Thermistor 2

 

Defrost

 

The models below have automatic or frost free design and do not require manual defrosting under normal 

conditions.

 

Defrost Settings

 

 

 

Base Model

 

Variant(s)

 

Compressor Run Time 

Between Defrost (Hours)

 

Duration in Minutes 

(Maximum)

 

Stop Temperature 

°F (°C)

 

1224

 

RF

 

12

 

45

 

15 (-9)

 

1215/1224/2218/2245/ 

2224/2260

 

WC, ZWC

 

12

 

45

 

45 (7)

 

1215/1224/2218/2245/ 

2224/2260

 

R, RSOD, RDC, 

BEV, DC, DWR, 

RGL

 

12

 

45

 

42 (6)

 

CO29

 

F

 

12

 

18

 

n/a

 

CO1224

 

F

 

12

 

18

 

45 (7)

 

1224FZR

 

Freezer Mode

 

6

 

45

 

42(6)

 

1224FZR

 

Refrigerator Mode

 

12

 

45

 

42(6)

 

The defrost settings for 3000 series models are determined by zone.

 

 

Defrost Settings by Zone (3000 Series)

 

 

Zones

 

Compressor Run Time 

Between Defrost (Hours)

 

Duration in Minutes 

(Minimum)

 

Duration in Minutes 

(Maximum)

 

Stop Temperature 

°F (°C)

 

Beverage/Drinks

 

12

 

5

 

60

 

42 (6)

 

Market/Fresh

 

12

 

5

 

60

 

42 (6)

 

Root/Root Cellar

 

12

 

5

 

60

 

45 (7)

 

Pantry

 

12

 

5

 

60

 

42 (6)

 

White Wine

 

12

 

5

 

60

 

45 (7)

 

Red Wine

 

12

 

5

 

60

 

45 (7)

 

Sparkling Wine

 

12

 

5

 

60

 

45 (7)

 

Polar

 

6

 

5

 

20

 

42 (6)

 

Deli

 

12

 

5

 

60

 

42 (6)

 

 Defrost 1

 

Remove Fan and Cover

 

CONVECTION COOLING 

This  unit  is  equipped  with  an  advanced  convection 

cooling  system.  Convection  cooling  stabilizes  cabinet 
temperature,  cools  product  faster  and  increases 
energy efficiency. 

 

Evaporator Fan 

The evaporator fan is responsible for circulating warm 

air  from  the  refrigeration  zone,  past  the  evaporator 
and back into the refrigerated zone.

 

The evaporator fan is factory set to have a 1 minute 

delay  at  the  beginning  of a  cooling  cycle.  This  delay 
gives  the  evaporator  time  to  cool  properly  before 
warm air is passed over it. The fan will continue to run 
for  an  additional  2  minutes  at  the  end  of  a  cooling 

Содержание U-3018RINT-00A

Страница 1: ...ATING INSTRUCTIONS MAINTENANCE SERVICE Modular 3000 Series 3018R 18 Solid Door Refrigerator SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Contents Intro Safety Safety and...

Страница 2: ...ent Parts System Diagnosis Guide Compressor Specifications Troubleshooting Extended Control Quick Guide Thermistor Defrost Remove Fan and Cover Door Adjust Operating Instructions First Use Control Ope...

Страница 3: ...and Product Warranty information are all available for reference and download at u line com PROPERTY DAMAGE INJURY CONCERNS In the unlikely event property damage or personal injury is suspected relate...

Страница 4: ...this safety statement could result in serious personal injury or death CAUTION Caution means that failure to follow this safety statement may result in minor or moderate personal injury property or e...

Страница 5: ...ren may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulations regarding the disposal and recycling of refrigeration appl...

Страница 6: ...ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of direct sunlight and away from h...

Страница 7: ...extension cord to connect power to the unit Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three p...

Страница 8: ...urements The opening must be square and plumb front to back Although not required you may choose to increase the overall cutout width for ease of installation The Modular 3000 Series units are enginee...

Страница 9: ...SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE USER GUIDE u line com Product Dimensions...

Страница 10: ...sted under Cutout Dimensions in each unit s Installation Guide Each door can be opened individually one at a time without interference However to ensure unobstructed door swing opening both doors at t...

Страница 11: ...try 3 Using a 3 32 2 50 mm drill bit drill 3 pilot holes 5 8 16 mm deep into bottom of counter top Use the anti tip bracket as a template 4 Install 3 8x5 8 screws into the plate using a 2 Phillips hea...

Страница 12: ...ning adjust the rear legs to achieve a total unit rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to b...

Страница 13: ...es are drilled to the correct depth in order to avoid splits in the wood when hardware is installed 1 Cut the panels to the dimensions listed in the diagram below 2 Optional Stain or finish panel to d...

Страница 14: ...adjustments A single prepared panel with insert must not weigh more than 20 lbs 10 kg Integrated Panel Preparation 1 Cut the main panel to the dimensions below For details see the drawings on the next...

Страница 15: ...EL NOTICE Due to differences in surrounding cabinetry the panel may not perfectly align with door The procedure below is designed to provide a 3 4 20 mm 28 13 16 mm 732 2 3 4 70 mm 2 3 4 70 mm R 5 8 R...

Страница 16: ...color Be sure to closely follow the instructions provided by the manufacturer 3 Optional Install handles and hardware NOTICE The door panel must not weigh more than 20 lbs 10 kg It is important to ens...

Страница 17: ...6 114 mm Front Side Extended Integrated Panel Extended Integrated Frame Integrated Panel Panel can extend beyond the door frame A minimum of 1 25 mm from the floor is required for proper ventilation 3...

Страница 18: ...GUIDE u line com A minimum of 1 25 mm is required from the floor to the bottom of the extended integrated panel frame for proper ventilation BACK SURFACE MUST HAVE AMPLE FLAT SURFACE TO MOUNT INTEGRAT...

Страница 19: ...Finish or stain your grille plinth strip base fascia panel to match your surrounding furniture Finish front back and edges to prevent warping Carefully follow the manufacturer s recommendations for f...

Страница 20: ...3 mm drill bit drill 6 pilot holes into the wood panel 1 2 12 mm deep using the holes in the door frame as a guide 10 Ensure the screws sit flush against the bottom of the channel Integrated Panel Int...

Страница 21: ...metal may be sharp Removing the grille plinth strip base fascia 1 Disconnect electrical current to unit 2 Using the included 7 64 Allen wrench loosen but do not remove both grille plinth strip base fa...

Страница 22: ...of each grille plinth strip base fascia rail 2 The grille plinth strip base fascia can be extended horizontally by pulling out a maximum of 1 1 2 38 mm Do not exceed 1 1 2 38 mm Secure the lock screws...

Страница 23: ...oor approximately 90 2 Remove hinge cover by lifting top and bottom of hinge cover and sliding the cover inwards to remove from hinge 3 Once cover is removed slide hinge pin into hole as shown Pin sho...

Страница 24: ...ully examine the door s gasket to ensure that it is firmly in contact with the cabinet Also make sure the door gasket is not pinched on the hinge side of the door CAUTION Do not attempt to use the doo...

Страница 25: ...N INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE USER GUIDE u line com b y l i f t i n g t o p a n d b o t t o m f l a p s a n d s l i d e i n w a r d s R e p e a t o n b o t t o m h i n g e D...

Страница 26: ...s from screw heads on opposite side 2 on top and 2 on bottom Using 2 Phillips bit remove the 4 underlying screws Reinstall the screws and caps on the opposite side 5 Partially install screw 1 in the o...

Страница 27: ...SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE USER GUIDE u line com Door Adjustments 2...

Страница 28: ...ds allowing the unit to run overnight before loading with product When plugged in the unit will begin operating under the factory default setting Follow the on screen prompt for language selection and...

Страница 29: ...ium or high Light ON OFF with door Press to have light on off with door Press and release to scroll through timer settings Customer menu Press and hold for 5 seconds Press to scroll through menu Mode...

Страница 30: ...tables Potatoes Onions Lemon Lime Melon Peppers Beans Cucumber Cut Vegetables QUICK CHILL CAUTION Quick chill is designed to quickly pull warm beverages and foods down to optimum storage temperature I...

Страница 31: ...Thrm Short Ambient thermistor circuit shorted Contact Customer Care L R Temp Hi 6H Left or right zone temperature 10 over set point for over 6 hours Verify door is closed and sealing Contact Customer...

Страница 32: ...ergy Saver Mode a small leaf icon will be displayed on the main screen 1 To enter Energy Saver Mode first select Energy Saver from the Customer Menu 2 Press to select Off in the menu 3 Press 4 Press t...

Страница 33: ...layed in either Fahrenheit or Celsius To change from Fahrenheit to Celsius enter the Fahrenheit Celsius Menu from within the Customer Menu 1 Press to select Degrees 2 Press The selection will begin to...

Страница 34: ...nd press to confirm Help To access the Help Menu select Help from the Customer Menu Press to scroll through available information The Help screen displays the following Model U Line contact informatio...

Страница 35: ...n internal temperatures and set points To enable Sabbath Mode 1 Open the unit s door to activate the display 2 To access the Customer Menu hold for 5 seconds 3 Press or to scroll through available sel...

Страница 36: ...ts at any time or the unit will not perform as expected When loading your unit leave space between the internal fans or vents and product loaded Anything blocking the required airflow circulation will...

Страница 37: ...e bin off the racks 3 Lift the rear of the bin off its seat on the rack 4 Pull the bin up and away from the racks To Reinstall 5 Fully extend the empty rack from within the cabinet 6 Set the rear of t...

Страница 38: ...brite will cause the graining in the stainless steel to become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete removal of the rust may not be possibl...

Страница 39: ...he drain pan and possibly damaging water sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in...

Страница 40: ...an the condenser when necessary Depending on environmental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric current to the unit before cleaning the condenser NOTI...

Страница 41: ...nit is returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain ope...

Страница 42: ...USER GUIDE u line com Extended Non Use 1...

Страница 43: ...e a tendency to reflect normal appliance operating noises Listed below are common refrigeration components with a brief description of the normal operating sounds they make NOTE Your product may not c...

Страница 44: ...displayed on the user interface See below for a list of errors NOTE Single zone models will not use L left or R right zone indicators in error notification ID Description Solution No Comm Unit lost c...

Страница 45: ...ater If required adjust the temperature control in a small increment see CONTROL OPERATION Causes which affect the internal temperatures of the cabinet include Temperature setting Ambient temperature...

Страница 46: ...that U Line will provide either under these warranties or under any warranty arising by operation of law U Line will not be responsible for any consequential or incidental damages arising from the br...

Страница 47: ...STALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE USER GUIDE u line com Copyright 2014 2017 U Line Corporation All Rights Reserved Publication Number 30379 04 2017 Rev K Warranty 1 Wir...

Страница 48: ...nt of a part the servicer is authorized to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial numb...

Страница 49: ...n year The number between the dashes 12 represents the production month In most cases warranty status can be verified by the production date information within the serial number Alternatively a Proof...

Страница 50: ...SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE USER GUIDE u line com Warranty Claims 1...

Страница 51: ......

Страница 52: ...at no charge after U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U Line requires the r...

Страница 53: ...king up Lower than normal Complete Restriction In deep vacuum Room temperature cool Room temperature cool Room temperature cool Room temperature cool No refrigeration Lower than normal No Gas 0 PSIG t...

Страница 54: ...e not shorted check the S and R to ground EMX20CLC Refrigerant R600a Voltage 115 127 VAC Frequency 60 Hz Run Cap 12 F 165 VAC Start Winding 6 7 Ohm at 77 F Run Winding 12 6 Ohm at 77 F LRA 3 7 A FLA 0...

Страница 55: ...on explanations Verification of temperature and thermistor performance can be identified by directly viewing actual temperature readings in the service mode Component failure issues can be identified...

Страница 56: ...uct Ensure proper use of Quick Chill mode Refer to Control Operation Section Control set too cold Refer to Adjusting Temperature Settings Section Review logged error codes Refer to Fault System Diagno...

Страница 57: ...e board for any suspected failures before attempting to remove the board for replacement or service Follow the guidelines below to fully test and diagnose the main control Power Fault If the unit does...

Страница 58: ...ing the unit to its factory default setting Factory defaults may be restored through the service menu CAUTION Precautions must be taken while working with live electrical equipment Be sure to follow p...

Страница 59: ...ect wire harness from main control board for pinch points or damage Repair split or pinched cabling Temp Hi 6H If excessive frost is also noted inspect door and door gasket for proper seal and alignme...

Страница 60: ...les The unit will otherwise operate normally Evaporator thermistor errors will be displayed in the error log Always assure that all thermistor connections are clean and dry Whenever opening a thermist...

Страница 61: ...E USED TO DETERMINE AT WHAT TEMPERATURE THE UNIT CYCLES O SETTING IS 2 DIFFERENTIAL RETURN TO MENU DIFFERENTIALS LEFT 16 C RIGHT 16 C EVAP FAN THIS MENU IS USED TO SET THE DURATION THE EVAPORATOR FAN...

Страница 62: ...t the main board where the communication cable plugs onto the pins for the red and black conductors If 5 VDC is not present replace the main control board If 5 VDC is present replace the communication...

Страница 63: ...n of zone valve Temp Lo Zone temperature Verify thermistor connections 12H 10 F under set are clean and dry Verify point for over 12 thermistor resistance Verify hours correct operation of zone valve...

Страница 64: ...porator Fan DC F3 Condenser Fan DC L1 Zone Lighting DC To access Relay Toggle 4 Press to select Relay Toggle 5 Press 6 Press to scroll through each relay and DC output 7 Press to toggle To exit the Re...

Страница 65: ...tomer All Temps menu To access Offsets 1 Press to select Offsets 2 Press 3 Press and to scroll through available thermistors To change offsets 4 Press the selected thermistor will begin to flash 5 Pre...

Страница 66: ...ith various differentials Evap Fan The Evap Fan option in the service menu allows servicers to change the Evaporator Fan runtime in minutes from 0 to 98 and OFF cycle time 0 to 98 To access Evap Fan 1...

Страница 67: ...he manufacturer warranty Re Select Model allows the units model information to be modified Changing the units model completely reprograms available zones relay assignments DC output assignments etc To...

Страница 68: ...f fan run times during and after a cooling cycle In order to allow time for the evaporator to properly cool the evaporator fan is delayed from starting with the cooling cycle for a given amount of tim...

Страница 69: ...select Off and press Off will begin to flash 4 Press to toggle between off and on 5 Press to confirm If set to on showroom mode will begin immediately To exit showroom mode press and hold for 5 secon...

Страница 70: ...tion can be found in the Control Operations Service section This unit has three thermistors Thermistor one Zone Located along the right hand side wall It is used to maintain the operating temperature...

Страница 71: ...or 1 Thermistor Resistance Data Temp F Temp C Nominal Resistance OHMS 40 40 169157 31 35 121795 22 30 88766 13 25 65333 4 20 48614 5 15 36503 14 10 27681 23 5 21166 32 0 16330 41 5 12696 50 10 9951 59...

Страница 72: ...ost Hours Duration in Minutes Minimum Duration in Minutes Maximum Stop Temperature F C Beverage Drinks 12 5 60 42 6 Market Fresh 12 5 60 42 6 Root Root Cellar 12 5 60 45 7 Pantry 12 5 60 42 6 White Wi...

Страница 73: ...d free of any dust buildup Evaporator Fan Replacement Should the evaporator fan need to be replaced follow the steps below 1 Remove any product from the unit 2 Uninstall unit 3 Disconnect power to the...

Страница 74: ...ough lower evaporator cover vents and push air out at fan mounting location 15 Installation is the reverse of removal 16 Care must be taken to assure the bottom of the evaporator cover is reinstalled...

Отзывы: