II.  Troubleshooting

A.  Troubleshooting problems where no error code is displayed.  

 

Warning

Electrical Shock Hazard.  Turn off power to boiler before working on wiring.

Condition

Possible Cause

Boiler not responding to call for heat, “Status” and 

“Priority” show “Standby”.

Boiler is not seeing call for heat. Check thermostat or zone wiring for loose connection, 

miswiring, or defective thermostat/zone control.

Boiler not responding to a call for heat, “Status” 

shows “Standby” and “Priority” shows Central Heat 

or Domestic Hot Water.

Boiler is not firing, temperature is greater than setpoint.  Water flow through boiler primary 

loop non-existent or too low.

Boiler Running but System or Boiler Circulator is 

not running

•  Check wiring for loose connection, miswiring.

•     When there is a Domestic Hot Water Heat Request the System or Boiler pumps will be                         

      forced “off” when there “Run Pump for” parameter is set to “Central heat, off DHW 

      demand” or “Central Heat, Optional Priority”.  This has been set to allow all of the heat 

      to be provided for fast indirect water heater recovery.  After one hour of “priority 

      protection” or the end of the Domestic Hot Water Heat Request the system and boiler 

      pumps will be free to run.

Home is cold during mild weather days

•   Increase Low Boiler Water Temperature parameter 5°F (2.8°C) per day.

Home is cold during cold weather days

•   Increase High Boiler Water Temperature parameter 5°F (2.8°C) per day

Faults are investigated by selecting the “Help” button from the “Home” screen.  When a fault is active the “Help” button flashes 

and the home screen turns a red color.  Continue to select flashing buttons to be directed to the Fault cause.  

B.  Display Faults:

indication

Condition

Possible Cause

Display Completely Dark

Fan off, LWCO lights off, no green power 

light on Control

No 120Vac Power 

at Boiler

Check breaker and wiring between breaker panel and boiler.

-  Blown high voltage fuse, Replacement Fuse Kit, part number 105349-01.

Display Completely Dark, Fan running

No 24Vac

Power to Control

-  Loose 120Vac connection wiring between boiler J-Box and transformer

-  Loose 24 Vac connection wiring between transformer and Control.

-  Blown low voltage fuse, Replacement Fuse Kit, part number 105349-01.

Blinking Green power light on Control

Control

Fault

-  The green light is connected to internal power supply. The power supply    

    is repeatedly starting and stopping (not normal) making the light flash. The 

    microprocessors are not running. 

-  Try disconnecting all terminals except 24VAC to power the Control. The 

    green light should be steady. If it is not, then the control is defective. If steady,  

    start plugging in all the connectors while watching the green light.  

    When faulty wiring reconnected, green light will begin to flash.

Display Completely Dark but Boiler fires No 5 Vdc

Power to Display

-  Loose 5 Vdc connection wiring between display and Control

-  Defective Display or Control.

Display lost 

Communication 

with Control 

-  Loose or defective display harness

-  Defective Display

-  Defective Control

Er0011

Adjustment 

Mode Password 

Timeout

-  The Control and Display are 

nOT

 defective.  The password has timed out.   

   Simply cycle power to the Display to restore operation.

Er0012

Control Failed

Defective Control.  Replace Sage.

Figure 9: Help Menu

Содержание K2

Страница 1: ...agency or the gas supplier This boiler requires a special venting system Read these instructions carefully before installing 9700609 As an ENERGY STAR Partner U S Boiler Company has determined that th...

Страница 2: ...ttp license reg state ma us pubLic pl_products pb_pre_form asp for the latest Approval Code or ask your local Sales Representative The Commonwealth of Massachusetts requires this product to be install...

Страница 3: ...f damage due to frozen pipes is a possibility the heating system should not be left unattended in cold weather or appropriate safeguards and alarms should be installed on the heating system to prevent...

Страница 4: ...4 105337 03 5 15 Table of Contents I Operation 5 II Troubleshooting 33...

Страница 5: ...r can be configured to start a lag boiler after operating at 50 modulation rate for longer than an adjustable time The boilers are modulated in unison parallel modulation rate to ensure even heat dist...

Страница 6: ...or is automatically adjusted as a thermostat s sleep or Away Modes or Outdoor Air Reset 5 Outdoor Air Reset Ifanoutdoortemperaturesensorisconnectedtotheboiler and Outdoor Reset is enabled the Central...

Страница 7: ...he boiler will shut down and an open limit indication and error code are provided If the limit installed is a manual reset type it will need to be reset before the boiler will operate 5 Boiler Mounted...

Страница 8: ...6 Multiple Demands TheSequenceMasterrespondstoCentralHeat Auxiliary Heat DHW and frost protection demands similar to the standaloneboiler Forexample whenselectedandDHW priorityisactive thesequencemast...

Страница 9: ...ce continues with run stabilization and low fire hold time Once the field adjustable low fire hold time is completed normal boiler operation begins modulation rate depending on temperature and setpoin...

Страница 10: ...e symbol returns to the display to previous menu or screen Repeatedly pressing the Close symbol will always return the display to the Home screen Arrow Symbol The Arrow symbol links together all scree...

Страница 11: ...boiler protection logic the 6 symbol blinks and becomes a screen link Rate The rate value is equal to the actual kbtu hr input divided by the boiler rated input Priority The selected Priority is shown...

Страница 12: ...mance For example studying a differential temperature trend may indicate pump speed settings need to be changed Trend Screens NOTE Firing Rate Trend shows fan demand and feedback Burner Status Screen...

Страница 13: ...ld zone number with a solid underscore Press the zone control button to view individual zone Zone Panel 1 typical for 2 through 4 Zone panel screens show individual zone status cycle counts and indivi...

Страница 14: ...Domestic Hot Water Frost Protection or Warm Weather Shutdown The Sequencer Status screen is selected by pressing Status button from the Home screen when Sequence Master is enabled The Networked Boiler...

Страница 15: ...n on the Home screen Press the Adjust button on the Adjust Mode screen or Press Service Contact for service provider contact information Press Login button to access password screen Press 5 digit disp...

Страница 16: ...trol s measurement matching the reference reading Not Connected Connected Not Connected Zone Control Status Connected When the Zone Control is connected adjustable settings are automatically shown und...

Страница 17: ...Expected Heat Rate This parameter defines the highest modulation rate the Control will go to during a Domestic Hot Water call for heat If the rated input of the indirect water heater is less than the...

Страница 18: ...565 7620 6984 7200 7150 Minimum Light off RPM 3500 3500 3500 3500 3500 Maximum Light off rate RPM 4000 4000 4000 4000 4000 Altitude 4501 7800 Ft Parameter K2 80 57 K2 100 57 K2 120 57 K2 150 57 K2 180...

Страница 19: ...pected Heat Rate Adjustment Screens HeatMatch Software Figure 6 Four Zone House with Zone Control Connected Figure 7 Expected Heat Rate Adjustment with Zone Control Connected Example call for heat dur...

Страница 20: ...Demand Any Demand Header Sensor Demand Boiler Pump run pump for Activates the boiler pump output according to selected function Any Demand Pump Runs during any call for heat Header Sensor Demand Pump...

Страница 21: ...djustable Parameters continued Single boiler Indirect Water Heater IWH Piped to Primary Optional Domestic Hot Water Priority Sequencer Master Boiler 1 Boiler 2 Wiring locations Thermostat X DHW call f...

Страница 22: ...optional It is permissible for the domestic and system pumps to run at the same time The boiler pump must run for every call for heat I Operation F Changing Adjustable Parameters continued Example Pum...

Страница 23: ...reen without Saving Clear Entire Field Backspace Save Field and Exit Save Press box to input contractor information Contractor Name i Bill Smith 1 7 6 5 4 3 2 A ES C D C B 8 CL R 7 BS 8 Enter Contract...

Страница 24: ...is 180 F the maximum Diff Above is 20 F Further if the setpoint is 190 F the maximum Diff Above is 10 F 5 F 2 8 C 2 F to 25 F 1 1 C to 14 C Central Heat Diff Below The boiler starts when the water tem...

Страница 25: ...at temperature controller Proportion Integral Derivative PID values Higher values cause a larger firing rate change for each degree of temperature change If set too high firing rate overshoots require...

Страница 26: ...the temperature to exceed the Diff Above setpoint and cycle the boiler unnecessarily Lower values cause a smaller firing rate change for each degree of temperature change If set too low the firing rat...

Страница 27: ...the coldest outdoor temperature 70 F 21 1 C 32 F to 100 F 0 C to 37 8 C Central Heat High Outdoor Temperature The High Outdoor Temperature parameter is the outdoor temperature at which the Low Boiler...

Страница 28: ...C Auxiliary Heat Low Outdoor Temperature The Low Outdoor Temperature parameter is also called Outdoor Design Temperature This parameter is the outdoor temperature used in the heat loss calculation It...

Страница 29: ...8 C Fan Coil 100 F to 140 F 37 8 C to 60 C In Slab Radiant High Mass Radiant 160 F to 190 F 71 1 C to 87 8 C Convection Baseboard Fin Tube Convective 130 F to 160 F 54 4 C to 71 1 C Staple up Radiant...

Страница 30: ...nd to rapid load increases 70 50 100 Base Load Common Rate To maximize condensing boiler efficiency the firing rate is limited to an adjustable value Boilers are kept at or below this firing rate as l...

Страница 31: ...tral Heat 3 User defined Zone Control 2 Zone 3 Central Heat 4 User defined Zone Control 2 Zone 4 Central Heat 1 User defined Zone Control 3 Zone 1 Central Heat 2 User defined Zone Control 3 Zone 2 Cen...

Страница 32: ...10 is used as the temperature setpoint The following two parameters may be used to adjust the signal range Modbus Modbus is used as the temperature setpoint 130 F 54 4 C 80 F 26 7 C Central Heat Setp...

Страница 33: ...Help button flashes and the home screen turns a red color Continue to select flashing buttons to be directed to the Fault cause B Display Faults Indication Condition Possible Cause Display Completely...

Страница 34: ...itch settings have changed Set Master Slave switch to Master Set Zone Control switch ZC1 to ON Cycle power Zone Panel Electronics Failure A Zone Panel Duplicate Zone The Control has detected duplicate...

Страница 35: ...Limit The following messages appear when the firing rate is limited or reduced to help avoid a lockout or save energy Refer to Hard Lockout section for corrective actions High Stack Temperature Limit...

Страница 36: ...only the time the pressure switch is open 3 Boiler Safety Limit Open Boiler Safety Limit or External Limit wired to terminals J5 1 OPEN Jumper for External Limit wired to terminals 11 and 12 or devic...

Страница 37: ...s purged of air and that appropriate valves are open Sensor wiring reversed Supply or return sensor defective 16 Supply temp has risen too quickly Supply water temperature has risen too quickly See po...

Страница 38: ...not being detected by Sage2 2 Loose connection in 120 VAC blower wiring Loose or miswired blower speed harness Defective blower 19 Purge rate proving failed Blower is not running at Purge rate when it...

Страница 39: ...39 105337 03 5 15...

Страница 40: ...40 105337 03 5 15 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...

Отзывы: