Compressor Specifications 1

u-line.com

SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • 

SERVICE

Compressor Specifications

DANGER

!

Electrocution can cause death or serious injury. 
Burns from hot or cold surfaces can cause 
serious injury. Take precautions when servicing 
this unit.

Disconnect the power source.

Do not stand in standing water when working 
around electrical appliances.

Make sure the surfaces you touch are not hot or 
frozen.

Do not touch a bare circuit board unless you are 
wearing an anti-static wrist strap that is 
grounded to an electrical ground or grounded 
water pipe.

Handle circuit boards carefully and avoid 
touching components.

To measure the start winding resistance, measure across 
the C and S pins.

To measure the run winding resistance, measure across 
the C and R pins.

Also check S to R and you should get the sum of the run 
and start windings.

To ensure the windings are not shorted, check the S and R 
to ground.

* All resistance readings are ±10%

EMX20CLC

Refrigerant

R600a

Voltage

115 - 127 VAC

Frequency

60 Hz

Run Cap

12

μ

F/165 VAC

Start Winding

6.7 Ohm at 77°F

Run Winding

12.6 Ohm at 77°F

LRA

3.7 A

FLA

0.5 A

Starting Device

8EA14C

Overload

4TM142RFBYY-53

C

S

R

OVERLOAD PROTECTOR

STARTING RELAY

CAPACITOR

RELAY COVER

ULIN_0368_A

48

Содержание Captain 1000 Series

Страница 1: ...GUIDE SERVICE MANUAL SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE 1000 Series 1215WC 15 Single Zone Wine Captain Model RIGHT PRODUCT RIGHT PLACE RIGHT TEMPERATURE SINCE...

Страница 2: ...tegrated Panel Installation Grille Plinth Installation Door Swing Door Adjust Wood Trim Finishing Operating Instructions First Use Control Operation Sabbath Mode Airflow and Product Loading U Line Win...

Страница 3: ...decades and is proud to have the opportunity to ship to you PRODUCT INFORMATION Looking for additional information on your product User Guides Spec Sheets CAD Drawings Compliance Documentation and Pro...

Страница 4: ...ury or death WARNING Warning means that failure to follow this safety statement could result in serious personal injury or death CAUTION Caution means that failure to follow this safety statement may...

Страница 5: ...reezer take off the doors and leave shelves in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulatio...

Страница 6: ...10 C and 100 F 38 C Higher ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of dir...

Страница 7: ...to the unit Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that ha...

Страница 8: ...ation When built in your unit does not require additional air space for top sides or rear However the front grille must NOT be obstructed and clearance is required for an electrical connection in the...

Страница 9: ...ons 1 u line com SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Product Dimensions 23 1 4 591 mm Includes 3 4 20 mm Integrated Panel 34 1 8 to 35 1 8 867 mm to 892 mm 14 15...

Страница 10: ...ed according to each unit s electrical specifications requirements Side by Side Installation with Bracket 1 Slide both units out so screws on top of units are easily accessible 2 Remove screws as show...

Страница 11: ...iver Tighten screws fully 4 Gently push unit into position Be careful not to entangle the electrical cord or water line if applicable 5 Check to be sure the unit is level from front to back and side t...

Страница 12: ...make two starter holes and fasten the anti tip brackets to the floor using the screws provided 7 Place the unit back into position making sure the feet engage the anti tip brackets properly Check the...

Страница 13: ...djust the rear legs to achieve a total unit rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gent...

Страница 14: ...ware is installed When applying an integrated panel to a unit ensure that both sides are finished in order to prevent warping In some frame installations the panel may be visible through the glass whi...

Страница 15: ...use of bar clamps to secure the panel to the door drawer If using tape be certain the tape will not damage panel finish upon removal 7 Using a 7 64 3 mm drill bit drill 6 pilot holes into the wood pan...

Страница 16: ...ove clamps from door drawer NOTICE If panel requires additional adjustment after removing clamps slightly loosen each screw and adjust panel as necessary Tighten screws upon completion 12 Starting at...

Страница 17: ...base fascia must be installed WARNING DO NOT touch the condenser fins 4 The condenser fins are SHARP and can be easily damaged Removing the grille 1 Disconnect power to the unit 2 Loosen the two screw...

Страница 18: ...adjacent to cabinets Stainless Steel and black and white models require 2 1 8 54 mm door clearance to accommodate the handle if installed next to a wall Integrated models require 1 4 6 mm clearance i...

Страница 19: ...et is not pinched on the hinge side of the door To align and adjust the door 1 Loosen do not remove top and bottom hinge screws 2 Align door squarely with cabinet 3 Make sure gasket is firmly in conta...

Страница 20: ...g on model Replace nuts if used Prepare door for reinstallation 1 Remove gasket This will reveal mounting holes for the magnet assembly 2 Remove magnet assembly from door with T 10 TORX driver Be sure...

Страница 21: ...ed to open past 90 do not require this step 1 Remove wine rack see WINE RACK INSTALLATION in Maintenance 2 Starting from the side that has the spacers previously unaltered units will be on the right h...

Страница 22: ...ning or finishing to prevent permanent damage to the inner liner of the unit Allow stain or finish to dry thoroughly at least 24 hours for each coat following the product manufacturer s instructions b...

Страница 23: ...Line recommends allowing the unit to run overnight before loading with product As warm air rises the temperature inside the unit tends to be slightly warmer at the top and slightly cooler at the bott...

Страница 24: ...OL FUNCTION GUIDE FUNCTION COMMAND DISPLAY OPTIONS ON OFF Press and release Unit will immediately turn ON or OFF Toggle lights Press and release to leave interior light on for 3 hours Glass door wine...

Страница 25: ...ain internal temperatures and set points View a full list of Star K certified U Line units at www star k org To enable Sabbath Mode 1 Press 4 and hold for ten seconds and release the F C symbol will f...

Страница 26: ...airflow to perform at its highest efficiency Do not block the front grille or the unit will not perform as expected Do not install the unit behind a door When loading your unit leave space between th...

Страница 27: ...subject of wine is your own palate Do not be afraid to make mistakes Experiment discover but most of all enjoy yourself and your new U Line product Guide To Common Styles Of Wine Matching Food and Wi...

Страница 28: ...e presentation of the cork has a rich and fascinating history dating back to the late 1800 s A phylloxera root louse devastation to the vineyards severely limited the supply of great wines Restaurateu...

Страница 29: ...at sediment is left undistributed and particles are not suspended vibration in a storage environment is not an issue Wines can become flat or tired when voids and vacuums are created inside the wine b...

Страница 30: ...Each U Line Wine Captain model is designed to impress and inspire anyone with an interest in wine by providing cellar conditions in stylish undercounter units U Line Wine Captain models offer stable s...

Страница 31: ...al wine racks properly position the bottles so the wine remains in contact with the cork which ensures the cork does not become dry U Line recommends arranging wine bottles as shown in the illustratio...

Страница 32: ...ss tile and counter cleaners If any surface discoloring or rusting appears clean it quickly with Bon Ami or Barkeepers Friend Cleanser and a nonabrasive cloth Always clean with the grain Always finish...

Страница 33: ...nal injury and damage to the inner lining NOTICE The drain pan was not designed to capture the water created when manually defrosting To prevent water from overflowing the drain pan place towels or ot...

Страница 34: ...tal conditions more or less frequent cleaning may be necessary WARNING Disconnect electric power to the unit before cleaning the condenser WARNING DO NOT touch the condenser fins The condenser fins ar...

Страница 35: ...is returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open t...

Страница 36: ...mponents listed Compressor The compressor makes a hum or pulsing sound that may be heard when it operates Evaporator Refrigerant flowing through an evaporator may sound like boiling liquid Condenser F...

Страница 37: ...or near a heat source The number of door openings and the time the door is open The time the internal light is illuminated This mainly affects product on the top rack or shelf Obstruction of front gri...

Страница 38: ...UG 220 240 VOLT PLUG OVERLOAD NEUTRAL WHITE 115v DARK BLUE 220 240v TO COMPRESSOR NEUTRAL WHITE 115v DARK BLUE 220 240v BLUE 115V LIGHT BLUE 220V 240V TO COMPRESSOR 1 10 CONTROL BOARD ZONE TEMP FUSE 1...

Страница 39: ...nt of a part the servicer is authorized to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial numb...

Страница 40: ...shes 12 represents the production month In most cases warranty status can be verified by the production date information within the serial number Alternatively a Proof of Purchase or equivalent may su...

Страница 41: ...4 00 14 Grille w screws 80 54230 00 15 Hinges 2 w screws 80 54233 00 16 LED light strip and cover assy 80 54000 00 17 Leg Levelers 4 80 54201 00 18 Magnet with bkt and screws 2 80 54250 00 19 Main boa...

Страница 42: ...s will be shipped at no charge after U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U L...

Страница 43: ...federal state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder type fire extinguisher...

Страница 44: ...equipment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing a...

Страница 45: ...he system prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing the system must be pur...

Страница 46: ...e access port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the...

Страница 47: ...Lower than normal Warm near room temperature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near ro...

Страница 48: ...st strap that is grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and...

Страница 49: ...utputs located on the relay power board Included in this section are some diagnostic tips and of course if additional help is required please contact the U Line Corp Customer Care Facility at 1 800 77...

Страница 50: ...efer to 14 Error Log in Service Mode Thermistor failure Check Error Log in Service Mode OHM thermistor Frost Buildup Inside Unit Door Ajar or Restricted from Closing Check door clearance to adjoining...

Страница 51: ...into overload The compressor will automatically deactivate during an overload and will remain deactivated until the overload switch cools This could take some time It is important to allow the compres...

Страница 52: ...d magnetic force pulls the reed to its contact and closes the circuit which turns the light and display off When the door is open the reed pulls away from the contact and opens the circuit If the door...

Страница 53: ...gates through service menu LED activated with button activation 3 Down Button Decreases temperature Navigates through service menu LED activated with button activation 4 Light Button Activates light f...

Страница 54: ...ter exit this mode hold the light key and the power key for 5 seconds The display will flash once and beep and the degree symbol will begin to flash When the degree symbol is flashing the unit will al...

Страница 55: ...efrigerator section 13 ADJUST DEFROST DURATION 0 TO 99 MINUTES The length of the defrost can be adjusted 0 to 99 minutes long The other defrost parameters still apply Lengthening a defrost may cause h...

Страница 56: ...e two digit model number of the specific unit See model list table 21 LIGHT ALL LED SEGMENTS This will illuminate all the LEDs on the display to ensure they work properly 22 VIEW DEFROST CYCLES Displa...

Страница 57: ...conds use the up and down arrow buttons to select the appropriate model number See Above Model List 5 Press the light bulb button once 6 The display will blink and then will appear as the programmed d...

Страница 58: ...ator Fan Condenser Fan N A N A 2218R N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2218RGL N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2218WC...

Страница 59: ...thermistor connection you should replace the thermistor and the thermistor harness Thermistor error information can be found in the Control Operations Service section This unit has two thermistors The...

Страница 60: ...C 1224 RF 12 45 15 9 1215 1224 2218 2245 2224 2260 WC ZWC 12 45 45 7 1215 1224 2218 2245 2224 2260 R RSOD RDC BEV DC DWR RGL 12 45 42 6 CO29 F 12 18 n a CO1224 F 12 18 45 7 1224FZR Freezer Mode 6 45...

Страница 61: ...nty arising by operation of law U Line will not be responsible for any consequential or incidental damages arising from the breach of these warranties or any other warranty whether express implied or...