C. Combi Domestic Hot Water and Space Heating Models
1)
Once a month
, recommend homeowner check the
faucet temperature using a glass thermometer.
2) Turn on faucet completely to hottest setting
available. Let faucet run for 3 minutes.
3) Measure faucet temperature using mercury free
glass thermometer that can be purchased at a local
hardware store.
4) Ensure steady state temperature is no more than
120°F (49°C).
5)
Once a year
, operate domestic water relief valve on
boiler several times up and down draining several
gallons of water through valve.
NOTICE
Hard water conditions may result in scale deposits in Combi components. Hard water will significantly
shorten the life of these parts. Water conditioning is recommended for water hardness greater than
200 ppm.
DHW output capacity in GPM changes with varying domestic inlet water temperatures.
Do not use ethylene glycol or chemicals that are not explicitly permitted by the boiler installation
instructions. See the “Start-Up and Checkout” section of instructions for important information on
water chemistry requirements.
DANGER
Electrical Shock Hazard. Positively assure all electrical connections are unpowered before attempting
installation or service of electrical components or connections of the boiler or building. Lock out all
electrical boxes with padlock once power is turned off.
DANGER
Water temperature above 120°F (49°C) can cause serious injury. Mixing valve temperature setting should
be done by a licensed contractor per local code requirements. To ensure correct temperature control, use
the water thermometer at faucet outlet.