

instructions TO TURN OFF GAS TO APPLIANCE 

(see Figure 2), and contact qualified service agency.

6.  Adjust thermostat to normal setting.

D.

 S

chedule Inspection by Qualified Service Agency 

(Annual or at Beginning of Heating Season).

 For 

continued safe operation a qualified service agency 

must provide a more detailed inspection of burners, heat 

exchanger and vent system, and provide maintenance 

as specified in Installation, Operating and Service 

Instructions.

WARNING

Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service agency. 

Inspections should be performed at intervals specified in Installation, Operating and Service Instructions and this 

manual. Maintain manuals in a legible condition.

Keep boiler area clear and free of combustible materials, gasoline and other flammable vapors and liquids.
Do not place any obstructions in boiler room that will hinder flow of combustion and ventilation air.

Figure 4:  Pilot Burner

Figure 5:  Main Burner Flame

Содержание SERIES 3

Страница 1: ...ENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incendie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort Ne...

Страница 2: ...e RCF parts or attempt any service or repair work involving RCF without wearing the following protective gear 1 A National Institute for Occupational Safety and Health NIOSH approved respirator 2 Long...

Страница 3: ...G Do not reset Blocked Vent Switch unless a qualified service agency has determined and corrected the cause of any blockage in the vent system or chimney 3 Blocked Vent Switch See Figure 1 A device wh...

Страница 4: ...4 Figure 1 Control Locations...

Страница 5: ...5 Figure 2 Operating Instructions NOTE YOUR BOILER IS EQUIPPED WITH A HONEYWELL VR8204 OR VR8304 GAS VALVE PLEASE FOLLOW THESE OPERATING INSTRUCTIONS...

Страница 6: ...osed Checked Trial For Ignition Ignition Source Off Main Gas On Pilot Flame Proven Pilot Flame Not Proven Call For Heat Ends Standby Intelligent Hydronic Control can display typical Delay 60 Seconds I...

Страница 7: ...medium hard blue enveloping 3 8 to inch of sensing probe If flame is yellow and lazy follow instructions TO TURN OFF GAS TO APPLIANCE see Figure 2 and contact qualified service agency 5 Check main bur...

Страница 8: ...sale distributor Should you require assistance in locating a U S Boiler Company distributor in your area or have questions regarding the availability of U S Boiler Company products or repair parts ple...

Отзывы: