USER GUIDE

 Troubleshooting - Extended 9

SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • 

SERVICE

ERROR NOTIFICATION

The 3000 model series continuously monitors a series of 
inputs and parameters to ensure proper and efficient 
operation of your unit. Should the system detect a fault, an 
error notification will be displayed on the user interface. 
These errors are considered active and can also be viewed 
in the Self Test and All Errors mode of the service menu. 
See below for a list of errors and possible solutions.

Actual Temps

The “Actual Temps” option displays the offset corrected 
temperature of each zone and evaporator, as well as 
ambient temperature. 

1. To view actual temperatures, select “Actual Temps”

from the customer menu.

2. Press

 or   to scroll through available information.

3. To exit, select “Return to Menu” and press  .

ID

Description

Solution

No Comm

Unit lost 

communication to 

the display.

Inspect Customer UI 

and Data Cable (if 

defective replace entire 

door)

Zone T Open Left or right zone 

thermistor circuit 

open.

Check connection. 

Replace if necessary.

Amb Thrm 

Open

Ambient thermistor 

circuit open.

Check connection. 

Replace if necessary.

Zone T Short Left or right zone 

thermistor circuit 

shorted.

Check connection. 

Replace if necessary.

Amb Thrm 

Short

Ambient thermistor 

circuit shorted.

Check connection. 

Replace if necessary.

Temp Hi 6H+ Left or right Zone 

tempe10° 

over set point for 

over 6 hours.

Check compressor, 

evaporator fan and 

related relays and DC 

outputs.

Temp Hi 

12H+

Zone temperature 

+10° over set point

for over 12 hours.

Check compressor, 

evaporator fan and 

related relays and DC 

outputs.

Temp Lo 6H+ Zone temperature

-10° under set point

for over 6 hours.

Check compressor, 

evaporator fan and 

related relays and DC 

outputs.

Temp Lo 

12H+

Zone temperature

-10° under set point

for over 12 hours.

Check compressor, 

evaporator fan and 

related relays and DC 

outputs.

Door Open 

5M

Door switch open for 

more then 5 

minutes.

Verify door is closed and 

sealing. Check reed 

switch and related 

connections.

Up

Select

Down

RETURN TO MENU

ACTUAL TEMPS

BIN TEMP = 1.6

COND TEMP = 45.5

Can be displayed in Celsius

54

Содержание U-3060FZRS-00A

Страница 1: ...USER GUIDE SERVICE MANUAL Model U 3060FZRS 00A...

Страница 2: ...on Integrated Grille Dimensions Grille Plinth Installation Door Swing Door Stop Door Adjust Maintenance Cleaning Cleaning Condenser Extended Non Use Operating Instructions First Use Control Operation...

Страница 3: ...54 0300 Service Email onlineservice u line com Parts Email onlineparts u line com GENERAL INQUIRIES U Line Corporation 8900 N 55th Street Milwaukee Wisconsin 53223 USA Monday Friday 8 00 am to 4 30 pm...

Страница 4: ...this guide This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given sup...

Страница 5: ...stall or operate the unit behind closed doors Be sure front grille plinth strip base fascia is free of obstruction Obstructing free airflow can cause the unit to malfunction and will void the warranty...

Страница 6: ...r take off the doors and leave shelves in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulations re...

Страница 7: ...and 90 F 32 C Higher ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of direct su...

Страница 8: ...dry If the detachable type electric supply cord is damaged it must be replaced by an equivalent cord available from the manufacturer or its service agent NOTICE Electrical installation must observe a...

Страница 9: ...must be square and plumb front to back Although not required you may choose to increase the overall cutout width for ease of installation The Modular 3000 Series units are engineered with a variety of...

Страница 10: ...imensions 1 SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Product Dimensions 24 610 mm 3 5 8 to 4 5 8 92 mm to 118 mm 33 11 16 to 34 11 16 856 to 881 mm 23 5 8 600 mm Not...

Страница 11: ...ensions in each unit s Installation Guide Each door can be opened individually one at a time without interference However to ensure unobstructed door swing opening both doors at the same time 1 4 6 4...

Страница 12: ...a 2 Phillips head screwdriver 3 Completely slide the unit into its position in the cabinet Be certain unit height is properly adjusted See GENERAL INSTALLATION 4 Open door completely Make certain door...

Страница 13: ...GRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE 5 Using a 3 32 drill bit drill 3 pilot holes 5 8 16 mm deep into cabinetry frame using the anti tip bracket as a template 6 Install the 3 remaining 8...

Страница 14: ...t rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Adjust the fron...

Страница 15: ...your grille plinth strip base fascia panel to match your surrounding furniture Finish front back and edges to prevent warping Carefully follow the manufacturer s recommendations for finish applicatio...

Страница 16: ...p base fascia rail with screw heads in base of unit 2 Push grille plinth strip base fascia rails towards the center of the unit and set rails over screw head 3 Slide grille plinth strip base fascia in...

Страница 17: ...the door to open 90 Allow for additional space for any knobs or pulls installed on the integrated panel frame Stainless Steel models that are installed adjacent to a wall require 2 1 4 57 mm door clea...

Страница 18: ...imately 90 2 Remove hinge cover by lifting top and bottom of hinge cover and sliding the cover inwards to remove from hinge 3 Once cover is removed slide hinge pin into hole as shown Pin should slide...

Страница 19: ...re that it is firmly in contact with the cabinet Also make sure the door gasket is not pinched on the hinge side of the door CAUTION Do not attempt to use the door to raise or pivot your unit This wou...

Страница 20: ...ment and Adjustment Procedure 1 Using a T 25 Torx Bit loosen each pair of Torx head screws on both the upper and lower hinge plates 2 Square and align door as necessary 3 Tighten Torx head screws on h...

Страница 21: ...s allowing the unit to run overnight before loading with product When plugged in the unit will begin operating under the factory default setting Follow the on screen prompt for language selection and...

Страница 22: ...will count down from 5 to off ON Press and release Unit will come on immediately Adjust temp Press to set temperature Press to confirm temperature or wait 5 seconds Adjust lighting Press to adjust li...

Страница 23: ...or notification will be displayed on the user interface See below for a list of errors NOTE Singe zone models will not use L left or R right zone indicators in error notification Setting Default F C R...

Страница 24: ...ss and select Actual Temps from the Customer Menu 2 Press or to scroll through available information 3 To return to the Customer Menu press and select Return to Menu Energy Saver Mode Energy Saver Mod...

Страница 25: ...To select a new sound level enter the Sound Level Menu from the Customer Menu 1 Press to select the current sound level 2 Press The current setting will begin to flash 3 Press or to select a differen...

Страница 26: ...hile settings are restored When restoration is complete Restoring will return to Restore To exit Factory Default press to select Return to Menu and press to confirm Help To access the Help Menu select...

Страница 27: ...maintain internal temperatures and set points To enable Sabbath Mode 1 Open the unit s door to activate the display 2 To access the Customer Menu hold for 5 seconds 3 Press or to scroll through avail...

Страница 28: ...Product Loading NOTICE The unit requires proper airflow to perform at its highest efficiency Do not block the front grille internal fans or vents at any time or the unit will not perform as expected...

Страница 29: ...he racks 3 Lift the rear of the basket off its seat on the rack 4 Pull the basket up and away from the racks To reinstall 1 Fully extend the empty rack from within the cabinet 2 Set the rear of the ba...

Страница 30: ...rite will cause the graining in the stainless steel to become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete removal of the rust may not be possible...

Страница 31: ...n pan and possibly damaging water sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in an ope...

Страница 32: ...essary Depending on environmental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric current to the unit before cleaning the condenser NOTICE DO NOT use any type of...

Страница 33: ...returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open to pr...

Страница 34: ...are common refrigeration components with a brief description of the normal operating sounds they make NOTE Your product may not contain all the components listed Compressor The compressor makes a hum...

Страница 35: ...e setting Ambient temperature where installed Installation in direct sunlight or near a heat source The number of door openings and the time the door is open The time the internal light is illuminated...

Страница 36: ...240 VOLT PLUG 16 8 9 1 NEUTRAL WHITE 115v DARK BLUE 220 240v TO COMPRESSOR 6 1 10 5 ZONE EVAP DOOR SWITCH AMBIENT TEMP TEST TERMINAL LIGHT EVAP FAN CONDENSER FAN WHITE 115v DARK BLUE 220 240v VALVE OR...

Страница 37: ...a part the servicer is authorized to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial number of...

Страница 38: ...12 represents the production month In most cases warranty status can be verified by the production date information within the serial number Alternatively a Proof of Purchase or equivalent may submitt...

Страница 39: ...l be shipped at no charge after U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U Line r...

Страница 40: ...l state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder type fire extinguisher in the...

Страница 41: ...pment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing any pa...

Страница 42: ...tem prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing the system must be purged wi...

Страница 43: ...ess port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the charg...

Страница 44: ...r than normal Warm near room temperature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near room te...

Страница 45: ...to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and S pins To measure the run...

Страница 46: ...tion is some diagnostic tips and as always if additional help is required please contact the U Line Corp Customer Care Facility at 1 414 354 0300 for assistance MAIN CONTROL The main control board is...

Страница 47: ...o allow the compressor at least 5 minutes off time between relay cycles 2 Toggle the relay Its related component should activate deactivate with the switching of the relay Inputs The main control moni...

Страница 48: ...ary Inspect wire harness from main control board for pinch points or damage Repair split or pinched cabling Amb Thrm Short Inspect thermistor cable for pinch points or damage Replace if necessary Insp...

Страница 49: ...Whenever opening a thermistor connection be sure to apply a fresh dab of die electric grease System Condition Suction Pressure Suction Line Compressor Discharge Condenser Capillary Tube Evaporator Wat...

Страница 50: ...grille internal fans or vents at any time or the unit will not perform as expected Do not install the unit behind a door Quick Chill CAUTION Quick chill is designed to quickly pull warm beverages and...

Страница 51: ...at the beginning of a cooling cycle This delay gives the evaporator time to cool properly before warm air is passed over it The fan will continue to run for an additional 2 minutes at the end of a coo...

Страница 52: ...ary Zone T Open Zone thermistor circuit open Check connection Replace if necessary Evap T Open Evaporator thermistor circuit open Check connection Replace if necessary Amb Thrm Open Ambient thermistor...

Страница 53: ...Sabbath Mode from the Customer Menu 2 Press to select Off 3 Press Off will begin to flash 4 Press or to change Off to On 5 Press to confirm your selection The display will fade out as the unit enters...

Страница 54: ...replace entire door Zone T Open Left or right zone thermistor circuit open Check connection Replace if necessary Amb Thrm Open Ambient thermistor circuit open Check connection Replace if necessary Zo...

Страница 55: ...two thermistors Thermistor one is located along the right hand side wall inside of the unit and is used to maintain temperature within the unit Thermistor two is located on the back of the evaporator...

Страница 56: ...Defrost These units are frost free technology Model Hrs Between Defrost Time Length Minutes Stop Point 2218R WC 12 45 42 2224BEV R WC 12 45 42 3018R WC 12 45 40 1224DWR 12 45 42 1224WC 12 45 45 3024D...

Страница 57: ...the fan will either continue running with the cooling cycle or if not currently cooling the fan will run for 1 minute to circulate air and clear any condensation that may have appeared on glass doors...

Страница 58: ...3 Remove the 4 screws mounting the fan shroud to the evaporator plate 14 Remove and replace fan Take special care to properly route fan wire NOTICE Fan must be oriented to pull air in through lower ev...

Страница 59: ...improper use maintenance installation service repair acts of God fire flood or other natural disasters The product must be installed operated and maintained in accordance with your product s User Guid...

Отзывы: