Single boiler Indirect Water Heater (IWH)Piped to Primary, Optional Domestic Hot Water Priority.
B
C
A
At least eight pipe diameters upstream of first tee.
A.
No further apart than 12" (~30 cm) or four pipe diameters, whichever is smaller.
B.
At least 18" (~46 cm) of straight pipe for Conventional Air Scoop.
C.
From
System
To
System
Flow
Check
Flow
Check
Full Port
Isolation
Valve
Full Port
Isolation
Valve
Optional
Full Port
Isolation
Valves
Optional
Full Port
Isolation
Valves
Heating
Circulators
Indirect
Circulator
Indirect
Supply
Indirect
Return
Expansion
Tank
Fill Valve
Backflow
Preventer
Cold
Water
Line
Air Separator
& Air Vent
Close Nipple
(Locate Header Sensor
As Close As Possible
To Downstream Tee)
Y-Strainer
(Recommended)
Secondary Unions Not
Required; Optional
Location Shown
Drain Valve
Relief Valve
Header Temperature
Sensor
(When Used)
Indirect Domestic
Water Heater
(IWH)
Boiler Circulator
Full Port
Isolation
Valves
To System
System
Zone
Valves
Heating
System
Circulator
Optional Zone Valve
Controlled System
Hydraulic Separator
May Be Substituted
For Tees
1
Parameter Selections:
System Pump = “Central Heat,
Optional Priority”
Boiler Pump = “any demand”
DHW Pump = “Primary Loop Piped IWH”
DHW Priority Enable is optional
Explanation:
This piping arrangement permits the
system pump to run or not run when
there is a domestic hot water call for heat.
Domestic hot water priority is optional. It
is permissible for the domestic and system
pumps to run at the same time. The boiler
pump must run for every call for heat.
CAUTION:
It is the installers responsibility
to select boiler piping configurations that provide
the proper flow rates and performance for the boiler
and indirect water heater.
B
C
A
Flow
Check
Optional
Full Port
Isolation
Valves
Optional
Full Port
Isolation
Valves
Heating
Circulators
To
System
Fill Valve
Backflow
Preventer
Expansion Tank
Air Separator
& Air Vent
Cold
Water
Line
Close Nipple
(Locate Header Sensor
As Close As Possible
To Downstream Tee)
Header Temperature
Sensor
(When Used)
Hydraulic Separator
May Be Substituted
For Tees
Y-Strainer
(Recommended)
From
System
Drain
Valve
Relief Valve
At least eight pipe diameters upstream of first tee.
A.
No further apart than 12" (~30 cm) or four pipe diameters, whichever is smaller.
B.
At least 18" (~46 cm) of straight pipe for Conventional Air Scoop.
C.
Secondary Unions Not
Required; Optional
Location Shown
Boiler Circulator
Full Port
Isolation
Valves
To
System
Optional Zone Valve
Controlled System
Heating
System
Circulator
System
Zone
Valves
1
Example Pump Parameter selections:
CAUTION:
It is the installers responsibility
to select boiler piping configurations that provide
the proper flow rates and performance for the
boiler.
Explanation:
This piping arrangement only
services central heat. When
there is any demand both
boiler and system pumps turn
on.
Parameter Selection:
System pump = “Central Heat,
Optional Priority”
Boiler pump = “any demand”
DHW pump = “never”
XII. Operation
F. Changing Adjustable Parameters (continued)
Single boiler with no Indirect Water Heater
Содержание K2FT-085
Страница 13: ...13 106375 01 4 16 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 87: ...87 106375 01 4 16 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Страница 88: ...88 106375 01 4 16 X Wiring continued ...
Страница 98: ...98 106375 01 4 16 Operating Instructions XI Start Up and Checkout continued ...
Страница 147: ...147 106375 01 4 16 XV Repair Parts continued 3A 3B 3C 3D 3F 3E 3G 3H 3O 3P 3Q 3R 3J 3K 3I 3M 3N 3L All Models ...
Страница 153: ...153 106375 01 4 16 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models ...
Страница 176: ...176 106375 01 4 16 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...