U-Line UADA24RGLB13B Скачать руководство пользователя страница 41

USER GUIDE

 Troubleshooting - Extended 3

u-line.com

SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • 

SERVICE

MAIN CONTROL

The main control board is very robust and is rarely the 
cause of system issues. It is important to fully diagnose 
the board for any suspected failures before attempting to 
remove the board for replacement or service. Follow the 
guidelines below to fully test and diagnose the main 
control.

Power Fault

If the unit does not (or seems to not) power on, follow the 
flow chart below to help diagnose the issue. Before 
beginning it is important to first verify the unit is not 
simply set to sabbath mode.

Testing The Main Control

If the main control is suspected of being faulty, the 
following procedure should be performed to verify main 
control for functionality.

Relay & DC Outputs

One of the primary functions of the main control is to 
operate the multiple relay and DC outputs during each 
cycle. Verify proper operation of these relays using the 
following procedure.

1. Enter “Relay Toggle” through the service menu.

NOTICE

Frequently toggling the compressor relay could 
force the compressor into overload. The 
compressor will automatically deactivate during 
an overload and will remain deactivated until the 
overload switch cools. This could take some 
time. It is important to allow the compressor at 
least 5 minutes off time between relay cycles.

2. Toggle the relay. Its related component should 

activate / deactivate with the switching of the relay. If 
it does not, test component.

Other Suspected Main Control Faults

If other components have been ruled out as being faulty 
but the unit continues to have operating issues, it is most 
likely due to a configuration error. Configuration errors 
can be cleared by restoring the unit to its factory default 
setting. Factory defaults may be restored through the 
service menu.

CAUTION

!

Precautions must be taken while working with 
live electrical equipment. Be sure to follow 
proper safety procedures while performing tests 
on live systems.

Check Voltage 

At Wall Outlet

Verify Voltage At 

Main Control 

Voltage Input

Check Fuse F1

For Continuity

Replace 

Reed Switch

Replace Main

Board

Replace

Fuse

Replace

Power Cord

Alert Customer 

Of Power Failure

Is the Reed

Switch Operating

Properly?

Inspect 

Customer UI 

and Data Cable 

Connect Test Display 

Cycle Power And Check 

For Operation 

No Voltage

No Voltage

Voltage

Continuity

Operating

Not Operating

No Continuity

No

Yes

Voltage

41

Содержание UADA24RGLB13B

Страница 1: ...SER GUIDE SERVICE MANUAL SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE ADA Series ADA24RGL 24 Glass Door Refrigerator RIGHT PRODUCT RIGHT PLACE RIGHT TEMPERATURE SINCE 196...

Страница 2: ...Installation Door Swing Door Adjust Maintenance Cleaning Cleaning Condenser Extended Non Use Operating Instructions First Use Control Operation Sabbath Mode Airflow and Product Loading Service Interio...

Страница 3: ...lect products are available worldwide PRODUCT INFORMATION Looking for additional information on your product User Guides Spec Sheets CAD Drawings Compliance Documentation and Product Warranty informat...

Страница 4: ...ury or death WARNING Warning means that failure to follow this safety statement could result in serious personal injury or death CAUTION Caution means that failure to follow this safety statement may...

Страница 5: ...reezer take off the doors and leave shelves in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulatio...

Страница 6: ...10 C and 100 F 38 C Higher ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of dir...

Страница 7: ...to the unit Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that ha...

Страница 8: ...llation When built in your unit does not require additional air space for top sides or rear However the front grille must NOT be obstructed and clearance is required for an electrical connection in th...

Страница 9: ...R GUIDE Product Dimensions 1 u line com SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Product Dimensions 23 1 4 591 mm 32 to 33 813 mm 838 mm 24 610 mm Not Including Handl...

Страница 10: ...ed according to each unit s electrical specifications requirements Side by Side Installation with Bracket 1 Slide both units out so screws on top of units are easily accessible 2 Remove screws as show...

Страница 11: ...models only have three screws but same screws are used in both applications 3 Place bracket part 14154 over holes and attach to unit with two screws removed in step 2 using a T 25 Torx driver Tighten...

Страница 12: ...djust the rear legs to achieve a total unit rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gent...

Страница 13: ...he unit the grille plinth strip base fascia must be installed WARNING DO NOT touch the condenser fins The condenser fins are SHARP and can be easily damaged Removing the grille 1 Disconnect power to t...

Страница 14: ...adjacent to cabinets Stainless Steel and black and white models require 2 1 8 54 mm door clearance to accommodate the handle if installed next to a wall Integrated models require 1 4 6 mm clearance i...

Страница 15: ...door TO ALIGN AND ADJUST THE DOOR Remove grille Remove the grille see GRILLE PLINTH INSTALLATION section of this guide 1 Loosen do not remove top and bottom hinge screws 2 Align door squarely with cab...

Страница 16: ...are door for reinstallation 1 Remove gasket This will reveal mounting holes for the magnet assembly 2 Remove plunger bracket from door with T 10 TORX driver Be sure to only remove the two screws holdi...

Страница 17: ...the factory Initial startup requires no adjustments NOTICE U Line recommends allowing the unit to run overnight before loading with product When plugged in the unit will begin operating under the fac...

Страница 18: ...OL FUNCTION GUIDE FUNCTION COMMAND DISPLAY OPTIONS ON OFF Press and release Unit will immediately turn ON or OFF Toggle lights Press and release to leave interior light on for 3 hours Glass door wine...

Страница 19: ...ain internal temperatures and set points View a full list of Star K certified U Line units at www star k org To enable Sabbath Mode 1 Press 4 and hold for ten seconds and release the F C symbol will f...

Страница 20: ...erform as expected When loading your unit leave space between the internal fans or vents and product loaded Anything blocking the required airflow circulation will result in uneven temperature distrib...

Страница 21: ...e hump on the right hand side 3 Tilt up right hand edge of shelf 2 4 Remove shelf from unit by pulling out 3 Insert the shelves as follows 1 To move to a different position in the unit insert shelf at...

Страница 22: ...ss tile and counter cleaners If any surface discoloring or rusting appears clean it quickly with Bon Ami or Barkeepers Friend Cleanser and a nonabrasive cloth Always clean with the grain Always finish...

Страница 23: ...nal injury and damage to the inner lining NOTICE The drain pan was not designed to capture the water created when manually defrosting To prevent water from overflowing the drain pan place towels or ot...

Страница 24: ...tal conditions more or less frequent cleaning may be necessary WARNING Disconnect electric power to the unit before cleaning the condenser WARNING DO NOT touch the condenser fins The condenser fins ar...

Страница 25: ...t is returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open...

Страница 26: ...listed Compressor The compressor makes a hum or pulsing sound that may be heard when it operates Evaporator Refrigerant flowing through an evaporator may sound like boiling liquid Condenser Fan Air mo...

Страница 27: ...openings and the time the door is open The time the internal light is illuminated This mainly affects product on the top rack or shelf Digital Display Shows 1 16 or 99 A factory test mode may be enabl...

Страница 28: ...UG 220 240 VOLT PLUG OVERLOAD NEUTRAL WHITE 115v DARK BLUE 220 240v TO COMPRESSOR NEUTRAL WHITE 115v DARK BLUE 220 240v BLUE 115V LIGHT BLUE 220V 240V TO COMPRESSOR 1 10 CONTROL BOARD ZONE TEMP FUSE 1...

Страница 29: ...nt of a part the servicer is authorized to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial numb...

Страница 30: ...shes 12 represents the production month In most cases warranty status can be verified by the production date information within the serial number Alternatively a Proof of Purchase or equivalent may su...

Страница 31: ...s 80 54320 00 15 Evaporator cover 80 54319 00 16 Evaporator fan 80 54321 00 17 Grille w screws 80 54325 00 18 Handle w logo 80 54214 00 19 Hinges 2 w screws 80 54208 00 20 Keys babylock 80 54330 00 21...

Страница 32: ...s will be shipped at no charge after U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U L...

Страница 33: ...federal state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder type fire extinguisher...

Страница 34: ...equipment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing a...

Страница 35: ...he system prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing the system must be pur...

Страница 36: ...e access port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the...

Страница 37: ...Lower than normal Warm near room temperature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near ro...

Страница 38: ...st strap that is grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and...

Страница 39: ...utputs located on the relay power board Included in this section are some diagnostic tips and of course if additional help is required please contact the U Line Corp Customer Care Facility at 1 800 77...

Страница 40: ...efer to 14 Error Log in Service Mode Thermistor failure Check Error Log in Service Mode OHM thermistor Frost Buildup Inside Unit Door Ajar or Restricted from Closing Check door clearance to adjoining...

Страница 41: ...into overload The compressor will automatically deactivate during an overload and will remain deactivated until the overload switch cools This could take some time It is important to allow the compres...

Страница 42: ...d magnetic force pulls the reed to its contact and closes the circuit which turns the light and display off When the door is open the reed pulls away from the contact and opens the circuit If the door...

Страница 43: ...gates through service menu LED activated with button activation 3 Down Button Decreases temperature Navigates through service menu LED activated with button activation 4 Light Button Activates light f...

Страница 44: ...ter exit this mode hold the light key and the power key for 5 seconds The display will flash once and beep and the degree symbol will begin to flash When the degree symbol is flashing the unit will al...

Страница 45: ...n the refrigerator section 13 ADJUST DEFROST DURATION 0 TO 99 MINUTES The length of the defrost can be adjusted 0 to 99 minutes long The other defrost parameters still apply Lengthening a defrost may...

Страница 46: ...n will continue to run at the end of a cooling cycle Adjustable 0 99 minutes 19 INDIVIDUAL COMPONENT TOGGLE 20 MODEL NUMBER INDICATOR Displays the two digit model number of the specific unit See model...

Страница 47: ...conds use the up and down arrow buttons to select the appropriate model number See Above Model List 5 Press the light bulb button once 6 The display will blink and then will appear as the programmed d...

Страница 48: ...t Evaporator Fan Condenser Fan N A N A 2218WC N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2224BEV N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N...

Страница 49: ...thermistor connection you should replace the thermistor and the thermistor harness Thermistor error information can be found in the Control Operations Service section This unit has two thermistors The...

Страница 50: ...C 1224 RF 12 45 15 9 1215 1224 2218 2245 2224 2260 WC ZWC 12 45 45 7 1215 1224 2218 2245 2224 2260 R RSOD RDC BEV DC DWR RGL 12 45 42 6 CO29 F 12 18 n a CO1224 F 12 18 45 7 1224FZR Freezer Mode 6 45...

Страница 51: ...ing with the cooling cycle or if not currently cooling the fan will run for 1 minute to circulate air and clear any condensation that may have appeared on glass doors and shelves Note If the unit is s...

Страница 52: ...emove the 4 screws mounting the fan shroud to the evaporator plate 13 Remove and replace fan Take special care to properly route fan wire NOTICE Fan must be oriented to pull air in through lower evapo...

Страница 53: ...nty arising by operation of law U Line will not be responsible for any consequential or incidental damages arising from the breach of these warranties or any other warranty whether express implied or...

Отзывы: