http://u-prox.com
17
1.
Panel checks for DHCP mode ON (panel address 0.0.0.0) or static IP
2.
If DHCP mode is ON, the dynamic IP address obtain routine will start
3.
The panel automatic configuration mode starts if the access control system
IP address (IP or DNS name) is not set:
a.
Panel sends data packages announcing access control system
server about itself as a new device in the local network
Despite it is broadcast announcement, it is limited with single
range local network and active network equipment. That’s why
the IP addresses of the access control system server are to be
set manually for networks with sophisticated topology.
b.
The system will warn operator after the receiving of the data
package from the new panel. Operator must add panel to the
system database (DB).
c.
After the panel added to the DB it receives the answer from the
access control system server. The address of the access control
system server recorded into the control panel and it stops to
broadcast.
d.
Operator has to upload panel after its adjustment recorded into
the DB. Panel becomes associated to the certain access control
system server, eliminating panel control capture with another
system.
Return panel to the factory settings to eliminate the panel
association to the system
e.
In the case of access control system server IP address change
panel will initiate the automatic configuration routine, but the data
exchange will be possible with previously connected system only.
Global antipassback
U-Prox IP100 control panel can operate in a system of global antipassback. The
main controller U-Prox IC A tracks the location of a person on the fact of its passage
through the access point. U-Prox IC A receives data about the passages from
control panels U-Prox IP400, NDC F18 IP, U-Prox IP100, U-Prox IP300.
The basis of the global antipassback is the zoned antipassback. The facility is
divided into rooms - zones of access or areas. With this division the entrance to
another area is exit from the previous one, and the passage in the area is possible
through various access points.
Antipassback control panel receives data from the access control panels and tracks
the movement of personnel from area to area . Also can be tracked the location of
the person who has multiple IDs (See Figure 8).