R-600A Specifications

USER GUIDE

 R-600A Specifications 3

u-line.com

SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE •

SERVICE

Evacuate/reclaim via the piecing pliers to ensure the 
system is empty of R-600a before any system work is 
performed.

The recovery cylinder must be evacuated (no air inside) 
prior to accepting R-600a.

The recovery cylinder must not be filled more than 45% 
safe fill level and refrigerants must not be mixed.

The recovery cylinder must be clearly marked with R-
600a and Flammable Warning labels. 

Ensure proper ventilation during recovery/reclaiming of R-
600a.

Start vacuum pump/recovery pump prior to piercing the 
compressor process tube.

Follow recovery/reclaim OEM instructions for the specific 
equipment used.

SYSTEM REPAIR

Ensure no residual R-600a refrigerant is left within the 
system prior to repair (simple venting is not sufficient).

Evacuate and charge with dry nitrogen for leak checks.

Repair leaks or replace system parts as required. 

When re-brazing, the system must be purged with dry 
nitrogen and at least one access point open to the 
atmosphere.

When re-brazing, proper ventilation is required along with 
constant monitoring for the presence of R600a refrigerant. 

The filter dryer must be replaced any time the sealed 
system is serviced. 

No system should be open to the atmosphere for longer 
than 15 minutes to avoid moisture migration into the 
system components.

LEAK DETECTION

After removal of the R-600a, the unit can be charged with 
dry nitrogen or helium.

Electronic leak detection or soap solution can be used to 
check for nitrogen/helium leaks.

Never use a halide torch or lighted match to check the 
system for leaks at any time. 

The high side of the refrigeration system (compressor 
discharge to outlet of drier) must be leak tested with the 
compressor running.

36

Содержание UHCL115IS01A

Страница 1: ...USER GUIDE SERVICE MANUAL Model UHCP115 SS81A...

Страница 2: ...rain Anti Tip Bracket General Installation Grille Installation Door Swing Door Adjust Maintenance Cleaning Cleaning Condenser Extended Non Use Operating Instructions First Use Control Operation Ice Ai...

Страница 3: ...HT PRODUCT RIGHT PLACE RIGHT TEMPERATURE PRODUCT INFORMATION Looking for additional information on your product User Guides Spec Sheets CAD Drawings and Product Warranty information are available digi...

Страница 4: ...oderate personal injury property or equipment damage This unit contains R600a Isobutane which is a flammable hydrocarbon It is safe for regular use Do not use sharp objects to expedite defrosting Do n...

Страница 5: ...e so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulations regarding the disposal and recycling of refriger...

Страница 6: ...ures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of direct sunlight and away from heat generating e...

Страница 7: ...it Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that has been pl...

Страница 8: ...t can NOT be installed behind a closed cabinet door If you would like to align the face of the unit with other adjacent cabinet doors you may need to alter the wall just behind the drain connection on...

Страница 9: ...cording to each unit s electrical specifications requirements Side by Side Installation with Bracket 1 Slide both units out so screws on top of units are easily accessible 2 Remove screws as shown bel...

Страница 10: ...ion WARNING Connect to potable water supply only CAUTION Review obey and understand the local plumbing codes before you install your unit Connect to the cold water supply The water pressure should be...

Страница 11: ...some vibration A water supply line contacting an internal component or cabinet wall can cause excessive noise during operation or damage to the line 4 On the back panel break away filler feature in b...

Страница 12: ...te of 1 4 per foot 1 cm per 50 cm Drain can NOT be located directly below the unit Unit has a solid base that will not allow the unit to drain below itself There is a possibility that hose connections...

Страница 13: ...ered a pre installed U Line P60 drain pump If you need to install a P60 drain pump into your unit see DRAIN PUMP section in the User Manual See below for typical installations requiring a drain pump F...

Страница 14: ...oles and attach to unit with two screws removed in step 2 using a T 25 Torx driver Tighten screws fully 4 Gently push unit into position Be careful not to entangle the electrical cord or water line if...

Страница 15: ...ing s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Readjust the front legs to level the unit after it is corre...

Страница 16: ...the grille must be installed Removing the grille 1 Disconnect power to the unit 2 Slightly loosen three screws on bottom hinge 3 Remove two grille screws 4 Slide grille to the left and remove Installi...

Страница 17: ...4 Min 6 mm Units have a zero clearance for the door to open 90 when installed adjacent to cabinets Stainless Steel and black and white models require 2 1 8 54 mm door clearance to accommodate the han...

Страница 18: ...top of unit 2 Loosen do not remove top and bottom hinge screws using a Torx T 25 screwdriver on the top and a 1 4 socket on the bottom 3 Align door squarely with cabinet 4 Make sure gasket is firmly...

Страница 19: ...ng outward exposing the gasket channel 3 Remove the 3 pieces of gasket channel filler and reinstall on the opposite end of door 4 Install gasket into channel beginning at one corner and pressing in fi...

Страница 20: ...ecommends discarding the ice produced during the first two to three hours of operation to avoid possible dirt or scale that may dislodge from the water line When plugged in the unit will begin operati...

Страница 21: ...t ice thickness See Ice section Enable Sabbath Mode Press and hold for 5 seconds and release The oF oC symbol will flash briefly after 5 seconds Interior light and display will go dark and remain so u...

Страница 22: ...rol Operations sections for details and other options For more information about BrightShield visit www u line com For more information about Vyv Antimicrobial Light Technology visit www vyv tech Test...

Страница 23: ...ogether as a slab increases A bridge thicker than 1 8 3 2 mm may cause cubes to overfill the ice bucket 32 ice cubes are formed on a 4 x 8 slab during each cycle Each cycle takes approximately 15 20 m...

Страница 24: ...ding Airflow and Product Loading NOTICE The unit requires proper airflow to perform at its highest efficiency Do not block the front grille at any time or the unit will not perform as expected Do not...

Страница 25: ...appropriate treatment Wear rubber gloves and safety goggles and or face shield when handling Ice Machine Cleaner Clean surfaces with a mild detergent and warm water solution Do not use solvent based...

Страница 26: ...for 5 seconds 9 When water begins flowing over the evaporator approximately 3 minutes pour 1 2 oz of Clear Ice Machine Cleaner into the water trough The cleaning process will last approximately 45 mi...

Страница 27: ...mental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric power to the unit before cleaning the condenser NOTICE DO NOT use any type of cleaner on the condenser uni...

Страница 28: ...remain open to prevent formation of mold and mildew Open door a minimum of 2 50 mm to provide the necessary ventilation WINTERIZATION If the unit will be exposed to temperatures of 40 F 5 C or less t...

Страница 29: ...ing components Despite this technology your model may make sounds that are unfamiliar Normal operating sounds may be more noticeable because of the unit s environment Hard surfaces such as cabinets wo...

Страница 30: ...in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial number of the unit it was removed from the date and the servicer...

Страница 31: ...r warranty labor Units must be registered prior to warranty submittal Customers may register at www U Line com A proof of purchase is required We also accept the following information to update warran...

Страница 32: ...TEMP THERMISTOR 80 54070 00 19 HINGE ASSEMBLY 80 55595 00 20 ICE SCOOP CLR 80 54080 00 21 LIGHT ASSENBLY VYV 80 54000 01 22 LEG LEVELERS 4 80 54019 00 23 MAGNET W SCREWS 2 80 54250 00 24 MAIN BOARD 8...

Страница 33: ...ranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U Line requires the return of original parts we will inform...

Страница 34: ...ust observe all federal state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder type fi...

Страница 35: ...pump and recovery equipment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system p...

Страница 36: ...is left within the system prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing the sy...

Страница 37: ...ll a Schrader Type access port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minu...

Страница 38: ...e Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near room temperature Very hot Top passes warm Lowe...

Страница 39: ...ist strap that is grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and...

Страница 40: ...e diagnostic tips and as always if additional help is required please contact the U Line Corp Customer Care Facility at 1 800 779 2547 for assistance NORMAL OPERATING SOUNDS All models incorporate rig...

Страница 41: ...unit if needed Low Ice Production Dirty evaporator dirty condenser faulty bin thermistor Clean the evaporator using U Line cleaner clean the condenser coil if needed check bin thermistor reading in s...

Страница 42: ...art below to help diagnose the issue Before beginning it is important to first verify the unit is not simply set to sabbath mode Check Voltage At Wall Outlet Verify Voltage At Main Control Voltage Inp...

Страница 43: ...vigates through service menu LED activated with button activation 3 Down Button Decreases temperature Navigates through service menu LED activated with button activation 4 Light Button Activates light...

Страница 44: ...ht key and the power key for 5 seconds The display will flash once and beep and the degree symbol will begin to flash When the degree symbol is flashing the unit will allow the use of the control for...

Страница 45: ...is model E5 Thermistor 1 shorted E6 Thermistor 2 shorted E7 Thermistor 3 shorted E8 Thermistor 4 shorted Does not apply to this model E9 Door 2 lower open P1 Pump Circuit open Does not apply to this m...

Страница 46: ...show the number of minutes the compressor has run in the prior cycle or current cycle if the compressor was running when service mode was entered 24 ACTIVATE DEFROST HARVEST Turns on the hot gas bypa...

Страница 47: ...use the up and down arrow buttons to select the appropriate model number See Above Model List 5 Press the light bulb button once 6 The display will blink and then will appear as the programmed display...

Страница 48: ...an Condenser Fan N A N A 2218R N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2218RGL N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2218WC N A N...

Страница 49: ...e operating temperature within that zone Thermistor two Evaporator Located on the evaporator It is used for defrost THERMISTOR FAILURE Zone Thermistor If the zone thermistor in the unit fails the unit...

Страница 50: ...USER GUIDE Defrost 1 SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Defrost These models have no defrost options 50...

Страница 51: ...improper use maintenance installation service repair acts of God fire flood or other natural disasters The product must be installed operated and maintained in accordance with your product s User Guid...

Отзывы: