USER GUIDE

 Control Operation - Service 4

u-line.com

SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • 

SERVICE

SERVICE MODE GUIDE 

1.

THERMISTOR 1 — TEMPERATURE

This will show the pure thermistor reading with no 
offsets taken into account. When placed in ice water 
this thermistor should read 32°F in this menu option.

2.

THERMISTOR 2

View thermistor #2 temperature minus the offset.

3. Does not apply to this model.

4. Does not apply to this model.

5.

ADJUST THERMISTOR 1 OFFSET

This calibration is only to be used if actual temperature 
at thermistor #1 is off from set point.

By adjusting the offset higher we can force the unit to 
drive the temperature down below the set point. 
(example: adjusting from 0 to +2 will drop the unit 
temperature 2 degrees) 

DO NOT MAKE AN ADJUSTMENT TO THIS WITHOUT 
CONTACTING TECH LINE.

6.

ADJUST THERMISTOR 2 OFFSET

Call tech line before adjusting.

7. Does not apply to this model.

8. Does not apply to this model.

9. VIEW THERMISTOR 2 SET POINT MINUS 

OFFSET

10.Does not apply to this model.

11.Does not apply to this model.

12.

DEFROST INTERVAL ADJUST — 3 TO 24 
HOURS

This will adjust the interval between defrosts from 3 to 
24 hours. Adjusting from the factory settings may 
cause undesired temperature in the refrigerator 
section.

13.

DEFROST LENGTH ADJUSTMENT — UP TO 
99 MINUTES

The length of the defrost can be adjusted up to 99 
minutes long. The other defrost parameters still apply. 
Lengthening a defrost may cause higher than normal 
temperatures in the refrigerator section.

14.

ERROR LOG

A list of the errors in the order they occurred will scroll 
once on the display. Repeat if desired. Once viewed, 
perform option 15, to clear the errors from memory.

15.

CLEAR ERROR LOG

Perform this operation after checking the errors.

16.

ADJUST THERMISTOR 1 DIFFERENTIAL

This number should not be adjusted.

17.

FAN DELAY ON=

“Fan Delay On” is the amount of time in minutes the 
fan will be delayed from starting from the beginning of 
a cooling cycle.

18.

FAN DELAY OFF=

“Fan Delay Off” is the amount of time in minutes the 
fan will continue to run at the end of a cooling cycle.

Содержание 2218WC 18 inch Wine Captain

Страница 1: ...USER GUIDE SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE 2000 Series 2218WC 18 Wine Captain Model RIGHT PRODUCT RIGHT PLACE RIGHT TEMPERATURE SINCE 1962...

Страница 2: ...tallation Door Swing Door Stop Door Adjust Wood Trim Finishing Operating Instructions First Use Control Operation Sabbath Mode Airflow and Product Loading U Line Wine Guide Recommended Wine Storage Ma...

Страница 3: ...ship to you PRODUCT INFORMATION Looking for additional information on your product User Guides Quick Reference Guides CAD Drawings Compliance Documentation and Product Warranty information are all ava...

Страница 4: ...jury or death WARNING Warning means that failure to follow this safety statement could result in serious personal injury or death CAUTION Caution means that failure to follow this safety statement may...

Страница 5: ...freezer take off the doors and leave shelves in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulati...

Страница 6: ...F 10 C and 100 F 38 C Higher ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of di...

Страница 7: ...use an extension cord to connect power to the unit Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded...

Страница 8: ...ides or rear However the front grille plinth strip base fascia must NOT be obstructed CAUTION Unit can NOT be installed behind a closed cabinet door U Line products are designed and manufactured to be...

Страница 9: ...Dimensions 1 u line com SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Product Dimensions 33 11 16 to 34 11 16 856 mm to 881 mm 17 3 4 450 mm 3 5 16 84 mm Not Including Han...

Страница 10: ...ut Dimensions in each unit s Installation Guide Each door can be opened individually one at a time without interference However to ensure unobstructed door swing opening both doors at the same time 1...

Страница 11: ...using a 2 Phillips head screwdriver 3 Completely slide the unit into its position in the cabinet Be certain unit height is properly adjusted See GENERAL INSTALLATION 4 Open door completely Make certa...

Страница 12: ...GRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE 5 Using a 3 32 drill bit drill 3 pilot holes 5 8 16 mm deep into cabinetry frame using the anti tip bracket as a template 6 Install the 3 remaining 3...

Страница 13: ...a total unit rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Adju...

Страница 14: ...ia panel to match your surrounding furniture Finish front back and edges to prevent warping Carefully follow the manufacturer s recommendations for finish application and cure times 3 Apply double sid...

Страница 15: ...e fascia When using the unit the grille plinth strip base fascia must be installed WARNING DO NOT touch the condenser fins The condenser fins are SHARP and can be easily damaged Removing the grille pl...

Страница 16: ...allow the door to open 90 Allow for additional space for any knobs or pulls installed on the integrated panel frame Stainless Steel models that are installed adjacent to a wall require 2 1 4 57 mm do...

Страница 17: ...approximately 90 2 Remove hinge cover by lifting top and bottom of hinge cover and sliding the cover inwards to remove from hinge 3 Once cover is removed slide hinge pin into hole as shown Pin should...

Страница 18: ...et Also make sure the door gasket is not pinched on the hinge side of the door CAUTION Do not attempt to use the door to raise or pivot your unit This would put excessive stress on the hinge system Re...

Страница 19: ...aining or finishing to prevent permanent damage to the inner liner of the unit Allow stain or finish to dry thoroughly at least 24 hours for each coat following the product manufacturer s instructions...

Страница 20: ...at the factory Initial startup requires no adjustments NOTICE U Line recommends allowing the unit to run overnight before loading with product When plugged in the unit will begin operating under the f...

Страница 21: ...TROL FUNCTION GUIDE FUNCTION COMMAND DISPLAY OPTIONS ON OFF Press and release Unit will immediately turn ON or OFF Toggle lights Press and release to leave interior light on for 3 hours Glass door win...

Страница 22: ...ntain internal temperatures and set points View a full list of Star K certified U Line units at www star k org To enable Sabbath Mode 1 Press 4 and hold for ten seconds and release the F C symbol will...

Страница 23: ...t any time or the unit will not perform as expected When loading your unit leave space between the internal fans or vents and product loaded Anything blocking the required airflow circulation will res...

Страница 24: ...he subject of wine is your own palate Do not be afraid to make mistakes Experiment discover but most of all enjoy yourself and your new U Line product Guide To Common Styles Of Wine Matching Food and...

Страница 25: ...he presentation of the cork has a rich and fascinating history dating back to the late 1800 s A phylloxera root louse devastation to the vineyards severely limited the supply of great wines Restaurate...

Страница 26: ...hat sediment is left undistributed and particles are not suspended vibration in a storage environment is not an issue Wines can become flat or tired when voids and vacuums are created inside the wine...

Страница 27: ...n Each U Line Wine Captain model is designed to impress and inspire anyone with an interest in wine by providing cellar conditions in stylish undercounter units U Line Wine Captain models offer stable...

Страница 28: ...so the wine remains in contact with the cork which ensures the cork does not become dry U Line recommends arranging wine bottles as shown in the illustrations below Racks 1 through 5 Rack 6 Rack 7 La...

Страница 29: ...lems Using abrasive pads such as Scotchbrite will cause the graining in the stainless steel to become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete...

Страница 30: ...he drain pan and possibly damaging water sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in...

Страница 31: ...hen necessary Depending on environmental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric current to the unit before cleaning the condenser NOTICE DO NOT use any...

Страница 32: ...e cabinet NOTICE Do not remove the track rails from the cabinet To insert wine racks in the cabinet 1 Align the left and right rack channels with the tracks in the cabinet Ensure an even track engagem...

Страница 33: ...it is returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open...

Страница 34: ...s listed Compressor The compressor makes a hum or pulsing sound that may be heard when it operates Evaporator Refrigerant flowing through an evaporator may sound like boiling liquid Condenser Fan Air...

Страница 35: ...r openings and the time the door is open The time the internal light is illuminated This mainly affects product on the top rack or shelf Digital Display Shows 1 16 or 99 A factory test mode may be ena...

Страница 36: ...r you can register on line at www u lineservice com 3 The warranty listed above does not apply to floor display models The warranty for these models shall be 30 days from the date of retail purchase a...

Страница 37: ...able warranty period 8 THIS LIMITED WARRANTY IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTIC...

Страница 38: ...240V TO COMPRESSOR 1 10 CONTROL BOARD ZONE TEMP FUSE T O D I S P L A Y 115 VOLT PLUG 220 240 VOLT PLUG 16 8 9 1 NEUTRAL WHITE 115v DARK BLUE 220 240v TO COMPRESSOR 6 1 10 5 T O U S B ZONE EVAP DOOR SW...

Страница 39: ...roduct equipped with a drain pump the drain pump must be returned along with the unit regardless of the drain pump manufacturer To complete the damage claim process for the customer please forward the...

Страница 40: ...dashes 12 represents the production month In most cases warranty status can be verified by the production date information within the serial number Alternatively a Proof of Purchase or equivalent may...

Страница 41: ...r U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U Line requires the return of original...

Страница 42: ...ge Lower than normal Warm near room temperature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near...

Страница 43: ...ist strap that is grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and...

Страница 44: ...d Remedy Not Cooling Compressor overheating Verify proper air flow through condenser Is condenser clean Confirm condenser fan operation Confirm proper compressor operating voltage Use 19 Component Tes...

Страница 45: ...ult If the unit does not or seems to not power on follow the flow chart below to help diagnose the issue Before beginning it is important to first verify the unit is not simply set to sabbath mode Sys...

Страница 46: ...onents have been ruled out as being faulty but the unit continues to have operating issues it is most likely due to a configuration error Configuration errors can be cleared by restoring the unit to i...

Страница 47: ...unit will otherwise operate normally Evaporator thermistor errors will be displayed in the error log Always assure that all thermistor connections are clean and dry Whenever opening a thermistor conne...

Страница 48: ...emperature Navigates through service menu LED activated with button activation 4 Light Button Activates light for 3 hours on select models Used to select items in service menu LED activated with butto...

Страница 49: ...l will begin to flash When the degree symbol is flashing the unit will allow the use of the control for demonstrations The unit can be left in this mode indefinitely To exit this mode interrupt power...

Страница 50: ...light icon to enter and save change 14 Display error log Use up down to access and light bulb key to view 15 Clear error log Use up down to access and light bulb key to clear 16 View thermistor 1 dif...

Страница 51: ...odel 9 VIEW THERMISTOR 2 SET POINT MINUS OFFSET 10 Does not apply to this model 11 Does not apply to this model 12 DEFROST INTERVAL ADJUST 3 TO 24 HOURS This will adjust the interval between defrosts...

Страница 52: ...24 hours 23 COMPRESSOR RUNTIME BASED ON LAST CYCLE This will show the number of minutes the compressor has run in the prior cycle or current cycle if the compressor was running when service mode was e...

Страница 53: ...Celsius F C Defrost Duration Minutes 45 Next Defrost Hours 12 Thermistor Four OFFSET 0 Thermistor Three OFFSET 0 Thermistor Two OFFSET 0 Thermistor One OFFSET 2 Thermistor One Differential Up 1 Thermi...

Страница 54: ...DURATION 0 TO 99 MINUTES UP DOWN TO SELECT LIGHT ICON TO ENTER AND SAVE CHANGE 14 DISPLAY ERROR LOG USE UP DOWN TO ACCESS AND LIGHT BULB KEY TO VIEW 15 CLEAR ERROR LOG USE UP DOWN TO ACCESS AND LIGHT...

Страница 55: ...shorted E9 Door open error PI Pump Circuit open Programming the unit to correct model number 1 Unplug unit and install new board 2 Push and hold the hidden icon 3 Plug the unit in 4 Release the hidde...

Страница 56: ...ight hand side wall It is used to maintain the operating temperature within the unit Thermistor two is located on the back of the evaporator It is used for defrost purposes Thermistor three is located...

Страница 57: ...SERVICE Defrost These units are frost free technology Model Hrs Between Defrost Time Length Minutes Stop Point 2218R WC 12 45 42 2224BEV R WC 12 45 42 3018R WC 12 45 40 1224DWR 12 45 42 1224WC 12 45 4...

Страница 58: ...e air and clear any condensation that may have appeared on glass doors and shelves Note If the unit is set to sabbath mode the evaporator fan will no longer respond to the state of the door switch In...

Страница 59: ...n wire NOTICE Fan must be oriented to pull air in through lower evaporator cover vents and push air out at fan mounting location 15 Installation is the reverse of removal 16 Care must be taken to assu...

Отзывы: