C.  Combi Domestic Hot Water and Space Heating Models

1) 

Once a month

, recommend homeowner check the 

faucet temperature using a glass thermometer. 

2)  Turn on faucet completely to hottest setting 

available. Let faucet run for 3 minutes.

3)   Measure faucet temperature using mercury free 

glass thermometer that can be purchased at a local 

hardware store.

4)  Ensure steady state temperature is no more than 

120°F (49°C). 

5) 

Once a year

, operate domestic water relief valve on 

boiler several times up and down draining several 

gallons of water through valve.

 

NOTICE

Hard water conditions may result in scale deposits in Combi components.  Hard water will significantly 

shorten the life of these parts.  Water conditioning is recommended for water hardness greater than 

200 ppm.
DHW output capacity in GPM changes with varying domestic inlet water temperatures.
Do not use ethylene glycol or chemicals that are not explicitly permitted by the boiler installation 

instructions.  See the “Start-Up and Checkout” section of instructions for important information on 

water chemistry requirements.

 

DANGER

Electrical Shock Hazard.  Positively assure all electrical connections are unpowered before attempting 

installation or service of electrical components or connections of the boiler or building.  Lock out all 

electrical boxes with padlock once power is turned off.

 

DANGER

Water temperature above 120°F (49°C) can cause serious injury.  Mixing valve temperature setting should 

be done by a licensed contractor per local code requirements.  To ensure correct temperature control, use 

the water thermometer at faucet outlet.